X20 system modules • X20 interface module communication • X20IF1053-1
1788
X20 system User's Manual 3.10
4.23.7.3 Technical data
Product ID
X20IF1053-1
Short description
Communication module
DeviceNet adapter (slave)
General information
B&R ID code
0xA715
Status indicators
Module status, network status, data transfer, terminating resistor
Diagnostics
Module status
Yes, using status LED and software
Network status
Yes, using status LED and software
Data transfer
Yes, using status LED
Terminating resistors
Yes, using status LED
Power consumption
1.1 W
Additional power dissipation caused by the actua-
tors (resistive) [W]
-
Electrical isolation
PLC - IF1
Yes
Certification
CE
Yes
cULus
Yes
ATEX Zone 2
Yes
KC
Yes
GL
Yes
GOST-R
Yes
Interfaces
IF1 interface
Fieldbus
DeviceNet adapter (slave)
Design
5-pin male multipoint connector
Max. distance
500 m
Transfer rate
Max. 500 kbit/s
Terminating resistors
Integrated in the module
Controller
netX100
Operating conditions
Mounting orientation
Horizontal
Yes
Vertical
Yes
Installation at elevations above sea level
0 to 2000 m
No limitations
>2000 m
Reduction of ambient temperature by 0.5°C per 100 m
EN 60529 protection
IP20
Environmental conditions
Temperature
Operation
Horizontal installation
-25 to 60°C
Vertical installation
-25 to 50°C
Derating
-
Storage
-40 to 85°C
Transport
-40 to 85°C
Relative humidity
Operation
5 to 95%, non-condensing
Storage
5 to 95%, non-condensing
Transport
5 to 95%, non-condensing
Mechanical characteristics
Note
Order 1x TB2105 terminal block separately
Slot
In the X20 CPU and in the X20BC1083 expandable bus controller
Table 563: X20IF1053-1 - Technical data
4.23.7.4 LED status indicators
Figure
LED
Color
Status
Description
Green/red
Off
No power to module
Green
On
PCI bus communication in progress
READY/RUN
Red
On
Communication on the PCI bus has not yet been started
Green/red
Off
Module supply not connected or module is not online
Blinking
Module is online but the I/O connection is not active
Green
On
Module is online and the I/O connection is active ("operating")
Blinking
The red LED blinks if at least one of the following errors has occurred:
•
Minor fault (recoverable fault)
•
Connection error
•
No DeviceNet supply voltage
MOD/NET
Red
On
Critical fault or critical connection error (double MAC ID, bus failure or module
defect)
TxD
Yellow
Flickering or
on
Module sending data via the DeviceNet interface
TERM
Yellow
On
Terminating resistor integrated in the module switched on