background image

Manual

2100-573A

Page

7 of 21

SHIPPING DAMAGE

Upon receipt of equipment, the carton should be checked
for external signs of shipping damage.  If damage is
found, the receiving party must contact the last carrier
immediately, preferably in writing, requesting inspection
by the carrier’s agent.

GENERAL

The equipment covered in this manual is to be installed
by trained, experienced service and installation
technicians.

The refrigerant system is completely assembled and
charged.  All internal wiring is complete.

The unit is designed for use with or without duct work.
Flanges are provided for attaching the supply and return
ducts.

These instructions explain the recommended method to
install the air cooled self-contained unit and the
electrical wiring connections to the unit.

These instructions and any instructions packaged with
any separate equipment required to make up the entire
air conditioning system should be carefully read before
beginning the installation.  Note particularly “Starting
Procedure” and any tags and/or labels attached to the
equipment.

While these instructions are intended as a general
recommended guide, they do not supersede any national
and/or local codes in any way.  Authorities having
jurisdiction should be consulted before the installation is
made.  See Page 3 for information on codes and
standards.

Size of unit for a proposed installation should be based
on heat loss calculation made according to methods of
Air Conditioning Contractors of America (ACCA).  The
air duct should be installed in accordance with the
Standards of the National Fire Protection Association for
the Installation of Air Conditioning and Ventilating
Systems of Other Than Residence Type, NFPA No.
90A, and Residence Type Warm Air Heating and Air
Conditioning Systems, NFPA No. 90B.  Where local
regulations are at a variance with instructions, installer
should adhere to local codes.

DUCT WORK

All duct work, supply and return, must be properly sized
for the design airflow requirement of the equipment.  Air
Conditioning Contractors of America (ACCA) is an
excellent guide to proper sizing.  All duct work or
portions thereof not in the conditioned space should be
properly insulated in order to both conserve energy and
prevent condensation or moisture damage.

Refer to Table 6 for maximum static pressure available
for duct design.

Design the duct work according to methods given by the
Air Conditioning Contractors of America (ACCA).
When duct runs through unheated spaces, it should be
insulated with a minimum of 1-inch of insulation.  Use
insulation with a vapor barrier on the outside of the
insulation.  Flexible joints should be used to connect the
duct work to the equipment in order to keep the noise
transmission to a minimum.

A 1/4 inch clearance to combustible material for the first
three feet of duct attached to the outlet air frame is
required.  See Wall Mounting Instructions and Figures 3
and 4 for further details.

Ducts through the walls must be insulated and all joints
taped or sealed to prevent air or moisture entering the
wall cavity.

Any grille that meets the 5/8 inch louver criteria, may be
used.  It is recommended that Bard Return Air Grille Kit
RG-5 or RFG-5 be installed when no return duct is used.
Contact distributor or factory for ordering information.
If using a return air filter grille, filters must be of
sufficient size to allow a maximum velocity of 400 fpm.

NOTE: If no return air duct is used, applicable

installation codes may limit this cabinet to
installation only in a single story structure.

FILTERS

A 2-inch pleated MERV 8 filter is supplied with each
unit.  The filter slides into position making it easy to
service.  This filter can be serviced from the outside by
removing the filter access panel.

CONDENSATE DRAIN

A plastic drain hose extends from the drain pan at the top
of the unit down to the unit base.  There are openings in
the unit base for the drain hose to pass through.  In the
event the drain hose is connected to a drain system of
some type, it must be an open or vented type system to
assure proper drainage.

              CAUTION

Some installations may not require any return
air duct.  A return air grille is required with
installations not requiring a return air duct.
The spacing between louvers on the grille
shall not be larger than 5/8 inches.                

Содержание HA4S3

Страница 1: ...3A Supersedes 2100 573 File Volume III Tab 16 Date 07 09 12 Bard Manufacturing Company Inc Bryan Ohio 43506 Since 1914 Moving ahead just as planned 0 6 WALL MOUNTED PACKAGED AIR CONDITIONER INSTALLATION INSTRUCTIONS Models HA4S3 HL4S2 HA5S3 HL5S2 ...

Страница 2: ...ll Mounting Information 8 Mounting the Unit 8 Typical Installations 8 Wiring Main Power 8 9 12 Wiring Low Voltage Wiring 12 Dirty Filter Switch Relay 12 Start Up General 13 Topping Off System Charge 13 Safety Practices 13 Important Installer Note 14 Crankcase Heaters 14 High Low Pressure Switch 14 Service Hints 15 Compressor Control Module 15 Adjustments 16 Motor Start Device 16 Pressure Service P...

Страница 3: ...d Manual N Summer Air Conditioning Low Pressure Low Velocity ACCA Manual D or Duct System Design for Winter Manual Q and Summer Air Conditioning FOR MORE INFORMATION CONTACT THESE PUBLISHERS ACCA Air Conditioning Contractors of America 1712 New Hampshire Ave N W Washington DC 20009 Telephone 202 483 9370 Fax 202 234 4721 ANSI American National Standards Institute 11 West Street 13th Floor New York...

Страница 4: ... 2 n i e l b a l i a v a e r a s r e t a e h c i r t c e l e e s e h T 1 See Table 3 for Heater Availability by Model VOLTS PHASE A 230 208 1 KW 0Z No KW w Circuit Breaker or Pull Disconnect 05 5 KW 08 8 KW 10 10 KW 15 15 KW VENTILATION OPTIONS B Blank off Plate Standard COLOR OPTIONS X Beige Standard 4 Buckeye Gray 5 Desert Brown 8 Dark Bronze A Aluminum S Stainless Steel OUTLET OPTIONS X Front S...

Страница 5: ...ockable 4 Pitch Entrance Disconnect Rain Hood Air Built In Inlet Access Panel Low Voltage C Breaker High Voltage Electrical Drain Side View 2 13 C D K J A H I MIS 2762 Electrical Location Shipping Optional Mounting Supply Air Opening Side Wall Return Air Opening Entrances Brackets Built In Top Rain Flashing Bottom Installation Bracket Back View E 44 M T R S2 P S2 L O S1 Q N S1 S1 B I A C K 2 13 H ...

Страница 6: ... 8 8 7 3 7 3 6 2 2 5 5 4 5 4 0 3 0 6 8 8 0 1 6 0 1 0 1 0 1 0 1 S 5 L A H Z 0 A 5 0 A 8 0 A 0 1 A 5 1 A 1 8 0 2 0 3 2 1 1 1 2 r o 1 2 r o 1 4 4 4 4 3 5 3 6 9 8 0 5 0 5 0 6 0 7 0 9 8 8 6 6 3 0 1 0 1 0 1 8 8 4 4 4 4 6 2 2 5 0 5 0 5 0 3 0 6 8 8 0 1 6 0 1 0 1 0 1 0 1 1 Maximum size of the time delay fuse or HACR type circuit breaker for protection of field wiring conductors 2 Based on 75 C copper wire ...

Страница 7: ...a ACCA is an excellent guide to proper sizing All duct work or portions thereof not in the conditioned space should be properly insulated in order to both conserve energy and prevent condensation or moisture damage Refer to Table 6 for maximum static pressure available for duct design Design the duct work according to methods given by the Air Conditioning Contractors of America ACCA When duct runs...

Страница 8: ... rigidity the return air and supply air frames or collars can be drilled and screwed or welded to the structural wall itself depending upon wall construction Be sure to observe required clearance if combustible wall 9 On side by side installations maintain a minimum of 20 inches clearance on right side to allow access to heat strips and control panel and to allow proper airflow to the outdoor coil...

Страница 9: ...16 16 16 1 7 8 6 1 2 6 1 2 2 1 8 7 8 1 3 4 Typ 4 Typ 6 1 2 30 E 16 A C C 3 1 8 B Wall Opening and Hole Location View RETURN AIR 1 REQUIRED DIMENSIONS TO MAINTAIN 1 4 MIN CLEARANCE FROM COMBUSTIBLE MATERIALS REQUIRED DIMENSIONS TO MAINTAIN 29 DUCT COMBUSTIBLE MATERIALS A B C D E 30 1 2 10 1 2 6 1 4 1 1 4 29 3 4 32 12 5 1 2 2 NOTES WALL STRUCTURE 1 SUPPLY AIR IT IS RECOMMENDED THAT A BEAD OF OPENING...

Страница 10: ...Y AIR MIS 548 A SIDE VIEW I A C K E 1 000 B 1 000 SUPPLY DUCT OVER FRAME INTERIOR FINISHED WALL ALL AROUND DUCT FRAMING MATERIAL EXTERIOR FINISH WALL OPENING FOR ACTUAL DIMENSIONS 2 x 4 S 2 x 6 S OR STRUCTURAL STEEL ATTACH TO TOP 1 000 CLEARANCE 1 000 CLEARANCE PLATE OF WALL C SEE UNIT DIMENSIONS FIGURE 2 OPENING RETURN DUCT 2 x 6 ATTACH TO BOTTOM OVER FRAME PLATE OF WALL L THIS STRUCTURAL MEMBER ...

Страница 11: ... WALL OPENING W GRILLE SUPPLY DUCT MAYBE LOCATED IN AN ATTIC OR BELOW CEILING RAFTERS AS SHOWN CEILING RAIN RETURN AIR SLEEVE WALL SUPPLY AIR DUCT RAFTERS RAFTERS RETURN AIR OPENING W GRILLE RAIN FALSE WALL INSTALLATION DUCTED SUPPLY GRILLE OUTSIDE SPACE FALSE WALL RETURN AIR GRILLE OUTSIDE OR BELOW CEILING RAFTERS AS SHOWN FINISHED CEILING SURFACE RAIN FLASHING RAIN FLASHING RETURN AT UNIT NO DUC...

Страница 12: ...208V taps are TAP RANGE 240 253 216 208 220 187 NOTE The voltage should be measured at the field power connection point in the unit and while the unit is operating at full load maximum amperage operating condition For wiring size and connections refer to MV4000 Controller Manual 2100 571 DIRTY FILTER SWITCH RELAY These units include a dirty filter switch and relay The alarm output of relay is norm...

Страница 13: ...frigerant composition during multiple leaks and recharges R 410A refrigerant is close to being an azeotropic blend it behaves like a pure compound or single component refrigerant The remaining refrigerant charge in the system may be used after leaks have occurred and then top off the charge by utilizing the pressure charts on the inner control panel cover as a guideline REMEMBER When adding R 410A...

Страница 14: ... SWITCH All models covered by this Manual are supplied with a remote reset high pressure switch and low pressure switch If tripped this pressure switch may be reset by turning the thermostat off then back on again IMPORTANT These procedures must be followed at initial start up and at any time power has been removed for 12 hours or longer To prevent compressor damage which may result from the prese...

Страница 15: ...utdown the delay or break timer starts and prevents restart until the delay on break and delay on make periods have expired During routine operation of the unit with no power interruptions the compressor will operate on demand with no delay High Pressure Switch and Lockout Sequence If the high pressure switch opens the compressor contactor will de energize immediately The lockout timer will go int...

Страница 16: ...r low cool when utilizing the charts Alarm Relay Output Alarm terminal is output connection for applications where alarm relay is employed This terminal is powered whenever compressor is locked out due to HPC or LPC sequences as described NOTE Both high and low pressure switch controls are inherently automatic reset devices The high pressure switch and low pressure switch cut out and cut in settin...

Страница 17: ...oid returns to its original position 3 If clicks can t be heard shut off power and remove the control circuit molded plug from the compressor and measure the solenoid coil resistance The resistance should be 32 to 60 ohms depending on compressor temperature 4 Next check the molded plug Voltage check Apply control voltage to the plug wires 18 to 28 volt ac The measured dc voltage at the female conn...

Страница 18: ... A R E P M E T E R U S S E R P 0 5 o F 5 5 o F 0 6 o F 5 6 o F 0 7 o F 5 7 o F 0 8 o F 5 8 o F 0 9 o F 5 9 o F 0 0 1 o F 5 0 1 o F 0 1 1 o F 5 1 1 o F S 4 A H S 4 L H B D 5 7 B W 2 6 E D I S W O L E D I S H G I H 2 2 1 4 8 1 4 2 1 1 0 2 5 2 1 8 1 2 7 2 1 6 3 2 9 2 1 4 5 2 1 3 1 2 7 2 1 3 1 1 9 2 2 3 1 2 1 3 3 3 1 5 3 3 4 3 1 9 5 3 5 3 1 1 8 3 7 3 1 7 0 4 9 3 1 5 3 4 1 4 1 3 6 4 B D 0 8 B W 7 6 E D...

Страница 19: ... it s air noise cabinet duct or motor noise interview customer if necessary Air noise High static creating high blower speed Is airflow set properly Does removing filter cause blower to slow down Check filter Use low pressure drop filter Check correct duct restrictions Symptom Cause Procedure Noisy blower or cabinet Check for loose blower housing panels etc High static creating high blower speed C...

Страница 20: ...lication Refer to the manufacturer s authorized replacement list USING THE WRONG CONTROL WILL RESULT IN IMPROPER OR NO BLOWER OPERATION Orient the control module so that the 3 wire motor plug can be inserted into the socket in the control Carefully insert the plug and press it into the socket until it latches A SLIGHT CLICK WILL BE HEARD WHEN PROPERLY INSERTED Finish installing the replacement con...

Страница 21: ...1 M F C S 4 L A H 0 2 0 0 8 0 5 2 8 0 0 1 1 0 0 5 1 0 0 1 1 0 0 5 1 S 5 L A H 0 2 0 0 8 0 0 5 8 0 0 3 1 0 0 7 1 0 0 1 1 0 0 5 1 TABLE 7 OPTIONAL ACCESSORIES HA4S3KA HA5S3KA L E D O M N O I T P I R C S E D 5 0 A S 4 A W H E e g a k c a P r e t a e H X 0 1 A S 4 A W H E e g a k c a P r e t a e H X 5 1 A S 4 A W H E e g a k c a P r e t a e H X 5 0 A S 5 A W H E e g a k c a P r e t a e H X 8 0 A S 5 A...

Отзывы: