background image

Manual 2100-568A 

Page 

5 of 23

duct WOrK

All duct work, supply and return, must be properly sized 

for the design airflow requirement of the equipment.  

Air Conditioning Contractors of America (ACCA) is an 
excellent guide to proper sizing.  All duct work or portions 
thereof not in the conditioned space should be properly 
insulated in order to both conserve energy and prevent 
condensation or moisture damage.

Refer to Maximum ESP of operation Electric Heat Table 7.

Design the duct work according to methods given by the 
Air Conditioning Contractors of America (ACCA).  When 
duct runs through unheated spaces, it should be insulated 
with a minimum of one inch of insulation.  Use insulation 
with a vapor barrier on the outside of the insulation.  
Flexible joints should be used to connect the duct work to 
the equipment in order to keep the noise transmission to a 
minimum.

For model series H42, H48 and H60 a 1/4 inch clearance to 

combustible material for the first three feet of duct attached 

to the outlet air frame is required.  See Wall Mounting 
Instructions and Figures 3 and 4 for further details.

Ducts through the walls must be insulated and all joints 
taped or sealed to prevent air or moisture entering the wall 
cavity.

Some installations may not require any return air duct.  A 
metallic return air grille is required with installations not 
requiring a return air duct.  The spacing between louvers on 
the grille shall not be larger than 5/8 inch.

Any grille that meets with 5/8 inch louver criteria may be 
used.  It is recommended that Bard Return Air Grille Kit 
RG5 or RFG5 be installed when no return duct is used.  
Contact distributor or factory for ordering information.  If 

using a return air filter grille, filters must be of sufficient 

size to allow a maximum velocity of 400 fpm.

NOTE:  If no return air duct is used, applicable installation  
 

codes may limit this cabinet to installation only in a  

 

single story structure.

filters

A 1-inch throwaway filter is standard with each unit.  

The filter slides into position making it easy to service.  

This filter can be serviced from the outside by removing 

the filter access panel.  A 1-inch washable filter and 

2-inch pleated filter are also available as optional 

accessories.  The internal filter brackets are adjustable 

to accommodate the 2-inch filter by bending two (2) 

tabs down on each side of the filter support bracket.

fresh air intaKe

All units are built with fresh air inlet slots punched in 
the service door.

If the unit is equipped with a fresh air damper assembly, 
the assembly is shipped already attached to the unit.  
The damper blade is locked in the closed position.  
To allow the damper to operate, the maximum and 
minimum blade position stops must be installed.  See 
Figure 1.

All capacity, efficiency and cost of operation 

information is based upon the fresh air blank-off plate 
in place and is recommended for maximum energy 

efficiency.

The blank-off plate is available upon request from the 
factory and is installed in place of the fresh air damper 
shipped with each unit.

cOndensate drain 

A plastic drain hose extends from the drain pan at 
the top of the unit down to the unit base.  There are 
openings in the unit base for the drain hose to pass 
through.  In the event the drain hose is connected to a 
drain system of some type, it must be an open or vented 
type system to assure proper drainage.

fiGure  1

fresh air damPer

Содержание H42A1

Страница 1: ...UCTIONS WALL MOUNTED PACKAGE AIR CONDITIONERS MODELS H42A1 H42L1 H48A1 H48L1 H60A1 H60L1 Manual 2100 568A Supersedes 2100 568 File Volume III Tab 16 Date 04 12 12 Bard Manufacturing Company Inc Bryan Ohio 43506 Since 1914 Moving ahead just as planned ...

Страница 2: ...ble 10 Vent Control Options 23 Getting Other Information and Publications 3 Wall Mount General Information Wall Mount Model Nomenclature 4 Shipping Damage 4 General 4 Duct Work 5 Filters 5 Fresh Air Intake 5 Condensate Drain 5 Installation Instructions Wall Mounting Information 6 Mounting the Unit 6 Clearances Required 6 Minimum Clearances 6 Wiring Main Power 12 Wiring Low Voltage Wiring 12 Dirty ...

Страница 3: ...g Duct Design for Residential ACCA Manual D Winter and Summer Air Conditioning and Equipment Selection For more information contact these publishers ACCA Air Conditioning Contractors of America 1712 New Hampshire Ave N W Washington DC 20009 Telephone 202 483 9370 Fax 202 234 4721 ANSI American National Standards Institute 11 West Street 13th Floor New York NY 10036 Telephone 212 642 4900 Fax 212 3...

Страница 4: ...mmended guide they do not supersede any national and or local codes in any way Authorities having jurisdiction should be consulted before the installation is made See Page 3 for information on codes and standards Size of unit for a proposed installation should be based on heat loss calculation made according to methods of Air Conditioning Contractors of America ACCA The air duct should be installe...

Страница 5: ...hen no return duct is used Contact distributor or factory for ordering information If using a return air filter grille filters must be of sufficient size to allow a maximum velocity of 400 fpm NOTE If no return air duct is used applicable installation codes may limit this cabinet to installation only in a single story structure FILTERS A 1 inch throwaway filter is standard with each unit The filte...

Страница 6: ...l surface at both sides A bottom mounting bracket attached to skid for shipping is provided for ease of installation but is not required 2 The unit itself is suitable for 0 inch clearance but the supply air duct flange and the first 3 feet of supply air duct require a minimum of 1 4 inch clearance to combustible material for model series H42 H48 and H60 However it is generally recommended that a 1...

Страница 7: ...Air Air Outlet Front View Return Air Opening Cond 1 Back View Condenser Bracket Installation Bottom Built In Brackets Mounting Side Wall Location Shipping Flashing Entrances Electrical Optional Entrance Electrical High Voltage Entrance Electrical Air Ventilation Door Vent Option Panel Filter Access Low Voltage Top Rain Lockable Access Panel Heat Electric Disconnect Panel Access Heater C Breaker Bu...

Страница 8: ... 1 4 29 3 4 32 12 5 1 2 2 NOTES WALL STRUCTURE 1 SUPPLY AIR IT IS RECOMMENDED THAT A BEAD OF OPENING Right Side View RAIN FLASHING SILICONE CAULKING BE PLACED BEHIND RECOMMENDED 1 CLEARANCE FROM THE SIDE MOUNTING FLANGES AND UNDER TOP FLASHING AT TIME OF INSTALLATION TOP PANEL HEATER ACCESS FOUR SIDES OF SUPPLY AIR DUCT IS REQUIRED FROM COMBUSTABLE WALL 1 4 CLEARANCE ON ALL MATERIALS Supply Openin...

Страница 9: ...tible materials This is required for the first 3 feet of ducting It is important to insure that the 1 4 inch minimum spacing is maintained at all points Failure to do this could result in overheating the combustible material and may result in a fire causing damage injury or death NOTE 1 SIDE SECTION VIEW OF SUPPLY AIR DUCT FOR WALL MOUNTED UNIT SHOWING 1 4 INCH CLEARANCE TO COMBUSTIBLE SURFACES ...

Страница 10: ...1 000 I A C K E 1 000 B 1 000 I A C K E 1 000 B 1 000 I A C K E 1 000 B 1 000 I A C K E 1 000 B 1 000 I A C K E 1 000 B 1 000 I A C K E 1 000 B 1 000 I A C K E 1 000 B 1 000 I A C K E 1 000 B 1 000 I A C K E 1 000 B 1 000 I A C K E 1 000 B 1 000 I A C K E 1 000 B 1 000 RETURN DUCT L 2 x 6 PLATE OF WALL ATTACH TO BOTTOM 1 000 CLEARANCE C STRUCTURAL STEEL OVER FRAME 2 x 4 S 2 x 6 S OR EXTERIOR FINIS...

Страница 11: ... WALL OPENING W GRILLE SUPPLY DUCT MAYBE LOCATED IN AN ATTIC OR BELOW CEILING RAFTERS AS SHOWN CEILING RAIN RETURN AIR SLEEVE WALL SUPPLY AIR DUCT RAFTERS RAFTERS RETURN AIR OPENING W GRILLE RAIN FALSE WALL INSTALLATION DUCTED SUPPLY GRILLE OUTSIDE SPACE FALSE WALL RETURN AIR GRILLE OUTSIDE OR BELOW CEILING RAFTERS AS SHOWN FINISHED CEILING SURFACE RAIN FLASHING RAIN FLASHING RETURN AT UNIT NO DUC...

Страница 12: ...eventing entry See Start Up section for important information on three phase scroll compressor start ups See Tables 3 4 for Electrical Specifications Low Voltage Connection These units use a 24 volt AC low voltage circuit The R terminal is the hot terminal and the C terminal is grounded G terminal is the fan input Y terminal is the compressor input for cooling 1 Stage units only W1 terminal is the...

Страница 13: ...ltiple leaks and recharges R 410A refrigerant is close to being an azeotropic blend it behaves like a pure compound or single component refrigerant The remaining refrigerant charge in the system may be used after leaks have occurred and then top off the charge by utilizing the pressure charts on the inner control panel cover as a guideline REMEMBER When adding R 410A refrigerant it must come out o...

Страница 14: ...or is allowed to run in reverse rotation for several minutes the compressor s internal protector will trip All three phase compressors are wired identically internally As a result once the correct phasing is determined for a specific system or installation connecting properly phased power leads to the same Fusite terminal should maintain proper rotation direction The direction of rotation of the c...

Страница 15: ... Lockout Sequence If the low pressure switch opens for more than 120 seconds the compressor contactor will de energize and go into a soft lockout Regardless the state of the low pressure switch the contactor will reenergize after the delay on make time delay has expired If the low pressure switch remains open or opens again for longer than 120 seconds the unit will go into manual lockout condition...

Страница 16: ... evacuate and recharge the unit to the serial plate charge REMOVAL OF FAN SHROUD 1 Disconnect all power to the unit 2 Remove the screws holding both grilles one on each side of unit and remove grilles 3 Remove screws holding fan shroud to condenser and bottom Nine 9 screws 4 Unwire condenser fan motor 5 Slide complete motor fan blade and shroud assembly out the left side of the unit 6 Service moto...

Страница 17: ...B Low Side High Side 137 350 139 371 141 393 142 416 142 435 146 465 148 492 150 519 152 548 154 578 85 deg DB 72 deg WB Low Side High Side 142 362 144 384 146 407 147 431 149 455 151 481 153 509 155 537 157 567 159 598 H48A1 L1 75 deg DB 62 deg WB Low Side High Side 125 349 127 370 129 391 131 415 133 440 136 467 137 495 140 526 143 557 146 590 80 deg DB 67 deg WB Low Side High Side 134 358 136 3...

Страница 18: ...Circuit l Minimum Circuit Ampacity j Maximum External Fuse or Ckt Brkr k Field Power Wire Size k Ground Wire l Minimum Circuit Ampacity j Maximum External Fuse or Ckt Brkr k Field Power Wire Size k Ground Wire Size Ckt A Ckt B Ckt A Ckt B Ckt A Ckt B Ckt A Ckt B H42A1 A00 A0Z A05 A10 A15 A20 230 208 1 1 1 1 1 or 2 1 or 2 33 33 59 85 111 50 50 60 90 125 8 8 6 4 2 10 10 10 8 6 59 59 26 52 60 60 30 6...

Страница 19: ... Code and all local codes Electrical Specifications H L Series Model Rated Volts and Phase No Field Power Circuits Single Circuit Dual Circuit l Minimum Circuit Ampacity j Maximum External Fuse or Ckt Brkr k Field Power Wire Size k Ground Wire l Minimum Circuit Ampacity j Maximum External Fuse or Ckt Brkr k Field Power Wire Size k Ground Wire Size Ckt A Ckt B Ckt A Ckt B Ckt A Ckt B Ckt A Ckt B H4...

Страница 20: ...1375 High E S P In H2O H42A L H48A L H60A L High Speed Low Speed High Speed Low Speed Dry Coil Wet Coil Dry Coil Wet Coil Dry Coil Wet Coil Dry Coil Wet Coil 0 1 2 3 4 5 1885 1770 1635 1500 1370 1250 1800 1665 1540 1400 1285 1150 1650 1550 1450 1350 1300 1600 1500 1400 1300 1175 2200 2100 2000 1875 1775 1650 2000 1900 1800 1700 1600 1475 1600 1525 1450 1375 Model H42A L H48A L H60A L Outlet FRONT ...

Страница 21: ... Amps BTUH Amps BTUH Amps BTUH 4 16 7 13650 14 4 10240 5 20 8 17065 18 1 12800 6 14 4 20500 12 5 15360 7 2 20500 8 33 3 27300 28 8 20475 9 21 7 30600 18 7 23030 10 8 30700 10 41 6 34130 36 2 25600 12 14 4 40950 15 62 5 51250 54 0 38400 36 2 51200 31 2 38400 18 0 51200 18 43 3 61430 37 5 46100 20 83 2 68260 72 1 51200 ...

Страница 22: ...PTIONAL ACCESSORIES EHWA05 A05 X X EHWA05 A10 X X X EHWA05 A15 X X X EHWA05 A20 X X X EHWA05 B09 X X EHWA05 B15 X X X EHW05A B18 X X X EHWA05A C09 X X X EHWA05A C15 X X X EHWA60 A05 X EHWA60 B09 X WMCB 05B X X WMCB 06B X WMCB 08A X X WMCB 09A X WMPD 01C X X X hEATER kITS CIRCUIT BREAKER WMCB PULL DISCONNECT WMPD ...

Страница 23: ... 15 Start Kit 230V 1 Phase X CMC 28 LAC X BFAD 5 Barometric Fresh Air Damper Standard X BOP 5 Blank Off Plate X ECONWMT T5 100 Economizer Temperature X ECONWMT E5 100 Economizer Enthalpy X ECONWMT T5 DC 100 Economizer DC Temperature X ECONWMT E5 DC 100 Economizer DC Enthalpy X ...

Отзывы: