background image

Manual 2100-647D

Page 

19 of 36

Adjustable Delay-on-Make and Delay-on-Break Timer

On initial power up and any time power is interrupted 
to the unit, the delay-on-make period begins, which is 
the time set on the potentiometer (delay-on-break time) 
plus 10% of the delay-on-break setting (delay-on-break 
factory default is 2 minutes).  When the delay-on-
make period is complete and the high pressure switch 
and low pressure switch are closed, the compressor 
contactor is energized.  Upon shutdown (end of the 
call for cooling), the delay-on-break timer starts and 
prevents restart (next call for cooling) until the delay-
on-break period has expired. 

During routine operation of the unit with no power 
interruptions, the compressor will operate on demand 
with no delay.

High Pressure Switch and Lockout Sequence

If the high pressure switch opens, the compressor 
contactor will de-energize immediately.  The lockout 
timer will go into a 

soft lockout

 and stay in soft lockout 

until the high pressure switch closes and the delay-on-
break time has expired.  If the high pressure switch 

opens again in this same operating cycle, the unit will go 
into 

manual lockout

 condition and the alarm relay circuit 

will energize.  Recycling the wall thermostat or main 
power resets the manual lockout. 

Low Pressure Switch, Bypass and Lockout Sequence

If the low pressure switch opens for more than 120 
seconds, the compressor contactor will de-energize and 
go into a soft lockout.  Regardless the state of the low 
pressure switch, the contactor will re-energize after 
the delay-on-make time delay has expired.  If the low 
pressure switch remains open, or opens again for longer 
than 120 seconds, the unit will go into manual lockout 
condition and the alarm relay circuit will energize.  
Recycling the wall thermostat or main power resets the 
manual lockout.

Alarm Relay Output

Alarm terminal is the output connection for 
applications where an alarm relay is employed.  This 
terminal is powered whenever the compressor is locked 
out due to HPC or LPC sequences as described above.

Terminal

Description

Use

Revision "2" 

Reference

1

Compressor on Output Signal from Jade to MV

Economizer Only

"A"

2

24VAC HOT

 from Terminal 2 Connected to Unit Transformer

24V HOT

"R"

3

24VAC COMMON

 from Unit Transformer to MV

24V COMMON

"C"

4

Unit Compressor Operation

Cooling Operation

"Y"

5

Close Damper Input (Close Blade 100%)

Economizer Only

"F"

6

Electric Heat On Operation, Stage 1 and 2

Heating Operation

"W1"

7

1st Stage Cooling Input, 1st Stage Cooling Signal to Jade

Economizer Only

"Y1"

8

2nd Stage Cooling Input, 2nd Stage Cooling Signal to Jade

Economizer Only

"Y2"

9

Blower Operation (Indoor Blower On)

Blower Operation

"G"

10

Filter Switch Normally Closed Dry Contacts

Alarm Signal

"4"

11

Filter Switch Normally Closed Dry Contacts

Alarm Signal

"5"

12

Blade Switch Delay Relay Normally Closed Dry Contacts

Economizer Only

"8"

13

Blade Switch Delay Relay Normally Closed Dry Contacts

Economizer Only

"9"

14

Occupied Signal Input, Econ Emergency Open (Open Blade 100%)

Economizer Only

"E"

15

Econ Open Output (

6V HOT, 24V HOT

 after Blade Open 100% and delay)

Economizer Only

"10"

16

Alarm Relay Common Dry Contact

Comp Alarm Signal

"3"

17

Alarm Relay Normally Open Dry Contact

Comp Alarm Signal

"2"

18

Alarm Relay Normally Closed Dry Contact

Comp Alarm Signal

"1"

19

24VAC HOT

 to Terminal 2 from Unit Transformer Through Smoke Alarm 

Jumper Wire*

24V HOT

"RT"

20

2nd Stage Heating On Operated Through Jumper to Terminal 6

Heating Operation, 

2nd Stage

"W2'

21

Blade Switch Terminal 

24V HOT

 When Blade is Open, Sends Signal from 

Switch to Delay Relay

Economizer Only

"7"

TABLE 1

Sequence of Operation

*  Replace jumper wire with smoke alarm connections to interrupt 24VAC unit power if smoke alarm is used in shelter.  Jumper can also 

be removed to break 24VAC power to unit.

Содержание H12AA-A

Страница 1: ...H12AA A H24AA A H36AA A H42AA A H48AA A H60AA A H72AA A H24LA A H36LA A H42LA A H48LA A H60LA A H72LA A Bard Manufacturing Company Inc Bryan Ohio 43506 www bardhvac com Manual 2100 647D Supersedes 210...

Страница 2: ...Blower Performance 25 Table 7 Max ESP of Operation Elec Heat Only 25 Table 8A H12 Electric Heat 26 Table 8B H24 72 Electric Heat 26 Table 9 Optional Accessories 27 Table 10 Vent and Control Options 2...

Страница 3: ...ummer Air Conditioning Duct Design for Residential ACCA Manual D Winter and Summer Air Conditioning and Equipment Selection For more information contact these publishers ACCA Air Conditioning Contract...

Страница 4: ...ed before the installation is made See page 3 for information on codes and standards Size of unit for a proposed installation should be based on heat loss calculation made according to methods of Air...

Страница 5: ...be insulated and all joints taped or sealed to prevent air or moisture entering the wall cavity Some installations may not require any return air duct A metallic return air grille is required with in...

Страница 6: ...olts 7 Secure rain flashing to wall and caulk across entire length of top see Figures 3A D 8 For additional mounting rigidity the return air and supply air frames or collars can be drilled and screwed...

Страница 7: ...63 CONDENSER AIR OUTLET HEATER FILTER ACCESS AIR VENTILATION CONDENSER AIRFLOW IS BLOW THRU 19 72 3 88 31 06 19 72 20 43 SHIPPING LOCATION ENTRANCE ELECTRICAL OPTIONAL TOP RAIN FLASHING DRAIN HOSE 22...

Страница 8: ...d Entrance Air Panel Drain Heater Disconnect Entrance 4 Pitch Inlet Access Panel Economizer Rain Hood Low Voltage Electrical Air Intake Hood C Breaker High Voltage Economizer Controls H A D J C I 2 13...

Страница 9: ...SUPPLIED FOAM AIR SEAL WALL WALL STRUCTURE MIS 3600 FLANGES AND UNDER TOP FLASHING AT TIME OF INSTALLATION SUPPLY AIR DUCT RETURN AIR NOTE IT IS RECOMMENDED THAT A BEAD OF SILICONE CAULKING BE PLACED...

Страница 10: ...F TOP TOP WALL OF CAULKING ALONG PANEL FOAM AIR SEAL WALL STRUCTURE OPENING TOP FLASHING AT TIME OF INSTALLATION THE SIDE MOUNTING FLANGES AND UNDER DUCT Wall Opening and Hole Location View Right Side...

Страница 11: ...4 CLEARANCE ON ALL HEATER ACCESS TOP FLASHING AT TIME OF INSTALLATION THE SIDE MOUNTING FLANGES AND UNDER SILICONE CAULKING BE PLACED BEHIND IS ON OPPOSITE LEFT SIDE OPENING CONTROLS AND HEATER ACCESS...

Страница 12: ...1 4 1 1 4 29 3 4 32 12 5 1 2 2 NOTES WALL STRUCTURE 1 SUPPLY AIR IT IS RECOMMENDED THAT A BEAD OF OPENING Right Side View RAIN FLASHING SILICONE CAULKING BE PLACED BEHIND RECOMMENDED 1 CLEARANCE FROM...

Страница 13: ...als This is required for the first 3 of ducting It is important to insure that the 1 4 minimum spacing is maintained at all points Failure to do this could result in overheating the combustible materi...

Страница 14: ...TURN AIR SUPPLY AIR FACTORY SUPPLIED RAIN FLASHING SUPPLY AIR MIS 548 A SIDE VIEW I A C K E 1 000 B 1 000 SUPPLY DUCT OVER FRAME INTERIOR FINISHED WALL ALL AROUND DUCT FRAMING MATERIAL EXTERIOR FINISH...

Страница 15: ...e that there will be no nuisance tripping due to the momentary high starting current of the compressor motor The disconnect access door on this unit may be locked to prevent unauthorized access to the...

Страница 16: ...eplace filter 4 Press Reset button 5 Verify filter light is off 6 Replace filter door 7 Turn on unit power For units equipped with economizer 1 Turn off unit power 2 Remove hood cover 3 Remove mist el...

Страница 17: ...nt composition during multiple leaks and recharges R 410A refrigerant is close to being an azeotropic blend it behaves like a pure compound or single component refrigerant The remaining refrigerant ch...

Страница 18: ...d with a three phase line monitor to prevent compressor damage due to phase reversal The phase monitor in this unit is equipped with two LEDs If the Y signal is present at the phase monitor and phases...

Страница 19: ...wer resets the manual lockout Alarm Relay Output Alarm terminal is the output connection for applications where an alarm relay is employed This terminal is powered whenever the compressor is locked ou...

Страница 20: ...nds DOB 144 second DOM 5 0 minute 300 seconds DOB 150 second DOM During routine operation of the unit with no power interruptions the compressor will operate on demand with no delay Typical Settings f...

Страница 21: ...rge quantity The pressure table on the following page shows nominal pressures for the units Since many installation specific situations can affect the pressure readings this information should only be...

Страница 22: ...38 587 80 67 Low Side High Side 125 331 128 355 130 379 133 404 136 430 138 457 140 485 143 513 145 542 147 572 148 602 85 72 Low Side High Side 129 343 132 367 135 392 138 418 141 445 143 473 145 502...

Страница 23: ...Ckt C Ckt A Ckt B Ckt C H12AA A0Z A03 A05 230 208 1 1 1 1 9 20 27 15 20 30 14 12 10 14 12 10 H24AA A00 A0Z A04 A05 A08 A10 230 208 1 1 1 1 1 1 21 25 30 46 56 30 30 30 50 60 10 10 10 8 6 10 10 10 10 1...

Страница 24: ...8 6 3 10 10 10 8 60 26 60 30 6 10 10 10 H60LA B00 B0Z B03 B05 B09 B15 230 208 3 1 1 1 1 1 27 27 27 35 53 40 40 40 40 60 8 8 8 8 6 10 10 10 10 10 H72LA A00 A0Z A05 A10 A15 230 208 1 1 1 1 1 or 2 58 58...

Страница 25: ...5 2010 1965 1950 1870 0 2 425 400 905 870 1265 1185 905 890 1820 1760 1615 1565 1820 1770 1600 1540 1970 1885 1400 1315 2115 2035 1960 1915 1885 1825 0 3 375 360 835 800 1180 1100 860 850 1735 1665 15...

Страница 26: ...7 13650 14 4 10240 5 20 8 17540 18 1 13275 12 0 17065 10 4 12799 6 14 4 20500 12 5 15360 8 33 3 27300 28 8 20475 9 21 7 30600 18 7 23030 10 41 6 34130 36 2 25600 15 62 5 51250 54 0 38400 36 2 51200 3...

Страница 27: ...A A05 X X EHW6TA B03 X EHW6TA B06 X EHW72A A10B X EHW72A A15B X EHW72A A20B X Circuit Breakers WMCB Pull Disconnects WMPD WMCB 03A X WMCB 05A X WMCB 08A X X WMCB 09A X X Left Hand Units H24LA A H36LA...

Страница 28: ...A X BOP 2 Blank Off Plate X EWM1 E EWM1 T Economizer Bldg Equipment Enthalpy Economizer Bldg Equipment DB Temp X X EWM2 E EWM2 T Economizer Bldg Equipment Enthalpy Economizer Bldg Equipment DB Temp X...

Страница 29: ...Closed Dry Contacts MV Signals Blade Switch Fail Alarm 8 on Relay Board 8 13 Blade Switch Delay Relay Normally Closed Dry Contacts MV Signals Blade Switch Fail Alarm 9 on Relay Board 9 14 Occupied Sig...

Страница 30: ...Contacts Not Used 4 11 Filter Switch Normally Closed Dry Contacts Not Used 5 12 Blade Switch Delay Relay Normally Closed Dry Contacts Not Used 8 13 Blade Switch Delay Relay Normally Closed Dry Contac...

Страница 31: ...22 21 6 Circuit Breaker 30 Low Press Control Hi Press Control Black Black Black Black White Blk Wht Black White Black White Black White Condenser Section Module Alarm Relay Indoor Delay Blower Relay F...

Страница 32: ...hite Black White Black White Heat Plug SMOKE JUMPER G LOUT 20 104 Condenser Section 6 Pin Electric Module Compressor Relay Alarm Relay Delay Blower Relay Indoor Relay Filter Switch Filter Reset Button...

Страница 33: ...1 12 13 4 8 18 6 33 20 104 14 109 2 110 16 111 11 112 3 113 9 117 7 118 21 116 5 121 19 136 Dual Can Capacitor LOUT 5 ECON LOUT DAMPER 128 103 B 128 3 Black White Light 113 124 Terminal Black Black B...

Страница 34: ...116 Black White 121 6 131 134 128 128 124 132 Black White 132 Light 23 32 10 Black White Black Black Black White 6 5 4 3 2 1 Blk Wht Black White Black White Black White Heat Plug Condenser Section 6...

Страница 35: ...2 NC 3 2 1 NO 12 PIN PLUG COM DAMPER MOTOR DAMPER BLADE IN RED BLACK BLACK IS SHOWN WITH THE CONTACT POSITION IAQ AUX1 O Y2 I 8 S BUS ACT 24V ACT RED YELLOW IAQ R MAT PLUG PLUG PLUG PLUG BROWN WHITE G...

Страница 36: ...n Vent Plug Pin 2 on Vent Plug Pin 5 on Vent Plug Pin 7 on Vent Plug Pin 10 on Vent Plug Time Delay Relay T1 T2 Y HPC Lo Press Sw LPC LPC Alarm Relay ALR CC Comp Control Module R MV Controller C 4 5 W...

Отзывы: