![Banner DXM150-S Series Скачать руководство пользователя страница 21](http://html.mh-extra.com/html/banner/dxm150-s-series/dxm150-s-series_instruction-manual_471835021.webp)
* Setting Enable Full Scale to 1 sets the ranges to a linear scale of 0 to 65535.
4.6 Setting the Modbus Slave ID on the I/O Base Board
Only DXM150-Sx and SxR2 Modbus Slave models require that the Modbus Slave ID to be adjusted on the I/O base board.
The DXM150-Sx Wireless Modbus Slave devices use DIP switch J and rotary dial K to set the Modbus slave ID. The device
can use a Modbus register 6804 in the I/O board to access the full range of Modbus Slave IDs.
On the DXM150-Sx Wireless Modbus Slave models, use rotary dial K to select the lower digit of the Modbus Slave ID.
4.6.1
DXM150-Sx Wireless Modbus Slave
Models
DIP Switch location J defines the course group of Modbus Slave IDs. DIP Switch 4 must be set to ON for DXM1
xx
-Sx and
DXM1
xx
-SxR2 models.
Settings
Location J DIP Switches
1
2
3
4
Modbus Slave ID set to 11 through 19
OFF
OFF
Modbus Slave ID set to 20 through 29
ON
OFF
Modbus Slave ID set to 30 through 39
OFF
ON
Modbus Slave ID set to 40 through 49
ON
ON
Not Used
-
Modbus Slave Configuration (S1 model only) 2
ON
I2C Processor Communication
OFF
Rotary dial location K and DIP Switch location J set the Modbus Slave IDs.
DIP Switches J
Location K Rotary Dials — Position 0 through 9
1
2
0
1
2
3
4
5
6
7
8
9
OFF
OFF
x 3
11
12
13
14
15
16
17
18
19
ON
OFF
20
21
22
23
24
25
26
27
28
29
OFF
ON
30
31
32
33
34
35
36
37
38
39
ON
ON
40
41
42
43
44
45
46
47
48
49
DXM150-Sx Wireless Modbus Slave
Example
To set the DXM150-Sx Wireless Modbus Slave to a Modbus Slave ID of 25, set the following:
Location J DIP switches set to: 1= ON, 2=OFF
Rotary dial set to 5
The DIP switch sets the upper digit of the slave ID to 2 while the rotary dial sets the lower digit to 5.
4.6.2 Setting the DXM I/O Board Modbus Slave ID using Modbus Registers
Write to the I/O board's Modbus register 6804 to set the Modbus Slave ID to any valid Modbus Slave ID (1 through 245).
• For the DXM150-Sx Wireless Modbus Slave model, rotary dial K should be in the zero position to use the Modbus
register slave ID.
4.6.3 I/O Board Jumpers
Hardware jumpers on the DXM I/O board allow the user to select alternative pin operations. Turn the power off to the device
before you change jumper positions.
2 Must be in the ON position for the -S1 model)
3 Uses value in Modbus register 6804.
DXM150-Sx Wireless Modbus Slave
www.bannerengineering.com - Tel: +1.763.544.3164
21