4.26.2.5.8.4 FrequencyBandMin01-32
Asynchronous minimum value of the respective frequency band in thousandths of a mm/s or g depending on the
configuration. See also section 4.26.2.5.8 "Module registers - Minimum and maximum values" on page 2178 and
4.26.2.2.9 "Frequency bands" on page 2074 for additional information.
If the frequency band parameter is set to a velocity signal, then this value is only calculated if the EnableVelocity-
Calculation bit (configured in the "SensorConfig01" register) for the respective channel is set; otherwise, 0 is output.
4.26.2.5.8.5 Iso10816Max01-04
Asynchronous maximum value of the "ISO10816" characteristic value of the respective channel in thousandths
of a mm/s. See also section 4.26.2.5.8 "Module registers - Minimum and maximum values" on page 2178 for
additional information.
4.26.2.5.8.6 Iso10816Min01-04
Asynchronous minimum value of the "ISO10816" characteristic value of the respective channel in thousandths of a
mm/s. See also section 4.26.2.5.8 "Module registers - Minimum and maximum values" on page 2178 for additional
information.
4.26.2.5.8.7 KurtosisRawMax01-04
Asynchronous maximum value of the "KurtosisRaw" characteristic value of the respective channel in thousandths.
Since division by the RMS value takes place in the module ("RmsRaw"), there may be an overflow if the RMS value
is very small. To prevent this, the module has an internal lower limit of 1 mg for the RMS value.
See also section 4.26.2.5.8 "Module registers - Minimum and maximum values" on page 2178 for additional in-
formation.
4.26.2.5.8.8 KurtosisRawMin01-04
Asynchronous minimum value of the "KurtosisRaw" characteristic value of the respective channel in thousandths.
Since division by the RMS value takes place in the module ("RmsRaw"), there may be an overflow if the RMS value
is very small. To prevent this, the module has an internal lower limit of 1 mg for the RMS value.
See also section 4.26.2.5.8 "Module registers - Minimum and maximum values" on page 2178 for additional in-
formation.
4.26.2.5.8.9 MinMaxCounter01
This asynchronous register specifies how many measurements were collected the last time the minimum and
maximum were determined. It is only updated when an edge occurs for MinMaxUpdate01. If the MinMaxUpdate01
bit is not toggled after 65535 measurements, then the counter is limited to 65535. Determination of the minimum
and maximum continues, however. All asynchronous minimum and maximum values are only valid if "MinMax-
4.26.2.5.8.10 PeakHighFrequencyMax01-04
Asynchronous maximum value of the "PeakHighFrequency" characteristic value of the respective channel in
1/65536 g. See also 4.26.2.5.8 "Module registers - Minimum and maximum values" on page 2178 for additional
information.
4.26.2.5.8.11 PeakHighFrequencyMin01-04
Asynchronous minimum value of the "PeakHighFrequency" characteristic value of the respective channel in
1/65536 g. See also 4.26.2.5.8 "Module registers - Minimum and maximum values" on page 2178 for additional
information.
4.26.2.5.8.12 PeakRawMax01-04
Asynchronous maximum value of the "PeakRaw" characteristic value of the respective channel in 1/65536 g. See
also 4.26.2.5.8 "Module registers - Minimum and maximum values" on page 2178 for additional information.
4.26.2.5.8.13 PeakRawMin01-04
Asynchronous minimum value of the "PeakRaw" characteristic value of the respective channel in 1/65536 g. See
also 4.26.2.5.8 "Module registers - Minimum and maximum values" on page 2178 for additional information.