Manual 2100-675
Page
2 of 2
2. Use UP or DOWN keys and ENTER key to enter
password 1313.
3. Press the UP or DOWN keys to scroll to the
Settings
menu; press ENTER key.
4. Press UP or DOWN keys to scroll to
Date/Time
menu;
press ENTER key.
5. Press UP or DOWN keys to scroll to
Timezone
; press
ENTER key.
6. Press UP or DOWN keys to scroll through available
timezones.
7. Press ENTER key to scroll to
Update Timezone
.
8. Press UP or DOWN key to change value to
YES
.
9. Press ENTER key to save and scroll to top of screen.
10. Press UP or DOWN keys to navigate to
Date/Time
change
.
11. Press ENTER key to scroll to the desired value to be
changed.
12. Press UP or DOWN keys to change the value.
13. Press ENTER key to save.
14. Press the ESCAPE key several times to return to Main
Menu screen.
Configure Sensors (LV Controller)
The LV is capable of utilizing three temperature sensors
and three humidity sensors. The controller must be
configured to match the sensors for the shelter. The
available sensors are
Indoor Humidity 1
,
Indoor Humidity
2
,
Indoor Humidity 3
,
Indoor Temperature 1
,
Indoor
Temperature 2
and
Indoor Temperature 3
.
If necessary, the sensors could be calibrated at this time
too. For information on calibrating the sensors, see page
41 in the manual 2100-674.
To enable/disable
Indoor Humidity 1
:
1. Press UP or DOWN keys to scroll to
IO Config
; press
ENTER key.
2. Press UP or DOWN keys to scroll to
Indoor Hum 1
(C3)
.
3. Press ENTER key to scroll to
Enable
.
4. Press UP or DOWN key to change value to ON to
enable sensor (or change value to OFF to disable
sensor).
5. Press ESCAPE key until back at
IO Config
; press
ENTER key.
Enable/disable the remaining sensors using the same
steps as listed above.
See LV1000 Service Instructions manual 2100-673 for
information on setting up the smoke, hydrogen and power
loss relays (if applicable).
Enter total units (LV Controller)
1. Press MENU key to go to the Main Menu screen.
2. Use UP or DOWN keys and ENTER key to enter
password 1313.
3. Press UP or DOWN keys to scroll to
Sys Config
; press
ENTER key.
4. Press ENTER key to scroll to
Total Units
.
5. Press UP or DOWN keys to adjust value to correct
number of units.
6. Press ENTER key to save.
7. Press ESCAPE key until back at Main Menu.
Verify units are online (LV Controller)
Once a unit is uniquely addressed, communication can be
verified at the LV controller.
With the correct number of units set at the LV controller,
each unit can be remotely viewed from the LV controller
information screen.
To view these screens:
1. Press
ESCAPE key to view the Status screen. (May
need to be pressed more than once.)
2. Press UP or DOWN key until the Quick Menu in
the lower right corner of the screen displays the
Information icon ( ); press ENTER key.
3. Press UP or DOWN keys to scroll through the
Information screens until the desired unit Information
screen appears. Three Info screens are available for
each unit. Unit serial number and model number and
24-hour run time information can also be viewed on
these screens.
In addition to being able to remotely view the units, an
alarm will be generated on the LV controller for units
not communicating.
Clear Controller Alarm Logs (LV Controller)
To clear the LV controller alarm logs:
1. Press MENU key to go to the Main Menu screen.
2. Use UP or DOWN keys and ENTER key to enter
password 1313.
3. Press UP or DOWN keys to scroll to
Settings
; press
ENTER key.
4. Press UP or DOWN keys to scroll to
Initialization
;
press ENTER key.
5. Press ENTER key to scroll to
Delete Alarm Logs?
6. Press UP or DOWN key to value to
YES
; press ENTER
key.
7. Press ESCAPE key several times to return to Main
Menu screen.
Once all the installation steps have been completed, all
alarms and alarm logs have been cleared and system
verification and run test results were satisfactory, the
installation can now be considered “complete”.