Teaching Analog Output Limits

The procedure for teaching analog output limits and discrete output limits is the same, except that the analog output has no hysteresis.

The analog output has one unique 

function:

 the discrete output limits Q1.1 and Q1.2 can be copied. To copy the discrete output limits

to the analog output, follow the steps below:
1.

Press 

 and 

 or 

 and 

 to scroll to TEACH-IN > <ANALOG>.

The sensor is ready to learn the analog output limits. The procedure is 

identical

 to the one for teaching discrete output limits, except

for the Copy and Paste 

function.

2.

Press 

 or 

 to copy and paste Q to A. COPY Q->A > <ENTER> .

The sensor is ready to copy the discrete output limits to the analog output.

3.

Press 

 to view the 

options.

4.

Press 

 and 

 to scroll between 

options.

5.

Press 

 to select an 

option.

• COPY Q->A > ->Q1 & Q2 .

• COPY Q->A ->Q2 & Q1.

• <300 mm
The selected 

option,

 in 

combination

 with the selected mode, determines the analog output slope.

• For Mode 1 

(positive

 slope): Q1 & Q2 – Limit Q1.1 becomes A1 (4 mA); Q2.1 becomes A2 (20 mA) Q2 & Q1 – Limit Q1.1

becomes A2 (20 mA); Q2.1 becomes A1 (4 mA)

• For Mode 2 

(negative

 slope): The above is reversed. If discrete limits are not at least 300 mm apart, the display will show <

300 mm. The sensor will not perform the copy 

function.

Accessing the 

Offset

 Menu

To access the OFFSET < 0 > menu, to save the current 

offset

 value

3

 (sensing distance), or to adjust it, follow the steps below:

1.

Press 

 to access the 

Offset

 < 0 > menu. OFFSET 0 > OFFSET 426 or OFFSET 0 > OFFSET CLEAR? is displayed.

OFFSET 0 returns the sensor to the default 

setting.

 OFFSET 426 represents a programmed 

offset

 value with the current sensing

distance expressed in millimeters or one-hundredth of one inch. Select OFFSET CLEAR? when an 

offset

 value is displayed that needs

to be cleared before a new one can be programmed.
• To clear an 

offset

 value, go to Step 2.

• To save an 

offset

 value, go to Step 3.

• To adjust an 

offset

 value, go to Step 4.

2.

Press 

 to clear the 

offset

 value: OFFSET CLEARED!.

The 

offset

 value is cleared. The sensor returns to the Main menu.

3.

Press 

 to save the current 

offset

 value if it is correct.

4.

Press 

 and 

 to 

activate

 the 

Offset

 Value Adjustment 

function:

 OFFSET 0 > OFFSET 426.

The cursor 

flashes

 on the fourth digit from the 

left.

5.

Press 

 to decrease or 

 to increase the value of each digit: OFFSET - 428 or  428.

Press 

 or 

 to change the minus symbol in front of the 

first

 digit to a plus symbol and vice versa.

6.

Press 

 to save the digit and to move the 

flashing

 cursor to the 

left

 by one digit 

location.

The sensor saves each digit, including the + and - symbols.

7.

Press 

 when the cursor is on the 

first

 digit to the 

left

 and the value is correct. OFFSET < -428> or OFFSET < +428>.

The new 

offset

 value is saved. The sensor returns to the Main menu.

3 The selected 

offset

 value applies to all outputs.

L-GAGE

®

 LT7 Long-Range Time-of-Flight Laser Sensor

 

 

P/N 120244 Rev. C

www.bannerengineering.com - Tel: +1-763-544-3164

11

Содержание L-GAGE LT7 Series

Страница 1: ...use in personnel safety applications A sensor failure or malfunction can cause either an energized or de energized sensor output condition Models Models Sensing Mode Laser Class Cable1 Sensing Range2...

Страница 2: ...aser pilot laser for alignment Both lasers are aimed at the identical target spot The laser beams are collimated to focus on a compact spot even at long sensing distances Diffuse Retroreflective 10 m...

Страница 3: ...range 5 mm hysteresis QA analog Mode 1 rising positive slope full sensing range Offset 0 Unit mm Serial RS422 Password OFF Hysteresis Manually adjustable in 1 mm steps symmetrically around the switch...

Страница 4: ...Limit 1 and Discrete Limit 2 to the analog output When copying discrete limits to analog Discrete Limit 1 and Discrete Limit 2 must be at least 300 mm apart or the sensor will not copy the limits The...

Страница 5: ...rence 60825 1 Amend 2 IEC 2001 E section 8 2 Class 2 Visible Pilot Laser Lasers that emit visible radiation in the wavelength range from 400 nm to 700 nm where eye protection is normally afforded by a...

Страница 6: ...gnment Aid The measuring sensing laser is located where the pilot laser spot is For fine adjustment use bracket SMBLT7 with the fine adjust accessory kit SMBLT7F for an angle of up to 3 in both X and...

Страница 7: ...30 V dc H RX Black RS422 Receiver data SS1 Clock J NC Violet K TX Gray Pink RS422 Transmitter data SS1 Data L Q2 Red Blue Discrete Output 2 M GND Blue 0 V GND Installation Notes Some targets pose spec...

Страница 8: ...ement laser stays ON alternating with the pilot laser The sensor proceeds to QuickSet on the Main menu Teaching the Outputs with QuickSet The received signal value is displayed as a bar graph the more...

Страница 9: ...ASSWORD 1234 and the message PASSWORD OK 9 Press to save the password The sensor proceeds to QuickSet on the Main menu Accessing QuickSet Teach the current conditions to output Q1 and output Q2 with Q...

Страница 10: ...to select the digit and move it to the left by one digit location 14 Press when the cursor flashes on the first digit on the left and the value is correct The sensor saves the setting and returns to...

Страница 11: ...or to adjust it follow the steps below 1 Press to access the Offset 0 menu OFFSET 0 OFFSET 426 or OFFSET 0 OFFSET CLEAR is displayed OFFSET 0 returns the sensor to the default setting OFFSET 426 repr...

Страница 12: ...intact 4 Press ESCAPE to return to Run mode DIST in 4839 The sensor returns to the Main menu with factory default settings intact Serial Communications Choose a RS422 compatible SSI1 10 compatible or...

Страница 13: ...it command ASCII text Data Whole numbers ASCII text Note In ASCII text Command Data spaces and uppercase lowercase letters are ignored RS422 Cable The RS422 interface is a reliable serial interface in...

Страница 14: ...put desired value ACK Input Offset Setting All Outputs Up to 12000 mm plus or minus or 48000 in plus or minus 4 IVL 0 1 ACK Enable Visible Laser 0 pilot laser OFF 1 pilot laser ON ISB 0 1 ACK Input St...

Страница 15: ...d Do not insert a period or comma For example 12 000 mm is 12000 mm 480 00 in is 48000 Analog Output QA Commands and Their Meaning Only for diffuse sensor models Do not insert a period or comma For ex...

Страница 16: ...er error As a result the GSI command reports 00000110 Error Message Error Output Active Low Bit Response Sequence Meaning Qs Qp BLINDING Active 01000000 Internal error or ambient light too strong LAS...

Страница 17: ...t Mode Select Analog Output Slope Select diffuse models only and Output Limit Manual Adjust Serial Interface RS422 or SSI compatible Serial Measurement Speed RS422 2 9 ms at 57 6 kBaud SSI 1 4 ms SSI...

Страница 18: ...y pk TX SSI Data rd bu Output 2 PNP bu Gnd LT7PIDQ bannerengineering com bannerengineering com Class 1 L GAGETM 42 0 mm 1 65 93 0 mm 3 66 95 0 mm 3 74 42 8 mm 1 68 42 0 mm 1 65 81 5 mm 3 21 5 75 mm 0...

Страница 19: ...minum backing for use with LT7 Temperature 20 C to 50 C 4 F to 122 F Approximate size BRT 250 250 mm 250 mm BRT 540 540 mm 540 mm BRT 700 700 mm 700 mm Retroreflective Tape Model Reflectivity Factor M...

Страница 20: ...R ANY INCIDENTAL CONSEQUENTIAL OR SPECIAL DAMAGES RESULTING FROM ANY PRODUCT DEFECT OR FROM THE USE OR INABILITY TO USE THE PRODUCT WHETHER ARISING IN CONTRACT OR WARRANTY STATUTE TORT STRICT LIABILIT...

Отзывы: