Manual 2100-566DPage
1 of 20
CONTROLLER INSTALLATION
OPERATION & QUICK START
Bard CompleteStat™
CS9B-THO, CS9B-THOC
CS9BE-THO, CS9BE-THOC
Manual: 2100-566DSupersedes: 2100-566CFile:
Tab 19
Date: 11-05-13
Страница 1: ...Manual 2100 566D Page 1 of 20 CONTROLLER INSTALLATION OPERATION QUICK START Bard CompleteStat CS9B THO CS9B THOC CS9BE THO CS9BE THOC Manual 2100 566D Supersedes 2100 566C File Tab 19 Date 11 05 13...
Страница 2: ...3 Basic Operation Note Page 4 Quick Start Programming Page 4 5 Auxiliary Heat Electric Heat Setup Page 5 Compressor Lockout Temperature Page 5 6 System Enable Page 6 Temperature Setpoints Page 6 Termi...
Страница 3: ...Low Voltage Wiring Manual to terminal blocks 6 Replace controller over base plate being careful not to pinch dislodge connections 7 Turn hex screws in bottom top of controller counter clockwise outwa...
Страница 4: ...vanced and enter Advanced Screen 4 Enter button again to select enter Applications Screen 5 Controller will ask for Admin Level Password Factory Default Admin Level Password BARD Press Enter 6 Enter b...
Страница 5: ...ighlight Aux Heat choices 10 Up Down buttons to toggle through available choices W OLockout Auxiliary heat will activate regardlessof compressor operationoroutdoor air temperature factory default If W...
Страница 6: ...etpoints 3 Enter button to select Setpoints and enter Setpoints Screen 4 Enter button to select Cool Setpt3 5 Up Down buttons to enter appropriate cooling setpoint 6 Enter button to save new Cool Setp...
Страница 7: ...ification X Ventilation1 X1 X NOTE1 CS9B E THOC CO2 Sensing Capability Models will activate both G and A terminals upon a ventilation call however the CS9B E THO NON CO2 Sensing Models will activate t...
Страница 8: ...pability Models will activate both G and A terminals upon a ventilation call however the CS9B E THO NON CO2 Sensing Models will activate the A terminal only if there is an existing call for the indoor...
Страница 9: ...W7220 Control On Off 10 HP THO THOC HP 2 Stage EN DIS 2 Stage HP with or w o Elec Heat EIFM Factory E Economizer w W7459 Control On Off 11 HP THO THOC HP 2 Stage EN DIS 2 Stage HP with or w o Elec He...
Страница 10: ...Dehumidification Units Only 1 6 CompleteStat programmed for Damper Economizer EN DIS D 3 A W2 W1 E Y2 Y G C R 3 4 2 1 CRV ERV OR MFAD 5 HVAC System 3 A W2 W1 E Y2 Y1 G C R 3 6 2 1 HONEYWELL W7459A HVA...
Страница 11: ...Only 4 CompleteStat programmed for Damper Economizer EN DIS 1 D A W2 W1 E Y2 Y1 G C R 3 4 2 1 HONEYWELL W7220 HVAC System Y D A W2 W1 E Y2 Y1 G C R 3 4 2 HONEYWELL W7459 HVAC System Y E F D SC A W2 W1...
Страница 12: ...ire not used on MFAD Ventilation option 2 Wire for Dehumidification Units Only 1 6 CompleteStat programmed for Damper Economizer En Dis Opt Wire only for 2 Stg Heating 15kW or more 3 A W2 W1 E Y2 Y1 G...
Страница 13: ...Damper Economizer EN DIS 1 E F Wire not used on MFAD Ventilation option 4 5 Factory installed wires and jumpers Field Installed Wire Nut W3 01 W2 E Y1 G C R 1 HVAC System Y E F CRV ERV OR MFAD 3 W1 B...
Страница 14: ...Economizer EN DIS Field installed wires and jumpers 3 Field Installed Wire Nut 2 Wire for Dehumidification Units Only 4 1 CH S Series Heat Pumps use DH Dehumidification Terminal Factory installed wir...
Страница 15: ...grammed for Damper Economizer EN DIS 1 Wire not used on MFAD Ventilation option 5 6 W G Series uses A Terminal for Ventilation Field installed wires and jumpers Factory installed wires and jumpers 2 1...
Страница 16: ...for Ventilation 2 Wire for Dehumidification Units Only 4 CompleteStat programmed for Damper Economizer EN DIS 1 Field installed wires and jumpers Factory installed wires and jumpers 3 F W2 W1 Y2 Y1 G...
Страница 17: ...Units Only 1 Field installed wires and jumpers Factory installed wires and jumpers Wire not needed if Aux Heat Strip is 10kW or less 3 3 F W2 W1 Y G C R 1 HONEYWELL W7459A HVAC System Y1 Y2 E F D 3 4...
Страница 18: ...res and jumpers Factory installed wires and jumpers 8403 067 to be used with Non C02 Sensing CompleteStatTM 3 D 3 4 A Y1 YO G C R 1 HVAC System 6 W2 W3 Y2 B W1 L BLK RED WHT BLU YEL ORG USE ENCLOSED R...
Страница 19: ...provided colors to wire CompleteStatTM 2 Wire for Dehumidification Units Only 1 Field installed wires and jumpers Factory installed wires and jumpers 1 F W2 W1 Y1 G C R 4 5 9 3 7 6 11 10 HVAC System P...
Страница 20: ...nstalled thermostat had no terminal board and were wired directly from Plug 4 Use provided colors to wire CompleteStatTM 2 Wire for Dehumidification Units Only 1 Field installed wires and jumpers Fact...