The CMA-32 is a field-installable low ambient fan cycling 
control kit. 

This fan cycling low ambient control is only 

for use on R-410A refrigerant systems.

The CMA-32 kit consists of:
•  7960-778 Installation Instructions
•  8607-017 Terminal Block
•  1012-066 Screw (1)
•  8612-027 230V Head Pressure Control
•  1804-0520 Extension Tube Assembly
•  8611-115 Plug Assembly
•  113-353 Mounting Bracket
•  1012-065 Screws (2)

The CMA-32 kit is for use with Bard models W42A2D, 
W48A2D and W60A2D wall-mount air conditioners.

INSTALLATION

Disconnect all power to wall-mount unit. Remove outer 
and inner control panel covers and right side condenser 
inlet grille. Circled numbers provided in Figure 1 
on page 2 correspond to the following installation 
steps. Dashed lines indicate where a wire has been 
disconnected from the terminal.

1.  Mount 8607-017 terminal block to unit control 

panel with 1012-066 screw as shown in Figure 1. 

2.  Disconnect black high voltage outdoor motor 

lead from compressor contactor and reconnect to 
terminal block.

Bard Manufacturing Company, Inc. 
Bryan, Ohio 43506
www.bardhvac.com

Manual: 7960-778
Supersedes: 

NEW

Date: 5-24-16

CMA-32  

Low Ambient Fan Cycling Control

INSTALLATION INSTRUCTIONS

3.  Remove the upper service port cap from the liquid 

line. Install the low ambient control on the liquid 
line by screwing it onto the service port as shown 
in Figure 2 on page 3. Use wrenches to make the 
connection snug and check for leaks.

4.  Route low ambient control wires up through the 

bushing in the bottom of the control panel. Replace 
sealing compound after routing wires through the 
bushing. Route the wires through the wire holders 
in the control panel as shown in Figure 1.

5.  Connect the low ambient control wires between the 

terminal block and T2 of the compressor contactor 
(see Figure 1).

6.  Recheck wiring by referring to Figure 1. Turn on 

power to unit. Check for proper operation of the 
unit by energizing in cooling mode (first or second 
stage). The compressor should start—except when 
equipped with economizer and enthalpy control is 
energizing “free cooling” mode. Energizing “Y2” 
will override the enthalpy control allowing the 
mechanical cooling to operate. Run the unit for at 
least 5 minutes. The condensor fan motor should 
not run until the liquid pressure has reached 350 
PSI. Should the liquid pressure fall below 225 PSI 
while running, the condensor fan motor will de-
energize until the head pressure builds to 350 PSI.

7.  Apply “This unit is equipped with CMA-32 control 

module” label to the inside of the inner control 
panel cover above the unit wiring diagram.

8.  Replace the right side condenser inlet grille 

and inner and outer control panel covers. This 
completes the installation.