Installation and Operating Instructions

VOC Room Sensor in the BAPI-Stat 3 Enclosure 

with Differential Ground Configuration

Building Automation Products, Inc., 750 North Royal Avenue, Gays Mills, WI  54631 USA

Tel:+1-608-735-4800 • Fax+1-608-735-4804 • E-mail:[email protected] • Web:www.bapihvac.com

Specifications subject to change without notice.

29156_ins_voc_room_dif_gnd

3 of 8

rev. 06/05/18

Terminal 

Function

SP1 & SP2

 ..... Setpoint output.  Not available with voltage outputs.

 

NOT connected to GND

 

Optional Override Output

EXT

................. External occupied LCD indicator is activated by 

logic LOW or ground at this terminal.  (5VDC Max 

for OFF)

SN+ & SN-

 ...... Temperature Sensor Output (Resistive Output). 

 

NOT connected to GND.

 

(For Semiconductors: SN+ = +, SN- = -)

 

Optional Override Output

CO2/VOC

 ....... Voltage output VOC Signal (0 to 2,000 ppm)  

referenced to GND

HUM

 ............... Voltage output Humidity Signal referenced to the 

GND terminal

GND

 ................ To controller Ground [GND or Common]

PWR

 ............... Power, referenced to GND

 

9 to 35 VDC @ 50 mA Max 

 

(9 to 24VDC recommended) for 0 to 5 VDC Outputs 

 

15 to 35 VDC @ 50mA Max 

 

(15 to 24VDC recommended) for 0 to 10 VDC Outputs

  

Termination

Note: Unit is not ready for 

operation until the 15 minute 

start-up time has elapsed.

Fig 3: 

Circuit Board

Note: For proper operation, the 

jumper on PRG connector of J19 

must be connected by only one leg.

  Optional Test and Balance Switch (SW1)

Sensor Type

Low Temp

High Temp

1000   RTD

1.02K (41.2°F)

1.15K (101.5°F)

3000   Thermistor

7.87K (39.8°F)

1.50K (106.8°F)

10K-2 Thermistor

30.1K (34.9°F)

4.75K (109.1°F)

10K-3 Thermistor

26.7K (35.9°F)

5.11K (108.4°F)

10K-3(11K) Thermistor

7.32K (43.7°F)

3.65K (105.2°F)

BAPI recommends using twisted pair of at least 22AWG and sealant filled connectors for all wire connections. Larger 

gauge wire may be required for long runs. All wiring must comply with the National Electric Code (NEC) and local codes. 

Do NOT run this device’s wiring in the same conduit as AC power wiring.  BAPI’s tests show fluctuating and inaccurate 

signals are possible when AC power wiring is in the same conduit as the signal lines.  If you are experiencing any of these 

difficulties, please contact your BAPI representative

.

BAPI recommends wiring the product with power disconnected. Proper supply voltage, polarity and wiring 

connections are important to a successful installation.  Not observing these recommendations may damage the 

product and void the warranty.

Содержание VOC

Страница 1: ...o AC Power 0 to 5 VDC Output Units 9 to 35 VDC 50 mA Max 9 to 15 VDC recommended 0 to 10 VDC Output Units 15 to 35 VDC 50mA Max 15 VDC recommended Sensing Elements Humidity Capacitive Polymer 2 RH Accuracy VOCs Micro machined Metal Oxide Temp Sensor Thermistor RTD or Semiconductor Mounting 2 x4 J Box or drywall mount screws provided VOC Detection Range 0 to 2 000 CO2 PPM equivalent Response Time L...

Страница 2: ...rywall Mounting 1 Place the base plate against the wall where you want to mount the sensor 2 Using a pencil mark out the two mounting holes and the area where the wires will come through the wall 3 Drill two 3 16 holes in the center of each marked mounting hole DO NOT punch the holes or the drywall anchors will not hold Insert a drywall anchor into each hole 4 Drill one 1 2 hole in the middle of t...

Страница 3: ...DC Outputs Termination Note Unit is not ready for operation until the 15 minute start up time has elapsed Fig 3 Circuit Board Note For proper operation the jumper on PRG connector of J19 must be connected by only one leg Optional Test and Balance Switch SW1 Sensor Type Low Temp High Temp 1000 RTD 1 02K 41 2 F 1 15K 101 5 F 3000 Thermistor 7 87K 39 8 F 1 50K 106 8 F 10K 2 Thermistor 30 1K 34 9 F 4 ...

Страница 4: ...hree arrow icons are used with the ARW option to show VOC levels and their meaning The main display indicates the numeric value of the quantity being displayed The minor display indicates the engineering units of the value such as VOC F C or RH Temperature Setpoint Slide Pot Moving the slide pot enough to change the setpoint by one degree will display the setpoint on the main display if equipped w...

Страница 5: ...ay Information Figs 12 and 13 show how to place the unit into field setup mode to adjust the parameter offsets and display functions shown in Table 1 below Take the jumper from the BNK terminals and place it on the PRG terminals The F C jumper is omitted for clarity The major display should read P1 and the minor display should read DSP Use the UP DN buttons See Fig 14 to select the desired page Pr...

Страница 6: ...splay Time in Minutes 0 1 2 3 4 5 6 7 8 9 10 11 12 13 14 15 Zero VOC Sensor Acclimation 5 Dynamic Range Estimate Apply Test Gas Undefined Dynamic Range Calculation Adapting to Environment 22 5 Normal Operation Normal Operation Power ON ON Icon Illuminates ON Icon Extinguished Fig 19 Sensor Start up Timeline BAPI s VOC sensor contains an adaptive self adjusting Volatile Organic Compound VOC sensor ...

Страница 7: ... at 450 ppm CO2 equivalent Display units will show 450 ppm equivalents B At 15 minutes the VOC sensor will terminate the start up period and begin normal operation C The VOC output will now report the VOCs present as CO2 equivalents 4 Result Analysis and Recommendations A The VOC algorithm requires a dynamic range of greater than 30 for proper operation Sensors reporting a dynamic range of 30 or l...

Страница 8: ...connect sensor and check power wires for proper voltage see specs on pg 1 Wait 15 minutes after a power interruption Check all software parameters Determine if the sensor is exposed to an external environment different from the room conduit draft Check all software parameters If available check the sensor against a calibrated instrument such as a hygrometer Determine if the sensor is exposed to an...

Отзывы: