Programming guidelines
ACOPOSinverter P84 User's Manual 2.10
209
[Auto DC injection] (AdC-)
Code
Name/Description
Setting range
Factory settings
AdC-
[Auto DC injection]
AdC
[Auto DC injection]
[Yes]
(YES)
Automatic current injection on stopping (at the end of the ramp)
nO
[No]
(nO)
: No activation.
YES
[YES]
(YES)
: Activation with adjustable duration
Ct
[permanent]
(Ct)
: Continuous activation at standstill.
Warning!
This function blocks the function
[Magnet Mot]
(FLU)
see "FLUXING BY LI (FLI-)" on page 217
). If
[Magnet Mot]
(FLU)
is set to
[permanent]
(FCt)
,
[Auto DC injection]
(AdC)
must be set to
[No]
(nO)
.
Note:
This parameter gives rise to the injection of current even if a run command has not been sent. It can be accessed with the frequency
inverter running.
SdC1
[Auto DC inj. level 1]
1)
0 to 1.2 In
2)
0.7 In
2)
Height of the DC connection at standstill
[Auto DC injection]
(AdC)
is not set to
[No]
(nO)
. For this parameter, the value 0 will be forced if
[Motor
control type]
(Ctt)
(
see "Drive parameters (Ctt)" on page 153
) =
[Sync. Motor.]
(SYn)
.
Caution!
Check that the motor will withstand this current without overheating.
Failure to follow this instruction can result in equipment damage.
tdC1
[Auto DC inj. time 1]
1)
0.1 to 30 s
0.5 s
Standstill injection time. The parameter can be activated if
[Auto DC injection]
(AdC)
is not set to
[No]
(nO)
.
If
[Typ Motor control]
(Ctt)
(
see "Drive parameters (Ctt)" on page 153
) is set to
[FVC]
(FUC)
or
[Sync. Motor]
(Syn)
, this time is the hold time
at zero speed.
SdC2
[Auto DC inj. level 2]
1)
0 to 1.2 In
2)
0.5 In
2)
2nd level of standstill DC injection current.
The parameter can be activated if
[Auto DC injection]
(AdC)
is not set to
[No]
(nO)
.
For this parameter, the value 0 will be forced if
[Motor control type]
(Ctt)
see "Drive parameters (Ctt)" on page 153
[Sync. Motor.]
(SYn)
.
Caution!
Check that the motor will withstand this current without overheating.
Failure to follow this instruction can result in equipment damage.
tdC2
[Auto DC inj. time 2]
1)
0 to 30 s
0 s
2nd standstill injection time.
The parameter can be activated if
[Auto DC injection]
(AdC)
is not set to
[Yes]
(YES)
.
AdC
SdC2
Function
YES
x
Ct
≠ 0
Ct
= 0
Movement command
Frequency
Note:
If
[Motor control type]
(Ctt)
is set to
[FVC]
(FUC)
:
[I DC-Auto braking 1]
(SdC1)
,
[I DC-Auto braking 2]
(SdC2)
and
[time aut. DC
brake2]
(tdC2)
cannot be activated. Only
[time aut. DC brake 1]
(tdC1)
can be activated. This is then a hold time at zero speed.
1)
This parameter can also be accessed via the
[SETTINGS]
(SEt-)
menu.
2)
In is the same as the rated current specified in the installation instructions and on the nameplate of the inverter.
Parameter that can be modified during operation or when stopped.
Содержание ACOPOSinverter P84
Страница 2: ......
Страница 384: ...Accessories 384 ACOPOSinverter P84 User s Manual 2 10 8I0FT180 300 1 A Nm lb in 8I0FT180 300 1 25 221 3...
Страница 391: ...Accessories ACOPOSinverter P84 User s Manual 2 10 391 4 7 2 Installation 8I0XF084 020 1...
Страница 392: ...Accessories 392 ACOPOSinverter P84 User s Manual 2 10 8I0XF084 030 1...
Страница 393: ...Accessories ACOPOSinverter P84 User s Manual 2 10 393 8I0XF084 040 1...
Страница 394: ...Accessories 394 ACOPOSinverter P84 User s Manual 2 10 8I0XF084 050 1...
Страница 395: ...Accessories ACOPOSinverter P84 User s Manual 2 10 395 8I0XF084 0x0 1...
Страница 400: ...Accessories 400 ACOPOSinverter P84 User s Manual 2 10...