Manual

2100-422N

Page

17 of 42

Then, to reset, hold the button down for 15
seconds until the red light turns off and the yellow
LED turns on.  Observe at least one full control
sequence of operation from startup to shutdown.
Simulate a flame failure lockout by following the
procedure (within this manual).  If the operation is
erratic, or not to specifications, then replace the
control.  Always verify the control functions
according to all specifications before leaving the
installation site.

DISABLE FUNCTION

Any time the burner is running, press and hold the
reset button to disable the burner.  The burner will
remain off as long as the button is held.

Burner Option

 – 

Flame Quality Monitor

This control is trained to recognize and remember a
good flame based on initial burner set up.  Control
then monitors the flame via the CAD cell signal for
deviation in the combustion characteristics of the
burner.  If the control senses a deviation on the high
side or on the low side from the original set up
condition for three consecutive cycles, it will trigger
an alarm circuit which can be tied to an audible local
device to signal the home owner or into the home
security system.  Upon being notified of the alarm,
the security agency will notify the dealer of choice
based upon information supplied by the home
owner.  The system will also be capable of being
connected to a phone line that will contact the dealer
directly with the alarm.  This alarm will typically
sound 3 to 5 days prior to the primary control going
into lockout giving the service agency a prior notice
before a sooting condition or other failure can occur
resulting in untold savings.  This monitor system is
available through your local distributor under the
Honeywell Part #QS7100F.

If the control locks out three times without a
satisfied call for heat, or due to other significant
events such as a relay contact weld, the Lockout
becomes 

restricted

 in order to prevent repetitious

resetting by the homeowner.

Electronic Blower Control Board

 (EBC)

This furnace is equipped with an Electronic Blower
Control (EBC), which controls all comfort air blower
operations.  This EBC has three relays; one for
heating speed, one for cooling speed, and one which
isolates the T–T signal from the oil primary control.

NOTE:  If a jumper wire is placed across “R” and

“W” prior to turning on power to the unit
and then power is applied, the comfort
air blower will start and run for the
ignition period and through the entire
call for heat.

Once this call for heat is satisfied, the
blower will function according to the
regular blower on and blower off delay
cycles.

This EBC is designed to be very simple and
dependable.  This basic control allows for easy
troubleshooting and maintenance.  As illustrated in
Figure 7 all connections are well marked.  The
blower on and off timings for both heating and
cooling speeds are timed automatically.  The heating
blower off delay can be selected from four different
timings by moving the selection jumper.  The timings
are as follows:

Heating Blower ON delay – 75 seconds from a call
for heat.

Heating Blower OFF delay – Selectable in seconds:
150, 180, 210 or 240.  Factory shipped at 240.

Cooling Blower ON delay – 6 seconds from a call for
cooling.

Cooling Blower OFF delay – 60 seconds.

RESETTING FROM RESTRICTED LOCKOUT

        CAUTION

Before resetting the control from restricted

lockout state, troubleshoot the heating

system for the root cause(s) of lockout and

make necessary repairs or adjustment to

ensure a safe start condition.

Содержание FH085D36F

Страница 1: ...rbon Monoxide is invisible orderless and toxic Bard Manufacturing recommends a carbon monoxide alarm in your home even if you do not own a gas appliance Locate the carbon monoxide alarm in the living...

Страница 2: ...Chart 4 FLF FLR085D36F Data 38 Chart 5 FLF FLR110D48F Data 38 Chart 6 FLF FLR110D60F Data 38 Chart 7 FLR140D60F Data 39 Chart 8 FC085D36F Data 39 FIGURES Figure 1 FLF R Models Dimensions 5 Figure 2 FH...

Страница 3: ...s Load Calculation for ACCA Manual J Residential Winter and Summer Air Conditioning Duct Design for Residential ACCA Manual D Winter and Summer Air Conditioning and Equipment Selection FOR MORE INFORM...

Страница 4: ...oil burner must have a generous supply of combustion air to operate properly The flow of combustion and ventilating air must not be obstructed from reaching the furnace See Combustion Air Requirement...

Страница 5: ...3 2 3 2 3 2 3 2 5 2 1 8 4 5 2 1 8 4 5 2 1 8 4 5 2 1 8 4 5 2 6 0 4 5 2 6 0 4 5 2 6 0 4 5 2 6 0 4 0 2 x 2 2 0 2 x 2 2 0 2 x 2 2 0 2 x 2 2 4 1 x 2 2 4 1 x 2 2 4 1 x 2 2 4 1 x 2 2 t n o r F t n o r F r a...

Страница 6: ...AND FH110 SPECIFICATION SHEET 19 1 4 16 RETURN OPENING CUT OUT OPTIONAL OIL ENTRANCE OIL ENTRANCE FRESH AIR KNOCKOUT OPTIONAL HIGH VOLTAGE ENTRANCE OPTIONAL LOW VOLTAGE ENTRANCE FLUE KNOCKOUT RETURN O...

Страница 7: ...AGE ENTRANCE REAR FLUE KNOCKOUT OPTIONAL HIGH VOLTAGE ENTRANCE ENTRANCE FRESH AIR LOW VOLTAGE KNOCKOUT OIL ENTRANCE FLUE KNOCKOUT OPTIONAL OPTIONAL OIL ENTRANCE SUPPLY OPENING 19 1 8 18 1 8 BOTTOM VIE...

Страница 8: ...ent CFM and external static pressure ratings to insure proper air delivery capabilities On replacement installations particularly if equipment is oversized the duct systems can easily be undersized Mo...

Страница 9: ...n r u B m u m i n i M t i u c r i C y t i c a p m A e m i T x a M e s u F y a l e D R C A H r o r e k a e r B t i u c r i C P H A L F P H A L F F 6 3 D 5 8 0 H F 1 0 6 5 1 1 3 7 3 1 6 5 7 1 7 1 9 5 1...

Страница 10: ...ow voltage thermostat entrance Shut off switch if not fused power line must include fuse or circuit breaker To power source To thermostat and optional A C unit Air Boot knockout optional Inspection do...

Страница 11: ...flue models remove appropriate cabinet knockout Mounting screws located under flue box cover Flue Box Cover L i n e d C h i m n e y Thimble Clean out Door keep closed Oil Burner MIS 1825 Follow all a...

Страница 12: ...must comply with NFPA31 BECKETT AFG OR NX OIL BURNER This furnace is equipped with a high static Beckett AFG or Beckett NX oil burner which is designed to produce adequate draft in nearly any vertical...

Страница 13: ...troubleshooting features to ease service and reduce down time The operational guide for the Genisys 7505 primary control is provided following on Page 14 BECKETT SOLID STATE IGNITER This igniter diff...

Страница 14: ...rryover Once flame is established the igniter remains on for 10 additional seconds to ensure flame stability 6 Run The flame is sustained until the call for heat is satisfied The burner is then sent t...

Страница 15: ...b t e s e r e h t r e t f A e b n e h t n a c n o t t u b e h t s d n o c e s 5 1 e c n e u q e s n o i t i n g i t x e n e h t g n i r u d d e p p a t e d o m e m i r P p m u P r e t n e o t f f o t...

Страница 16: ...ished during the four minute pump prime mode return to step 5 to re enter Pump Prime mode Repeat steps 5 through 7 until the pump is fully primed and the oil is free of bubbles 9 Terminate the call fo...

Страница 17: ...gs This monitor system is available through your local distributor under the Honeywell Part QS7100F If the control locks out three times without a satisfied call for heat or due to other significant e...

Страница 18: ...NECTIONS OIL PRIMARY T T CONNECTIONS LINE VOLTAGE CONNECTION HOT UNUSED BLOWER MOTOR SPEED CONNECTIONS LINE VOLTAGE CONNECTION COM L2 ELECTRIC AIR CLEANER CONNECTION HUMIDIFIER CONNECTION HEATING BLOW...

Страница 19: ...H F G F A y o B i H 5 7 0 w o l l o H 0 7 G I S P 0 0 1 0 0 0 5 0 1 0 0 0 7 8 5 6 0 0 0 0 1 9 0 0 0 6 7 5 5 0 0 0 0 7 7 0 0 0 4 6 F 8 4 D 0 1 1 H F X N y o B i H 5 8 0 d i l o S 0 6 G I S P 0 5 1 0 0...

Страница 20: ...Smoke Readings After burner has been operating 5 or 10 minutes take a smoke measurement in the flue following the smoke tester instructions Oily or yellow smoke spots on the filter paper are usually...

Страница 21: ...icated if the net stack temperature during steady operation exceeds 600 F N Check Ignition Check operation over repeated cycles to insure prompt ignition on starting O Check Pump Cutoff Slow pump cuto...

Страница 22: ...adjustment range 0 2 4 6 8 8 10 12 14 6 Knee Best air setting Plotted point Plotted point Plotted point CO Curve from plotted points 2 Air Settings Low High Bacharach Smoke Number Percent CO in Flue G...

Страница 23: ...Manual 2100 422N Page 23 of 42 FIGURE 9 PRESSURE GAUGE CONNECTION TO BLEED PORT MIS 1660 Pressure Gauge Remove Bleed Port to attach pressure guage...

Страница 24: ...RT UP SETTINGS l e d o M r e b m u N e l y t S r e n r u B o N t r a P e l z z o N d n a B r i A g n i t t e S r i A r e t t u h S g n i t t e S r i A t n e m t s u j d A e t a l P g n i t t e S e z i...

Страница 25: ...te combustion of the fuel oil Keep in mind that a certain amount of excess air is required as well to ensure complete combustion of the fuel oil When structures are constructed too tightly to supply s...

Страница 26: ...THIS ASSEMBLE INNER FLANGE TO UNIT FOR AIR BOOT ACCORDING TO MANUAL IN LEFT SIDE REMOVE KNOCKOUT MAKE ALL SETTINGS REMOVE PUMP TO INTAKE AIR TUBE MIS 1833 AFG BURNER COMBUSTION AIR BOOT ASSEMBLY AFG...

Страница 27: ...ppliances shall be provided For combustion air options see Page 25 Combustion Air Requirements NOTE Each opening shall have a free area of not less than one square inch per 1 000 BTU per hour 140 squa...

Страница 28: ...per hour 70 square inches per gallon per hour of total input of all appliances in the enclosure FIGURE 13 APPLIANCES LOCATED IN CONFINED SPACES ALL AIR FROM OUTDOORS NOTE Each air duct opening shall h...

Страница 29: ...quare inches per gallon per hour of the total input rating of all appliances in the enclosure FIGURE 15 APPLIANCES LOCATED IN CONFINED SPACES ALL AIR FROM OUTDOORS INLET AIR FROM VENTILATED CRAWL SPAC...

Страница 30: ...of a corrosion resistant material having an upward pitch of 1 4 for every foot of horizontal run and be made of material capable of handling temperatures up to 1800 F A barometric damper is supplied w...

Страница 31: ...0 0 2 m u i d e M 5 7 0 0 9 0 6 w o L F 6 3 D 5 8 0 F L F G F A 5 7 0 w o l l o H 0 7 G I S P 0 0 1 0 9 0 6 0 0 2 m u i d e M 5 6 0 0 9 0 6 w o L 5 5 0 0 9 0 6 w o L F 8 4 D 0 1 1 F L F X N 5 8 0 d i...

Страница 32: ...e type filters and 575 fpm for washable type filters See Figure 16 The counterflow filter kit part number FR25 comes with two washable filters If not installing the FR25 kit remember not to exceed 400...

Страница 33: ...cess door The electrical switch should be turned off prior to removing the access door Refer to Figure 18 below FIGURE 18 FILTER INSTALLATION LO BOY MODELS BY PULLING OUT ON SWELL LATCHES AND TILTING...

Страница 34: ...in checking the safety switch in this primary control A Flame Failure Simulate by shutting off oil supply manual valve while burner is on Within 9 seconds the control will shut the burner down and fl...

Страница 35: ...the burner tube and combustion chamber may be assured prior to installation into the furnace See Figure 19 and 20 WARNING The procedures described in Figures 19 and 20 should be conducted only by a q...

Страница 36: ...and corners of the front plate Pull entire assembly straight back away from furnace BE CAREFUL NOT TO TIP ASSEMBLY UP OR DOWN AS IT MAY DAMAGE THE COMBUSTION CHAMBER See Figure 20 BURNER AND COMB CHAM...

Страница 37: ...products are detrimental to the life expectancy of the combustion chamber and will destroy the chamber Refer to the Cleaning of Furnace section for proper cleaning methods COMMON CAUSES OF TROUBLE CA...

Страница 38: ...e w o l B w o L 6 0 2 1 7 1 1 2 w o L m u i d e M 0 1 7 1 3 2 0 3 h g i H m u i d e M 4 1 1 2 1 3 8 3 h g i H 0 2 0 3 0 4 0 5 CHART 4 FLF FLR085D36FDATA d e e p S r e w o l B c i t a t S r e w o l B w...

Страница 39: ...t a t S r e w o l B w o L 5 0 4 1 7 1 4 2 w o L m u i d e M 8 0 7 1 2 2 0 3 h g i H m u i d e M 1 1 0 2 7 2 5 3 h g i H 0 2 0 3 0 4 0 5 CHART 8 FC085D36F DATA d e e p S r e w o l B c i t a t S r e w...

Страница 40: ...MIT PLUG 2 CAPACITOR BLACK WHITE RETURN AREA BLOWER PRIMARY CONN 24V UNIT Y C W Rh Y G Rc THERMOSTAT COND OR EQUIVELANT T87F Q539A1220 VOLTAGE LOW VOLTAGE HIGH 5 WIRING FIELD 5 3 LIMIT BLACK HEATING A...

Страница 41: ...RS T87F Q539A1220 C BACKUP LIMIT CONTROL PANEL PRIMARY LIMIT 3 BLACK COOL SPR3 EAC COM SPR1 BLACK 1 4 BLUE BLUE YELLOW PURPLE PURPLE ORANGE GREEN GROUND BROWN BROWN T SEC1 HEAT RED 240 210 180 150 R W...

Страница 42: ...TOR OIL VALVE BURNER ASS Y T T 1 24V CONN YELLOW HUM UNIT Y C W Rh Y BURNER T87F Q539A1220 CONTROL PANEL OR EQUIVELANT BLACK BLACK BLACK BLACK BLACK G HEAT EX AREA HOT 2 HEAT COND 2 PRIMARY LIMIT BACK...

Отзывы: