Radio

General

ETSI/EN: In accordance with EN 300 328: V1.7.1
(2006-05)
IC: 7044A-DX8024

Spread Spectrum Technology

FHSS (Frequency Hopping Spread Spectrum)

Antenna Connection

Ext. Reverse Polarity SMA, 50 Ohms
Max Tightening Torque: 0.45 N·m (4 in·lbf)

Link Timeout

Gateway: Configurable
Node: Defined by Gateway

* With the 2 dB antenna that ships with the product. High-gain an-
tennas are available, but the range depends on the environment
and line of sight. To determine the range of your wireless network,
perform a Site Survey.

DX80 and DX80...C Mounting: #10 or M5 (SS M5 hard-
ware included)
DX80...E Mounting: 1/4-inch or M7 (SS M7 hardware
included)
Max. Tightening Torque: 0.56 N·m (5 in·lbf)

Interface

Indicators: Two bi-color LEDs
Buttons: Two
Display: Six character LCD

Wiring Access

DX80: Four PG-7, One 1/2-inch NPT, One 5-pin Euro-
style male connector
DX80...C: External terminals
DX80...E: Two 1/2-inch NPT

* For European applications, power the DX80 from a Limited Pow-
er Source as defined in EN 60950-1.

Inputs

Outputs

Discrete Input

Rating: 3 mA max current at 30V dc
Sample Rate: 1 second
Report Rate: On change of state

Discrete Input ON Condition

PNP: Greater than 8V
NPN: Less than 0.7V

Discrete Input OFF Condition

PNP: Less than 5V
NPN: Greater than 2V or open

Thermocouple Inputs

Sample Rate: 8 seconds
Report Rate: 32 seconds
Accuracy: 0.1% of full scale r 0.8° C
Resolution: 0.1° C, 24-bit A/D converter

Thermistor (used for CJC)

Model: BWA-THERMISTOR-001
Accuracy: 0.4° C (10 to 50° C); Up to 0.8° C (−40 to
+85° C)
Resolution: 0.1° C, 24-bit A/D converter

Discrete Output

Update Rate: 1 second
ON Condition: Less than 0.7V
OFF Condition: Open

Discrete Output Rating (Performance NMOS)

Less than 1 A max current at 30V dc
ON-State Saturation: Less than 0.7V at 20 mA

Output State Following Timeout

De-energized (OFF)

Environmental

Rating

DX80 models:IEC IP67; NEMA 6; (See UL section be-
low for any applicable UL specifications)
DX80...C models: IEC IP20, NEMA 1
DX80...E models: IEC IP54; NEMA 4

Conditions

Operating Temperature (P3 and P3C models): −40 to
+85° C (Electronics); −20 to +80° C (LCD)
Operating Temperature (P3E model): −40 to +65° C

Shock and Vibration

IEC 68-2-6 and IEC 68-2-7
Shock: 30g, 11 millisecond half sine wave, 18 shocks
Vibration: 0.5 mm p-p, 10 to 60 Hz

Refer to the SureCross

®

 DX80 Wireless I/O Network product

manual, Banner p/n 132607, for installation and waterproofing in-
structions. Operating the devices at the maximum operating condi-
tions for extended periods can shorten the life of the device.

 

 

SureCross Performance FlexPower Node

10

www.bannerengineering.com - tel: 763-544-3164

P/N 155863_web

Rev. C

Содержание SureCross Performance DX80N2X1S-P3E FlexPower

Страница 1: ...ete list of accessories refer to Banner Engineering s website www bannerengineering com surecross Models Frequency Power Housing I O DX80N9X2S P3 900 MHz ISM Band 10 to 30V dc or battery supply mod ule IP67 NEMA 6 Inputs Two selectable discrete four ther mocouple one thermistor for CJC Outputs One NMOS sinking discrete DX80N9X1S P3E 10 to 30V dc or integrated battery IP54 NEMA 4 DX80N2X2S P3 2 4 G...

Страница 2: ...g its Modbus RTU RS 485 connection is a Modbus slave to a Modbus RTU host controller the wireless network may contain up to 47 Nodes in a single wireless network and the Gateway holds the Modbus registers of all wireless devices within the network A Node is a wireless network end point device used to provide sensing capability in a remote area or factory The Node collects data from sensors and com...

Страница 3: ... To access the internal DIP switches follow these steps 1 Unscrew the four screws that mount the cover to the bottom housing 2 Remove the cover from the housing without damaging the ribbon cable or the pins the cable plugs into 3 Gently unplug the ribbon cable from the board mounted into the bottom housing For integrated battery models no ribbon cable and Class I Division 2 certified devices ribbo...

Страница 4: ...1600 degrees Fahrenheit or 1600 degrees Celsius switch the DIP switch to the ON position and use low resolution mode In high resolution the device cannot store values larger than 1600 Temperature Units Use the DIP switch to specify if the temperature is stored in degrees Fahrenheit or Celsius The default position is OFF setting the temperature to Fahrenheit For Celsius measurements set this switch...

Страница 5: ... OUT x GND Ground dc common connection PWR Power 10 to 30V dc power connection DX80 C Wiring Wiring power to the DX80 C models varies depending the power requirements of the model Terminal Label Gateway DX85 10 to 30V dc Powered Nodes Battery Powered Nodes V 10 to 30V dc 10 to 30V dc Tx RS485 D1 B V dc common GND dc common GND dc common GND Rx RS485 D0 A B 3 6 to 5 5V dc Connecting dc power to the...

Страница 6: ... optional 2 RS 485 D1 B RS 232 Tx 3 dc common GND dc common GND 4 RS 485 D0 A RS 232 Rx The BAT connection is a low voltage connection to the internal battery Remove the internal battery if a low voltage source is connected to the BAT terminal When powering the device from the integrated battery the BAT connection must remain open Terminal Block IP54 A4 A1 A3 A2 GND A3 PWR DO1 DI1 A1 A1 A3 A2 A2 A...

Страница 7: ...mocouples are available by configuring the Node Thermocouple Range F Range C Type B 212 to 3 272 F 100 to 1 800 C Type C 32 to 4 208 F 0 to 2 320 C Type E 58 to 1 832 F 50 to 1 000 C Type J 292 to 1 382 F 180 to 750 C Type K 292 to 2 282 F 180 to 1 250 C Type L 328 to 1 652 F 200 to 900 C Type N 32 to 2 192 F 0 to 1 200 C Type R 32 to 2 912 F 0 to 1 600 C Type S 32 to 2 642 F 0 to 1 450 C Type T 2...

Страница 8: ...m an integrated battery ship from the factory in storage mode to conserve the battery To wake the device press and hold button 1 for five seconds To put any FlexPower or integra ted battery SureCross radio into storage mode press and hold button 1 for five seconds The radio is in storage mode when the LEDs stop blinking but in some models the LCD remains on for an additional minute after the radio...

Страница 9: ...risk of explosion if the battery is re placed incorrectly 4 After replacing the battery allow up to 60 seconds for the device to power up Properly dispose of your used battery according to local regulations by taking it to a hazardous waste col lection site an e waste disposal center or other facility qualified to accept lithium batteries As with all batteries these are a fire explosion and severe...

Страница 10: ...OFF Condition PNP Less than 5V NPN Greater than 2V or open Thermocouple Inputs Sample Rate 8 seconds Report Rate 32 seconds Accuracy 0 1 of full scale reading 0 8 C Resolution 0 1 C 24 bit A D converter Thermistor used for CJC Model BWA THERMISTOR 001 Accuracy 0 4 C 10 to 50 C Up to 0 8 C 40 to 85 C Resolution 0 1 C 24 bit A D converter Discrete Output Update Rate 1 second ON Condition Less than 0...

Страница 11: ... the most recent version of any documentation refer to our website www bannerengineering com 2006 2010 Banner Engineering Corp All rights reserved Banner Engineering Corp Limited Warranty Banner Engineering Corp warrants its products to be free from defects in material and workmanship for one year following the date of shipment Banner Engineering Corp will repair or replace free of charge any prod...

Отзывы: