Bard CompleteStat CS9B-THO Скачать руководство пользователя страница 7

Manual 2100-566F 
Page 

7 of 24

Requires optional Bard 8403-061 Outdoor Air 
Temperature Sensor.

 

•  NONE = No auxiliary strip heat; controller will 

not energize W2. If NONE is chosen, press 
LEFT button five (5) times to return to home 
screen.

9.  Press DOWN button to highlight DELAY (MINS).

10. Press ENTER button to highlight default DELAY 

minutes.

11. Press UP or DOWN button to select amount 

of minutes desired to delay the electric heat 
before activation: 10-120 minutes, 10 minute 
increments. Press ENTER button to save choice.

12. Press LEFT button to return to ADDITIONAL 

SETUP.

If COMP LOCKOUT was chosen during the heat 
strip configuration process, an optional outdoor air 
temperature sensor will have to be installed/configured 
to specifically set the temperature at which the 
compressor will no longer be allowed to operate. To 
install Bard 8403-061 Outdoor Air Temperature Sensor, 
attach the leads to terminals “OAT” and “GND”. To set 
the compressor outdoor air temperature from the home 
screen:

1. Press 

RIGHT button to access Main Menu screen.

2. Press 

DOWN button to scroll to ADVANCED. Press 

ENTER button.

3.  In the ADVANCED menu screen, press UP or 

DOWN button to scroll to LIMITS. Press ENTER 
button.

4.  Press DOWN button to scroll to COMP OAT HTG 

LOW. Press ENTER button.

5.  Press UP or DOWN button to select outdoor air 

temperature for compressor lockout. Press ENTER 
to save choice.

6.  Press LEFT button to return to ADVANCED menu.

Damper, Fan and Humidity Setup

1.  In the ADVANCED menu screen, press ENTER 

button to enter the APPLICATION menu. 

2.  Controller will ask for Admin Level Password.  

Enter BARD or 1914. Press ENTER button.

3.  Press DOWN button to scroll to ADDITIONAL 

SETUP. Press ENTER button.

4.  Press DOWN button to scroll to DAMPER. Press 

ENTER button.

5.  Press UP or DOWN button to choose from the 

available economizer options:

 

•  NONE = No economizer, or standard vent 

package (ERV/CRV/MFAD)

 

•  EN/DIS = Economizer in system

6.  Press ENTER button to select/save appropriate 

economizer option.

7.  Press LEFT button to go back to ADDITIONAL 

SETUP.

8.  The indoor blower can be set for ON or AUTO 

in either occupied or unoccupied conditions.

 

To 

access or change blower settings, press DOWN 
button to scroll to FAN. Press ENTER button to 
enter FAN SETUP.

9.  Press DOWN button to scroll through selections; 

adjust as necessary.

 

•  Speeds: Constant speed (nonadjustable)

 

•  Off Delay: “0” = System fan will run for 

specified time after call ends; 0-600 seconds 
in 30-second increments.

 

•  Unocc: “ON” = System fan will run 

continuously during all operational modes; 
“AUTO” = System fan will operate during call 
for cooling or heating, but will cycle off when 
no compressor or no heating is needed (factory 
default).

 

•  Occ: “ON” = System fan will run continuously 

during all operational modes (factory default); 
“AUTO” = System fan will operate during call 
for cooling or heating, but will cycle off when 
no compressor or no heating is needed.

10. Press ENTER button to save changes to FAN mode 

selections.

11. Press LEFT button to go back to ADDITIONAL 

SETUP.

12. Press DOWN button to scroll to HUMIDITY. Press 

ENTER button to enter HUMIDITY SETUP.

13. Press ENTER button again to choose 

DEHUMIDIFICATION.

14. Press ENTER button again to highlight current 

dehum choice (default is DISABLE).

15. Press UP or DOWN button to toggle ENABLE/

DISABLE. Press ENTER button to select/save 
choice.

16. Press DOWN button to scroll through additional 

DEHUMIDIFICATION screen choices:

 • ALLOW HTG DEHUM = Allows 

dehumidification in heating as well as cooling:  
YES/NO.

 • DEHUM SETPT = Relative Humidity 

(RH) setpoint: 50% RH to 75% RH, 1% 
increments.

Содержание CompleteStat CS9B-THO

Страница 1: ...OPERATION QUICK START GUIDE INSTALLATION INSTRUCTIONS Bard Manufacturing Company Inc Bryan Ohio 43506 www bardhvac com Manual 2100 566F Supersedes 2100 566E Date 9 1 16 Bard CompleteStatTM Models CS9...

Страница 2: ...ge with Honeywell W7459A Control Economizer with or without dehumidification 17 WD9 Heat Pump 1 Stage with Honeywell W7220 JADETM Control Economizer with or without dehumidification 18 WD10 Heat Pump...

Страница 3: ...al from control to unit 2 Turn the hex screws in the bottom and top of the controller clockwise inward until they clear the cover Remove base plate from controller INSTALLATION 3 Route completed wirin...

Страница 4: ...l Setback 15 Heat Setback 16 Standby Time Minutes 17 Motion Sensing Daily Schedule 18 Date 19 Time 20 Occupied Minimum Cooling 21 Occupied Maximum Cooling 22 Unoccupied Minimum Cooling 23 Unoccupied M...

Страница 5: ...ll to ADVANCED Press ENTER button 3 In the ADVANCED menu screen press ENTER button to enter the APPLICATION menu 4 Controller will ask for Admin Level Password Enter BARD or 1914 Press ENTER button 5...

Страница 6: ...to choose DEHUMIDIFICATION 11 Press ENTER button again to highlight current dehum choice default is DISABLE 12 Press UP or DOWN button to toggle ENABLE DISABLE Press ENTER button to select save choice...

Страница 7: ...Press ENTER button 4 Press DOWN button to scroll to DAMPER Press ENTER button 5 Press UP or DOWN button to choose from the available economizer options NONE No economizer or standard vent package ERV...

Страница 8: ...mode only OFF HVAC system is inactive 4 Press ENTER button to save choice 5 Press LEFT button two 2 times to return to home screen Setpoints To access setpoints from the home screen 1 Press RIGHT but...

Страница 9: ...Y1 1st Stage Compressor Output 24VAC SPST Relay Y0 Economizer Output 24VAC SPST Relay SC 24VAC to Relay Outputs Y0 O B G Power O B Reversing Valve Output 24VAC SPST Relay G Indoor Blower Output 24VAC...

Страница 10: ...s an existing call for the indoor blower whether through space conditioning or through constant fan operation Conventional 1H 1C 2H 1C 1H 2C or 2H 2C with Economizer Operation G Y O Y1 Y2 W1 E W2 O B...

Страница 11: ...e System Selection on page 5 3 Electric heat must be configured for a heat pump application see Auxiliary Heat Electric Heat Setup on page 7 Single Stage Heat Pump without Economizer Operation G Y O Y...

Страница 12: ...a heat pump application see Auxiliary Heat Electric Heat Setup on page 7 Two Stage Heat Pump with Economizer Operation G Y O Y1 Y2 W1 E W2 O B D A Fan Only X 1st Stage Cooling X X X 2nd Stage Cooling...

Страница 13: ...DIS 2 Stage HP with or w o Elec Heat EIFM Factory E Economizer w W7459A Control On Off 11 HP THO THOC HP 2 Stage EN DIS 2 Stage HP with or w o Elec Heat ECONWM Factory T or W Economizer w JADE W7220...

Страница 14: ...2100 566F Page 14 of 24 IMPORTANT Be sure to connect these field installed jumpers for proper operation IMPORTANT Be sure to connect these field installed jumpers for proper operation EIFM WIRING DIA...

Страница 15: ...anual 2100 566F Page 15 of 24 IMPORTANT Be sure to connect these field installed jumpers for proper operation IMPORTANT Be sure to connect these field installed jumpers for proper operation EIFM JADET...

Страница 16: ...00 566F Page 16 of 24 IMPORTANT Be sure to connect these field installed jumpers for proper operation IMPORTANT Be sure to connect these field installed jumpers for proper operation JADETM WIRING DIAG...

Страница 17: ...Manual 2100 566F Page 17 of 24 IMPORTANT Be sure to connect these field installed jumpers for proper operation IMPORTANT Be sure to connect these field installed jumpers for proper operation EIFM...

Страница 18: ...566F Page 18 of 24 IMPORTANT Be sure to connect these field installed jumpers for proper operation IMPORTANT Be sure to connect these field installed jumpers for proper operation EIFM JADETM WIRING DI...

Страница 19: ...Manual 2100 566F Page 19 of 24 IMPORTANT Be sure to connect these field installed jumpers for proper operation IMPORTANT Be sure to connect these field installed jumpers for proper operation JADETM...

Страница 20: ...100 566F Page 20 of 24 IMPORTANT Be sure to connect these field installed jumpers for proper operation IMPORTANT Be sure to connect these field installed jumpers for proper operation EIFM WIRING DIAGR...

Страница 21: ...Manual 2100 566F Page 21 of 24 IMPORTANT Be sure to connect these field installed jumpers for proper operation IMPORTANT Be sure to connect these field installed jumpers for proper operation EIFM...

Страница 22: ...2100 566F Page 22 of 24 IMPORTANT Be sure to connect these field installed jumpers for proper operation IMPORTANT Be sure to connect these field installed jumpers for proper operation WIRING DIAGRAMS...

Страница 23: ...Manual 2100 566F Page 23 of 24 IMPORTANT Be sure to connect these field installed jumpers for proper operation IMPORTANT Be sure to connect these field installed jumpers for proper operation...

Страница 24: ...ystem PINK PURPLE 1 W3 01 W2 E Y1 G C R Y E F W1 B L HONEYWELL W7220 BLK RED WHT BLU YEL ORG USE ENCLOSED RELAY D SC A W2 W1 E SC Y2 Y1 YO O B G IN9 ROS GND REM OAT LAS SC A B GND L COM 24V CompleteSt...

Отзывы: