Bard CMA-44 Скачать руководство пользователя страница 2

Manual 7960-855
Page 

2 of 6

INSTALLATION

1.  Disconnect all power to wall mount before 

installing sensors.

2.  Remove inner and outer control panel covers. 

Remove electric heater access panel, front 
condenser grill and upper front door.

3.  Install the airflow switch assembly (see Figure 1). 

Use two (2) 1012-086 screws to attach the switch 
bracket to the blower partition.

4.  Install one (1) 8611-028 snap bushing in the back 

of the blower partition and route the hose from the 
airflow switch through the bushing as shown in 
Figure 1.

5.  Secure the hose to the blower partition using the 

7950-005 nylon clamp and the 1012-153 smooth 
hex head screw as shown in Figure 1.

6.  Install the 8611-047 snap bushings in the filter 

partition and control panel bracket as shown in 
Figure 1.

7.  Route the wires from the airflow switch down 

through the blower partition and into the control 
panel as shown in Figure 1.

8.  Install the filter switch items using the 7960-854 

instructions. Filter switch testing and adjustment 
can be made after all sensors have been installed.

Figure 1 

Sharp metallic edges.

Take care and wear appropriate protective 
devices to avoid accidental contact with 
sharp edges.

Failure to do so can result in personal 
injury.

!

CAUTION

MIS-4092

AIRFLOW SWITCH ASSEMBLY

PART #910-2070

RUN HOSE DOWN THE BLOWER PARTITION

USING BUSHING PART #8611-028 THEN

SECURE THE HOSE USING CLAMP

PART #7950-005 AND SCREW PART #1012-153

FEED WIRES

THRU 3/4" SNAP

BUSHING 8611-047