12.5 Programming System Flash
The Power Panel is delivered without an operating system installed. An operating system can be
downloaded or updated using the programming software. Installation of the operating system is
possible with both programming systems. When carrying out operating system download for the
first time using B&R Automation Studio™ , the steps below must be taken:
1) Switch off power supply to the PLC.
2) Set the MODE switch to 00.
3) Switch on the power supply again.
4) Make on-line connection to PC (physcially).
5) Start B&R Automation Studio™ ("OFFLINE" is displayed in the status bar)
6) Select menu item "PROJECT" - "SERVICES" - "TRANSFER OPERATING SYSTEM"
7) A window named "Operating System Transfer" opens
8) The COM port can be changed in this window, if required. Only in this case (using the "Try
to connect Bootstraploader" button) must the connection be reestablished. If several PLC
sofware versions are available, these can also be selected.
9) By clicking on "Next" in the new window CAN bus specific settings can be made.
12.6 PCMCIA Slot
The Power Panels are equipped with one PCMCIA interface for B&R memory cards. PCMCIA
memory cards conforming to JEIDA V4.0 Type I or PCMCIA Standard Release 2.0 (max. 3 mm
high) are supported.
The memory on the PCMCIA card can be used with all types of B&R modules. Executable
programmes (Task) should not be stored on the PCMCIA card, because accessing the card
takes considerably longer than accessing the Power Panel's onboard memory.
FD
This setting should not to be used.
Update Mode
- In this switch position, the Power Panel checks if an update memory card is inserted. If no card
is inserted, the Power Panel goes into SERVICE mode. Otherwise (depending on the Update configuration) the
operating system and/or the user-ROM for the Power Panel is cleared and reinstalled from the memory card. If
an error occurs during the installation, the red ERROR LED blinks. When no errors have occurred during
installation the green READY LED and the yellow RUN LED blink.
FE
Reserved for B&R expansions – these settings are not allowed to be used!
FF
Diagnosis Mode
Switch Position
Description
Table 19: Switch settings for the MODE switch
Содержание PP21
Страница 2: ...2 Power Panel User s Manual...
Страница 3: ...Power Panel User s Manual 3 Chapter 1 Power Panel Chapter 2 Technical Appendix Index...
Страница 4: ...4 Power Panel User s Manual...
Страница 17: ...Power Panel User s Manual 17 Chapter 1 Power Panel Power Panel Power Panel PP21 5 4 Images Figure 3 PP21...
Страница 18: ...18 Power Panel User s Manual Power Panel Power Panel PP21 5 5 Dimensions Figure 4 PP21 dimensions...
Страница 24: ...24 Power Panel User s Manual Power Panel Power Panel PP41 6 4 Images Figure 6 PP41...
Страница 46: ...46 Power Panel User s Manual Power Panel Changing the Battery...
Страница 52: ...52 Power Panel User s Manual Technical Appendix Characters for LC Displays English Katakana...
Страница 54: ...54 Power Panel User s Manual Index T Technical Appendix 47 Terminal Block 40 V Visualization 33...
Страница 55: ...Power Panel User s Manual 55 Index Index...
Страница 56: ...56 Power Panel User s Manual Index...