18
UNILUX-6 52
Installation instructions
The minimum depth of the constructional hearth is 500 mm. A superimposed hearth on
top of the constructional hearth must have a minimum depth of 225 mm and must be
free of any combustible material. The actual depth of a superimposed hearth is depen-
dent on the installation height of the appliance. The higher the appliance is installed the
deeper the superimposed hearth should be to avoid scorched fl oor coverings. On the
diagram below the minimum depth of the superimposed hearth in relation to the height
of the appliance can be determined.
Figure 2: Minimum depth of the superimposed hearth in relation to the height
of the appliance
Figure 1: Minimum dimensions appliance
The constructional hearth and a superimposed hearth must have a width extending at
least 150 mm from each side of the appliance.
A = Superimposed hearth
B = Constructional hearth
B
150 mm
150 mm
A
Min. 500 mm
Min. depth
see diagram
Содержание UNILUX-6 52
Страница 2: ......
Страница 3: ...3 UNILUX 6 52 Installation instructions...
Страница 4: ...4 UNILUX 6 52 Installation instructions...
Страница 6: ...6 UNILUX 6 52 Installation instructions...
Страница 42: ...42 UNILUX 6 52 Installation instructions 7 DIMENSIONS 7 1 without frame...
Страница 43: ...43 UNILUX 6 52 Installation instructions 7 2 with built in frame...
Страница 44: ...44 UNILUX 6 52 Installation instructions 7 3 with classic frame...
Страница 45: ...45 UNILUX 6 52 Installation instructions 7 4 45 with classic frame...
Страница 46: ...46 UNILUX 6 52 Installation instructions 7 5 with deepened frame...
Страница 51: ......
Страница 52: ...01 080515 340447 Your Barbas dealer...