Setup and Connections
Vlinx MESP211 Modbus Gateway
12
lines are differential pairs (A & B) in which the B line is positive relative to the A line in the
idle (mark) state. Ground provides a common mode reference.
When configured for
2-wire operation
the connection supports one signal pair: Data B(+)
and Data A(-) signal channels using half-duplex operation. The data lines are differential
with the Data B line positive relative to Data A in the idle (mark) state. Ground provides a
common mode reference.
CONNECTING THE MESP211
The
MESP211
has either a DB9M serial connector or a 5-position terminal block connector.
If you select RS-232 mode when you configure the Modbus Gateway, you must connect the
Modbus serial network to the Modbus Gateway via a serial cable. The MESP211 is a DTE. If
the Modbus network is a DTE, use a null modem (cross-over) cable. If the Modbus network
is a DCE, use a straight-through cable. DTE and DCE ports are complementary, the
Output
signals on a DTE port are
Inputs
to a DCE port, and
Output
signals on a DCE port are
Inputs
to a DTE port. The signal names match each other and connect pin for pin. Signal
flow is in the direction of the arrows
MESP211 Serial Connections
Figure 10.
Содержание Vlinx MESP211
Страница 1: ...1 www bb elec com www bb europe com Vlinx MESP211 Ultra Compact Modbus Gateway...
Страница 32: ...Setup and Connections Vlinx MESP211 Modbus Gateway 31 Modbus Port Screen Figure 32...
Страница 55: ...Setup Examples Vlinx MESP211 Modbus Gateway 54 Modbus Priority Figure 51...
Страница 66: ...Appendices Vlinx MESP211 Modbus Gateway 65 www bb elec com www bb europe com APPENDIX C DIMENSIONAL DIAGRAM...