background image

Manual 2100-586G 

Page 

22 of 25

TABLE 7

Model

Rated 

Volts & 

Phase

No. 

Field 

Power 

Circuits

Single Circuit

Multiple Circuit

Minimum

Circuit

Ampacity

k

 

Max.

External 

Fuse or 

Ckt. Brkr.

l

 

Field

Power

Wire 

Size

l

 

Ground

Wire

 

Minimum Circuit

Ampacity

k

 

Max. Circuit

Exterior Fuse

or Ckt. Brkr.

l

 

Field Power

Wire Size

l

 

Ground Wire

Ckt. A

Ckt. B

Ckt. C

Ckt. A

Ckt. B

Ckt. C

Ckt. A

Ckt. B

Ckt. C

Ckt. A

Ckt. B

Ckt. C

C36H1-A0Z

230/208-

60-1

1

27

40

8

10

-A05

1

53

60

6

10

-A10

1 or 2

79

80

4

8

27

52

40

60

8

6

10

10

 -A15

1 or 2

85

90

4

8

33

52

40

60

8

6

10

10

C36H1-B0Z

230/208-

60-3

1

23

30

10

10

-B06

1

41

45

8

10

-B09

1

50

50

8

10

 -B15

1

52

60

6

10

C36H1-C0Z

460-60-3

1

12

15

14

14

-C06

1

21

25

10

10

-C09

1

26

30

10

10

 -C15

1

27

30

10

10

C42H1-A0Z

230/208-

60-1

1

31

40

8

10

-A05

1

57

60

6

10

-A10

1 or 2

83

90

4

8

31

52

40

60

8

6

10

10

 -A15

1 or 2

86

90

3

8

34

52

40

60

8

6

10

10

C42H1-B0Z

230/208-

60-3

1

27

35

8

10

-B06

1

45

50

8

10

-B09

1

54

60

6

10

 -B15

1

54

60

6

10

C42H1-C0Z

460-60-3

1

13

15

14

14

-C06

1

22

25

10

10

-C09

1

26

30

10

10

 -C15

1

27

30

10

10

C48H1-A0Z

230/208-

60-1

1

37

50

8

10

-A04

1

57

60

6

10

-A05

1

62

70

6

8

37

26

50

30

8

10

10

10

-A10

1 or 2

88

90

3

8

37

52

50

60

8

6

10

10

 -A15

1 or 2

88

90

3

8

37

52

50

60

8

6

10

10

 -A20

1 or 3

113

125

2

6

37

52

52

50

60

52

8

6

6

10

10

10

C48H1-B0Z

230/208-

60-3

1

27

40

8

10

-B06

1

45

50

8

10

-B09

1

54

60

6

10

 -B15

1

54

60

6

10

 -B18

2

N/A

N/A

N/A

N/A

54

28

60

30

6

10

10

10

C48H1-C0Z

460-60-3

1

13

20

12

12

-C06

1

22

25

10

10

-C09

1

27

30

10

10

 -C15

1

27

30

10

10

C60H1-A0Z

230/208-

60-1

1

45

60

8

10

-A05

1 or 2

71

80

4

8

45

26

50

30

8

10

10

10

-A10

1 or 2

97

100

3

8

45

52

50

60

8

6

10

10

 -A15

1 or 2

97

100

3

8

45

52

50

60

8

6

10

10

 -A20

1 or 3

113

125

2

6

45

52

52

50

60

52

8

6

6

10

10

10

C60H1-B0Z

230/208-

60-3

1

32

45

8

10

-B06

1

50

60

8

10

-B09

1

59

60

6

10

 -B15

1

59

60

6

10

 -B18

2

N/A

N/A

N/A

N/A

59

28

60

30

6

10

10

10

C60H1-C0Z

460-60-3

1

17

20

12

12

-C06

1

26

30

10

10

-C09

1

31

35

8

10

 -C15

1

31

35

8

10

  These “Minimum Circuit Ampacity” values are to be used for sizing the field power conductors. Refer to the National Electrical code (latest version), 

Article  310 for power conductor sizing. 

CAUTION

: When more than one field power circuit is run through one conduit, the conductors must 

be derated. Pay special attention to note 8 of Table 310 regarding Ampacity Adjustment Factors when more than three (3) current carrying 
conductors are in a raceway.

k

  Maximum size of the time delay fuse or circuit breaker for protection of field wiring conductors.

l

  Based on 75°copper wire. All wiring must conform to the National Electrical Code and all local codes.

 

Maximum KW that can operate with the heat pump on is 10KW. Full heat available during emergency heat mode.

  Maximum KW that can operate with the heat pump on is 9KW. Full heat available during emergency heat mode.

NOTE:

 

The Maximum Overcurrent Protection (MOCP) value listed is the maximum value as per UL 1995 calculations for MOCP (branch-circuit 

conductor sizes in this chart are based on this MOCP). The actual factory-installed overcurrent protective device (circuit breaker) in this 

model may be lower than the maximum UL 1995 allowable MOCP value, but still above the UL 1995 minimum calculated value or 

Minimum Circuit Ampacity (MCA) listed.

IMPORTANT:

 

While this electrical data is presented as a guide, it is important to electrically connect properly sized fuses and conductor wires in 

accordance with the National Electrical Code and all local codes.

  

Electrical Specifications — C**H Series

Содержание C36H1-A

Страница 1: ...Models INSTALLATION INSTRUCTIONS C36H1 A C36H1 B C36H1 C C42H1 A C42H1 B C42H1 C C48H1 A C48H1 B C48H1 C C60H1 A C60H1 B C60H1 C Bard Manufacturing Company Inc Bryan Ohio 43506 www bardhvac com Manual...

Страница 2: ...e Sensor Outside Unit Circuit 19 Fan Blade Setting Dimensions 20 Removal of Fan Shroud 20 R 410A Refrigerant Charge 20 Troubleshooting ECM Indoor Blower Motors 24 FIGURES Figure 1 Fresh Air Damper Ass...

Страница 3: ...OPTIONS X Beige 1 White 4 Buckeye Gray 5 Desert Brown 8 Dark Bronze S Stainless Steel CAPACITY 36 3 Ton 42 3 Ton 48 4 Ton 60 5 Ton VENTILATION OPTIONS B Blank off Plate V Commercial Ventilator Mod Sp...

Страница 4: ...led in accordance with the Standards of the National Fire Protection Association for the Installation of Air Conditioning and Ventilating Systems of Other Than Residence Type NFPA No 90A and Residence...

Страница 5: ...ersonal injury The safety alert symbol shall not be used with this signal word As an alternative to NOTICE the word CAUTION without the safety alert symbol may be used to indicate a message not relate...

Страница 6: ...s used Contact distributor or factory for ordering information If using a return air filter grille filters must be of sufficient size to allow a maximum velocity of 400 fpm NOTE If no return air duct...

Страница 7: ...tible wall Placement 1 On side by side installations maintain a minimum of 20 clearance on right side to allow access to control panel and heat strips and to allow proper airflow to the outdoor coil A...

Страница 8: ...ket optional use for direct mount not used when unit installed with curb C H RIGHT UNIT FIGURE 2 All dimensions are in inches Dimensional drawings are not to scale Dimensions of Basic Unit for Archite...

Страница 9: ...LY AIR IT IS RECOMMENDED THAT A BEAD OF OPENING Right Side View RAIN FLASHING SILICONE CAULKING BE PLACED BEHIND RECOMMENDED 1 CLEARANCE FROM THE SIDE MOUNTING FLANGES AND UNDER TOP FLASHING AT TIME O...

Страница 10: ...PPLY AIR DUCT FOR WALL MOUNTED UNIT SHOWING 1 4 INCH CLEARANCE TO COMBUSTIBLE SURFACES Fire hazard Maintain minimum 1 4 clearance between the supply air duct and combustible materials in the first 3 o...

Страница 11: ...IR FACTORY SUPPLIED RAIN FLASHING SUPPLY AIR MIS 548 A SIDE VIEW I A C K E 1 000 B 1 000 SUPPLY DUCT OVER FRAME INTERIOR FINISHED WALL ALL AROUND DUCT FRAMING MATERIAL EXTERIOR FINISH WALL OPENING FOR...

Страница 12: ...best unit performance and efficiency Review duct grille or return duct work Avoid using restrictive duct work to Unit Mount Return Grille Fixed Blade Wall wall Outside Wall Ducted Installations Adjus...

Страница 13: ...anel straight out This tab will now line up with the slot in the door When shut a padlock may be placed through the hole in the tab preventing entry See Start Up section for important information on t...

Страница 14: ...come out of the charging cylinder tank as a liquid to avoid any fractionation and to ensure optimal system performance Refer to instructions for the cylinder that is being utilized for proper method...

Страница 15: ...leaning of the outdoor coil to permit full and unrestricted airflow circulation is essential Sequence of Operation Cooling Stage 1 Circuit R Y makes at thermostat pulling in compressor contactor start...

Страница 16: ...wise the timing will remain accelerated and run through the 1 minute minimum defrost length sequence in a matter of seconds and will automatically terminate the defrost sequence There is an initiate d...

Страница 17: ...25 120 SW 1 SW 2 TIME SEC OFF OFF ON ON OFF ON OFF ON 30 60 180 MIS 2668 A OFF LOW PRESSURE BYPASS TIMER SWITCH FACTORY SETTING 120 SECONDS ACCUMULATED DEFROST TIME TIMER FACTORY SETTING 60 MIN ON FIG...

Страница 18: ...rmer is bad or the unit wiring is incorrect 10 Check for Compressor output signal Is there 24 volts AC between CC C Yes go to Step 12 No go to Step 13 11 No Y compressor input signal Check thermostat...

Страница 19: ...6 0 144374 22 0 43554 60 0 15310 98 0 6098 15 0 139576 23 0 42295 61 0 14921 99 0 5961 14 0 134956 24 0 41077 62 0 14544 100 0 5827 13 0 130506 25 0 39898 63 0 14177 101 0 5697 12 0 126219 26 0 38757...

Страница 20: ...ty The following pressure tables show nominal pressures for the units Since many installation specific situations can affect the pressure readings this information should only be used by certified tec...

Страница 21: ...WB LOW SIDE HIGH SIDE 147 321 147 341 147 362 148 387 150 415 151 444 153 476 156 510 158 548 161 587 C48H 75 DB 62 WB LOW SIDE HIGH SIDE 137 315 137 336 138 360 139 385 141 412 142 442 143 473 145 50...

Страница 22: ...3 8 45 52 50 60 8 6 10 10 A20 1 or 3 113 125 2 6 45 52 52 50 60 52 8 6 6 10 10 10 C60H1 B0Z 230 208 60 3 1 32 45 8 10 B06 1 50 60 8 10 B09 1 59 60 6 10 B15 1 59 60 6 10 B18 2 N A N A N A N A 59 28 60...

Страница 23: ...variable speed ECM indoor motor that automatically adjusts itself to maintain approximately the same rate of indoor airflow in both heating cooling dry and wet coil conditions and at both 230 208 or 4...

Страница 24: ...ontrol replacement check Perform Moisture Check Motor won t start Motor rocks but won t start Check for loose or compliant motor mount Make sure blower wheel is tight on shaft Perform motor control re...

Страница 25: ...motor plug just removed to the motor shell is 100K ohms see Figure 11 Measure to unpainted motor end plate If any motor lead fails this test do not proceed to install the control module the motor is d...

Отзывы: