X20(c)SA4430
Data sheet V1.141 X20(c)SA4430 Translation of the original documentation
21
14 Register description
14.1 Parameters in the I/O configuration
Group: Function model
Parameter
Description
Default value
Unit
Function model
This parameter is reserved for future functional expansions.
Default
-
Table 12: I/O configuration parameters: Function model
Group: General
Parameter
Description
Default value
Unit
System behavior when a module is missing
On
-
Module supervised
Parameter value
Description
On
A missing module triggers service mode.
Off
A missing module is ignored.
Module information
(up to AS 3.0.90)
This parameter enables/disables the module-specific information in the I/O
mapping:
•
SerialNumber
•
ModuleID
•
HardwareVariant
•
FirmwareVersion
Off
-
This parameter enables blackout mode (see section Blackout mode in Automa-
tion Help under: Hardware → X20 system → Additional information → Black-
out mode).
Off
-
Blackout mode
(hardware upgrade 1.10.1.1 or later)
Parameter value
Description
On
Blackout mode is enabled.
Off
Blackout mode is disabled.
SafeLOGIC ID
In applications with multiple SafeLOGIC controllers, this parameter defines the
module's association with a particular SafeLOGIC controller.
•
Permissible values: 1 to 1024
Assigned
automatically
-
SafeMODULE ID
Unique safety address of the module
•
Permissible values: 2 to 1023
Assigned
automatically
-
Table 13: I/O configuration parameters: General