Internal Temperature = ((A
–
L) / (H
–
L)) × 5 + T
A
Table 58: Temperature
the ADC Value obtained from the controller
L
the ADC value on the lookup table less than or equal to A
H
the ADC value on the lookup table greater than A
T
the temperature associated with the L value
9.7.3 Actuator Distance
Convert the binary reading into a number. If the number matches an ADC value in the following table, read the distance. If
the number is between the readings in the table, use the following formula to obtain the actual distance.
ADC Reading
Temperature (°C)
41
-40
54
-35
69
-30
88
-25
110
-20
136
-15
165
-10
199
-5
237
0
278
5
321
10
367
15
414
20
461
25
508
30
554
35
598
40
640
45
679
50
715
55
748
60
778
65
804
70
829
75
850
80
869
85
886
90
901
95
914
100
926
105
936
110