Manual 2100-585A
Page 18 of 19
TABLE 4
RECOMMENDED AIRFLOW
TABLE 5
INDOOR BLOWER PERFORMANCE
TABLE 6
ELECTRIC HEAT
Speed
H42/48
H60
High
Low
High
Low
ESP
(Inch H20)
Dry Coil
Wet Coil
Dry Coil
Wet Coil
Dry Coil
Wet Coil
Dry Coil
Wet Coil
0.0
1850
1800
1605
1555
2080
2015
1505
1460
0.1
1775
1725
1545
1500
2020
1960
1450
1405
0.2
1685
1640
1460
1415
1925
1865
1395
1355
0.3
1590
1550
1390
1345
1870
1815
1340
1300
0.4
1495
1460
1310
1270
1755
1705
1225
1185
0.5
1400
1365
1225
1185
1660
1610
1125
1085
Model
Rated
CFM *
Rated
ESP *
Recommended
Airflow Range
Factory Speed
Connection
H42A, H42L
1400
.45
1600 - 1150
High
H48A, H48L
1550
.30
1750 - 1285
High
H60A, H60L
1700
.40
1950 - 1375
High
Models
240V-1
208V-1
KW
Amps
BTUH
Amps
BTUH
5
20.8
17065
18.1
12800
10
41.6
34130
36.2
25600
15
62.5
51250
54.0
38400
* Rated CFM and ESP on high speed tap.