PROBLEMS:

No voltage on output

Voltage on output is reading low or high

POSSIBLE SOLUTIONS:

-  Verify that input voltage is correct
-  If the unit has a replaceable glass fuse, check it for continuity. If a 

replacement fuse is needed, replace it wth a 4.0 A fuse.

 

*Loading higher value fuses may cause damage and void 

warranty

-  If the unit has a resettable fuse and the fuse is tripped, it may 

be an output short circuit or overload. Remove input power and 

determine the problem. When the problem is corrected, reapply 

power to the unit.

-  Verify that input voltage is correct
-  Verify that the “Output Adjust” trim potentiometer is set correctly 

using the “Voltage Output Adjustment” procedure shown below

-   Check wiring for proper termination

VC3000 

series voltage converters have an adjustable output of 1.2 to 24 VDC. Adjust output to a custom 

voltage as follows:
1.  Using a voltmeter, connect the positive lead to the “+” and the negative lead to the “-” of the  terminal block 

labeled “VDC”. 

2.  With a small, straight bladed screwdriver, adjust the “Output Adjust” trim potentiometer (located next to the  

“VDC” terminal block) until the voltmeter reads the desired output. 

3.  Disconnect the voltmeter 
4.  Connect the load. 
5.  If exact output voltage is required, measure the voltage out under load and adjust accordingly.

Voltage Output Adjustment

Diagnostics

Half Wave

  Input Voltage ............18 to 28 VAC

  Input Current ............3.1 Amps AC max @ 24 VAC (75 VA)

  Output Voltage .........1.2 to 24 VDC @ 1.5 Amps max 

  Output Ripple ...........20 mV max

Full Wave

  Input Voltage ............18 to 28 VAC

  Input Current ............4.1 Amps AC max @ 24 VAC (98 VA)

  Output Voltage .........1.2 to 24 VDC @ 2.5 Amps max

  Output Ripple ...........25 mV max