X20 system modules • Other functions • X20CM8323
X20 system User's Manual 3.10
2233
4.26.4.9.4.5 Disables the high-speed cutoff
Name:
ConfigOutput21
This register can be used to enable or disable the high-speed cutoff for individual channels.
Data type
Value
USINT
See bit structure.
Bit structure:
Bit
Description
Value
Information
0
Enabled for Channel 1
0
High-speed cutoff
1
Disabled for Channel 1
...
...
0
Enabled for Channel 8
7
High-speed cutoff
1
Disabled for Channel 8
4.26.4.9.4.6 Configuration of the time base
Name:
TimeBase
This register can be used to configure the interval between current measurement points.
The interval between measurement points is normally one quarter of the defined X2X Link cycle. When using a
CAN controller this value is not available. The time base for the 1/4 measurement cycle must therefore be set
separately in Function model 254 - Bus controller.
Data type
Value
Information
UINT
400 to 10000
Measurement point interval in µs for 1/4 measurement cycle