2.1. RS-232 (Interactive & Block modes)

Interactive and Block modes support the 3-wire RS-232 configuration with TXD,

RXD and signal common. The cable requires an overall shield to protect against

electrical noise. Xon and Xoff can be used for communication handshaking.

3-Wire RS-232

Host Controller

MAP450D Terminal Block

TXD

Pin 9

-

RXD

RXD

Pin 10

-

TXD

Signal Ground

Pin 8

-

Return

2.2. RS-422/485 (Interactive & Block modes)

Interactive and Block modes support the 3-wire and 5-wire RS-422/485

configurations. The 3-wire configuration has both transmit and receive on the same

pair of wires plus a signal common. The 5-wire configuration has differential signal

pairs for transmit and receive plus a signal common. In both configurations the

signal pairs must be twisted and surrounded by an overall shield.

NOTE:

When using 3-wire RS-422/485, Jumper JP4 must be in position “B”.

Refer to section 2.4 for instructions.

3-Wire RS-422/485

Host Controller

MAP450D Terminal Block

TXD+ & RXD+

Pins 4 & 6

-

RXD+ & TXD+

TXD- & RXD-

Pins 5 & 7

-

RXD- & TXD-

Signal Ground

Pin 8

-

Return

5-Wire RS-422/485

Host Controller

MAP450D Terminal Block

TXD+

Pin 4

-

RXD+

TXD-

Pin 5

-

RXD-

RXD+

Pin 6

-

TXD+

RXD-

Pin 7

-

TXD-

Signal Ground

Pin 8

-

Return

INSTALLATION MANUAL

9

1010-0046A, REV 00

Содержание MAP450D-004 MAP450D

Страница 1: ... C D F E P N V W INSTALLATION MANUAL 1010 0046A REV 00 Secure online ordering 24 7 365 from European Headquarters Westlink Commercial Park Oranmore Co Galway Ireland www bb europe com Phone 353 91 792444 orders bb europe com Fax 353 91 792445 support bb europe com International Headquarters 707 Dayton Rd P O Box 1040 Ottawa IL 61350 USA www bb elec com Phone 815 433 5100 orders bb elec com Fax 815...

Страница 2: ...cense is granted by implication or otherwise under any patent or patent rights of Maple Systems Inc Maple Systems retains the right to revise or change its products and documentation at any time without notice IF SERVICE IS REQUIRED Package the unit in its original packaging container or if unavailable any suitable rigid container If a substitute container is used surround the unit with shock abso...

Страница 3: ...e circuitry inside is exposed to possible damage by electrostatic discharge during handling Minimize the possibility of electrostatic discharge by Discharging personal static by grounding yourself prior to handling the OIT Handling the OIT at static free grounded work stations Connecting the chassis of the OIT to a clean ground Placing the OIT into an anti static bag during transport Unpacking the...

Страница 4: ...D to a Host Controller 7 2 1 RS 232 Interactive Block modes 9 2 2 RS 422 485 Interactive Block modes 9 2 3 RS 422 485 Network mode 10 2 4 Set Jumper for 3 Wire RS 422 485 13 3 Mounting the MAP450D 14 3 1 Panel Mount 14 3 2 Pedestal Pendent Mount 15 3 3 Benchtop Mount 16 4 Configuring the MAP450D 17 4 1 Connecting the MAP450D to a PC 17 Appendix A OIT Hardware Specifications 18 Appendix B Differenc...

Страница 5: ...re braid should be installed from the hinged control panel to the rest of the enclosure 1 2 Power Supply Selection The power supply used to power the OIT should have an output between 12 and 30 VDC The voltage should measure between 12 and 30V at the OIT between Pins 2 and 3 of the OIT terminal block A 24 VDC 0 5 amp linear power supply dedicated to the OIT is recommended The power leads on the op...

Страница 6: ...ches 20 cm of separation between the OIT cables and other power wiring If voltages greater than 120 VAC are used in the system greater separation is required IftheOITcablesmust come nearAC wiring make sure theycrossat90degrees Running AC power wires in a separate grounded conduit is the preferred method for electrical noise reduction Keep the lengths of the OIT cables as short as possible Do not c...

Страница 7: ...nk tubing from the end of the OIT operating cable 4 Slide the ferrite coil over the OIT operating cable This usually requires rotating the ferrite coil back and forth while simultaneously pulling on the OIT operating cable 5 Slide the ferrite coil up against the inside wall of the OIT enclosure and pull through enough additional cable to reconnect the OIT operating cable wires INSTALLATION MANUAL ...

Страница 8: ...inst the inside wall of the OIT enclosure with the protruding OIT operating cable kept short 9 Tighten the cable strain relief nut 10 Re install the four screws into the back of the OIT enclosure 11 Route the operating cable to the host controller and connect 12 Route the power pigtail to the OIT power supply 13 Install the wires into the power supply as follows RED output BLACK output SHIELD case...

Страница 9: ...e configuration has both transmit and receive on the same pair of wires plus a signal common The 5 wire configuration has differential signal pairs for transmit and receive plus a signal common In both configurations the signal pairs must be twisted and surrounded by an overall shield NOTE When using 3 wire RS 422 485 Jumper JP4 must be in position B Refer to section 2 4 for instructions 3 Wire RS...

Страница 10: ...at the same time 3 wire RS 422 485 only supports half duplex communications which means that the host controller cannot transmit and receive data at the same time Although 3 wire RS 422 485 installations may be less costly than 5 wire installations the increased complexity in programming the host controller for 3 wire RS 422 485 may increase development time 10 MAP450D 1010 0046A REV 00 5 COM RXD ...

Страница 11: ...le in this mode Therefore each command sent from the host controller should end with the appropriate line terminator If the host controller sends a command that requires a response from the OIT the host controller must wait for a response from the OIT before sending another command Otherwise a situation can occur in which the OIT and the host controller attempt to transmit at the same time cuasing...

Страница 12: ... Network Grounding To communicate properly serious attention must be paid to the grounding scheme of the devices connected to the com link Improper grounding improper termination and faulty shielding of the com link are the most common causes of system failure in a multidrop network 12 MAP450D 1010 0046A REV 00 Shield Signal Ground From Host To Host Shield To OIT To OIT Signal Ground From Host To ...

Страница 13: ...tentials and currents Connecting the signal ground to chassis or earth ground can damage the devices connected to the com link 2 4 Set Jumper for 3 Wire RS 422 485 This step is required only if the OIT will be communicating with the host controller using RS 485 half duplex 3 wire communication STEPS 1 Remove the protective cover from the rear of the unit CAUTION When the rear cover is removed the ...

Страница 14: ...cutout required for proper panel installation The panel cutout should be cleaned and deburred before the OIT is installed 14 MAP450D 1010 0046A REV 00 The OIT is mounted using four 6 32UNC screws sandwiching the OIT halves to panel Screw length is equal to panel thickness plus 1 2 inch NOTE The mounting screws must not be torqued to more than 18 pound inches Over torquing can strip the threads in ...

Страница 15: ... to a mounting plate using the four pre tapped holes in the rear cover The OIT enclosure and cable strain relief provide the environmental seal to NEMA 4 and NEMA 12 standards Figure 11 shows the minimum dimensions of the pedestal pendant mounting plate The area on the pedestal pendant mounting plate around the mounting holes where the heads of the screws make contact should have any existing pain...

Страница 16: ...ar cover has two legs set at a five degree angle to give the display and keypad a sloped front while sitting on a bench Four rubber feet are attached to the legs to prevent slippage as well as damage to the surface of the bench 16 MAP450D 1010 0046A REV 00 0 156 dia nominal MOUNTING PLATE 5 400 0 015 5 00 nominal 4 600 0 015 6 00 nominal 4 holes clearance 1 8 thick min recommended for 6 screws PED...

Страница 17: ...re 4 1 Connecting the MAP450D to a PC First remove the operating cable from the terminal block pins Next connect an RS 232 serial communications cable Maple Systems P N 7431 0048 to the proper COM port on your computer and the terminal block pins on the MAP450D See Figure 13 below for pin assignments INSTALLATION MANUAL 17 1010 0046A REV 00 9S 10 COM RXD TXD 24V 3 9 2 1 TB1 OIT PC Shield 24V GND P...

Страница 18: ...vy industrial environment Power Requirements Input Voltage 12 to 30 VDC Power Usage 2 5 watts typical Display Display Type MAP450D 003 Liquid Crystal Display LCD 5 x 7 dot matrix with cursor Display Type MAP450D 004 Backlit Liquid Crystal Display LCD 5 x 7 dot matrix with cursor Display Character Size 2 lines by 40 characters 0 2 inches 5 mm high Display Viewing Angle Approximately 120 degrees Key...

Страница 19: ...00 127 0 90 23 depth behind the front of a panel 8 12 206 6 32UNC x 0 50 12 7 screw 4 places SS 6 32UNC x 0 30 7 6 deep threads for Pedestal Mounting only REAR VIEW FRONT VIEW SIDE VIEW Free Standing Pedestal Mount 7 10 180 SIDE VIEW Panel Mount 1 70 43 overall Waterproof strain relief for operating cable entry Panel ...

Страница 20: ...immunity and emissions 5 Local setup mode is entered by pressing and holding the Clear key instead of the S key while the Initializing prompt is on the display Local setup mode can also be entered after initialization by pressing the Enter key three times 6 The power supply input requirement is 12 to 30 VDC instead of 5or 8 to 13 VDC 7 The MAP450D offers 2 LCD viewing angles instead of 10 8 The MA...

Отзывы: