background image

SureCross Performance Node 

 

Configurable Node with up to 12 sourcing discrete inputs or outputs 

 

The SureCross

® 

wireless system is a radio frequency network with integrated I/O that can 

operate in most environments and eliminate the need for wiring runs. Wireless networks are 

formed around a Gateway, which acts as the wireless network master device, and one or 

more Nodes. 

• Wireless industrial I/O device with up to 12 sourcing discrete inputs or outputs. Default 

configuration is set to 6 inputs and 6 outputs (without bit-packing). 

• Selectable transmit power levels of 250 mW or 1 Watt for 900 MHz models and 65 mW 

for 2.4 GHz models 

• 10 to 30V dc power input 

• DIP switches for user configuration 

• Frequency Hopping Spread Spectrum (FHSS) technology and Time Division Multiple 

Access (TDMA) control architecture ensure reliable data delivery within the unlicensed 

Industrial, Scientific, and Medical (ISM) band 

For additional information, updated docu- 

mentation, and accessories, refer to Ban- 

ner Engineering's website

www.banner- 

engineering.com/surecross

• Transceivers provide bidirectional communication between the Gateway and Node, in- 

cluding fully acknowledged data transmission 

• Lost RF links are detected and relevant outputs set to user-defined conditions 

 

Models 

Frequency 

I/O 

DX80N2X6S-P8-KR 

2.4 GHz ISM Band 

Discrete I/O: Up to 12 PNP inputs or up to 12 PNP outputs (for a total of 12 I/O) 

(Default configuration is 6 IN and 6 OUT, without bit-packing)

 

 

DX80...C (IP20; NEMA 1) models are also available. To order this model with an IP20 housing, add a C to the end of the 

model number: DX80N9X6S-P8C. 

 

 

 

 

          

WARNING: Not To Be Used for Personnel Protection 

Never use this device as a sensing device for personnel protection. Doing so could lead to serious 

injury or death. This device does not include the self-checking redundant circuitry necessary to allow its 

use in personnel safety applications. A sensor failure or malfunction can cause either an energized or de- 

energized sensor output condition. 

 

 

 

CAUTION: Never Operate 1 Watt Radios Without Antennas 

To avoid damaging the radio circuitry, never power up SureCross Performance or SureCross MultiHop (1 

Watt) radios without an antenna. 

 

 

 

SureCross User Configuration Tool 

 

The User Configuration Tool (UCT) offers an easy way to link I/O points in your wire- 

less network, view I/O register values graphically, and set system communication pa- 

rameters when a host system is not part of the wireless network. 

The UCT requires a special USB to RS-485 (model number BWA-UCT-900 for 1 Watt 

radios, BWA-HW-006 can be used for all other radios) converter cable to pass infor- 

mation between your computer and the Gateway. Download the most recent revi- 

sions of the UCT software from Banner Engineering's website: 

http://www.banneren- 

gineering.com/wireless

 

 

 

P/N 158215-KR 

Rev. C 

10/2013 

Содержание SureCross DX80N2-6S-P8-KR

Страница 1: ...ISM Band Discrete I O Up to 12 PNP inputs or up to 12 PNP outputs for a total of 12 I O Default configuration is 6 IN and 6 OUT without bit packing DX80 C IP20 NEMA 1 models are also available To order this model with an IP20 housing add a C to the end of the model number DX80N9X6S P8C WARNING Not To Be Used for Personnel Protection Never use this device as a sensing device for personnel protectio...

Страница 2: ...wing product manuals SureCross Quick Start Guide Banner part number 128185 SureCross Wireless I O Network Manual 132607 Web Configurator Manual used with Pro and DX83 models 134421 Host Configuration Manual 132114 Configuring the DIP Switches Before making any changes to the DIP switch positions disconnect the power DIP switch changes will not be recognized if power isn t cycled to the device For ...

Страница 3: ...re May 2011 this default position configures the device for 12 inputs and zero outputs bit packed In the OFF position users can send commands directly from the host system to the devices to select custom I O configuration Users may also use the User Configuration Tool UCT to write custom configuration In the ON position use DIP switches 5 through 8 to select one of the pre programmed discrete I O ...

Страница 4: ...acked values are stored in right justified format Input Param eter Bit 15 14 13 12 11 10 09 08 07 06 05 04 03 02 01 00 Input Point 0 0 0 0 0 0 0 IN 5 IN 4 IN 3 IN 2 IN 1 Parameter Data 0 0 0 0 0 OUT 7 OUT 6 OUT 5 OUT 4 OUT 3 OUT 2 OUT 1 Defining Inputs and Outputs Using the UCT To configure either a Gateway or Node select the Gateway or specific Node from the dropdown list To configure a DX85 Remo...

Страница 5: ...Performance and non Performance radios within the same network refer the technical note titled Mixing Performance Radios and 150 mW Radios in the Same Networklisted on the FAQ Knowledgebase section of Banner s Wireless Sensor Networks website Wiring Your SureCross Device Use the following wiring diagrams to first wire the sensors and then apply power to the SureCross devices 5 pin Euro Style Wirin...

Страница 6: ...and 12 for the outputs For the default configuration of 6 IN and 6 OUT use IO 1 through 6 to wire the inputs and IO 7 through 12 to wire the outputs Discrete Input Wiring for PNP Sensors Discrete Output Wiring PNP 10 30V dc PWR DIx PWR DOx GND Load 10 30V dc dc common The DIx and DOx of these wiring diagrams correspond to the IOx on the terminal block DX80 C Wiring Wiring power to the DX80 C model...

Страница 7: ...d Discrete OUT 0 1 0 1 IO1 to IO12 10 10 10 Node 16 Non Bit Packed Discrete OUT de pending on DIP switch configuration 11 11 11 Node 16 12 12 12 Node 16 13 13 13 Node 16 14 14 14 Node 16 15 15 15 Node 16 Control Message 16 16 16 Node 16 Reserved Specifications Radio General Range 900 MHz 1 Watt Up to 9 6 kilometers 6 miles 2 4 GHz Up to 3 2 kilometers 2 miles Transmit Power 900 MHz 1 Watt 30 dBm 1...

Страница 8: ... applications power the DX80 from a Limited Power Source as defined in EN 60950 1 Inputs Outputs Discrete Inputs Rating 3 mA max current at 30V dc Sample Rate 62 5 milliseconds Report Rate On change of state ON Condition PNP Greater than 8V OFF Condition PNP Less than 5V Discrete Outputs Update Rate Up to 62 5 milliseconds ON Condition PNP Supply minus 2V OFF Condition PNP Less than 2V Output Stat...

Страница 9: ... take responsibility for the violation of any warning listed in this document Make no modifications to this product any modifications to this product not expressly approved by Banner Engineering could void the user s authority to operate the product All specifications published in this document are subject to change Banner reserves the right to modify product specifications or to update docu menta...

Отзывы: