10.5 UHA[T][X][S] Series Internal Wiring Diagram for Two Stage Gas Valves

1

W2

HIGH/LOW CONTROL

HIGH

LOW

COMMON

NOTE:

For field wiring into service junction box, or if any of the original wire supplied with the heater 
must be replaced, it must be replaced with wiring material having a temperature rating of at least 221° F 
(105° C) and 600 volts. For supply connections use No. 14 AWG or larger wires.

Содержание UHAM150

Страница 1: ...tor qualified in the installation and service of gas fired heating equipment or your gas supplier Improper installation adjustment alteration service or maintenance can result in death injury or property damage Read the Installation Operation and Service Manual thoroughly before installing or servicing this equipment Installer Please take the time to read and understand these instructions prior to...

Страница 2: ......

Страница 3: ...s instructions peut entraîner la mort des blessures corporelles ou des dommages matériels ATTENTION L installation doit être effectuée par un installateur éprouvé contractant qualifié dans l installation et la maintenance du système de chauffage par infrarouge activé au gaz L installation l ajustement l altération le démarrage ou l entretien inadéquat peuvent causer la mort des blessures ou des dé...

Страница 4: ......

Страница 5: ...eries Internal Wiring Diagram for Single Stage Gas Valves 22 10 4 UHA X S Series Ladder Wiring Diagram for Single Stage Gas Valves 23 10 5 UHA T X S Series Internal Wiring Diagram for Two Stage Gas Valves 24 10 6 UHA T X S Series Ladder Wiring Diagram for Two Stage Gas Valves 25 10 7 UHA M X S Series Internal Wiring Diagram for Modulating Gas Valves 26 10 8 UHA M X S Series Ladder Diagram for Modu...

Страница 6: ...16 4 Dimension Data for Models UHA T M X S 300 400 57 16 5 General Technical Data Table 58 16 6 Technical Data Table 58 SECTION 17 The BANANZA UHA Series Warranty 59 ...

Страница 7: ...ntric Vertical and Horizontal Vent Termination Separated Combustion Heater 16 Figure 11 Gas Connection 19 Figure 12 Automatic Burner Control Sequence 30 Figure 13 Single Stage Gas Valve for Models UHA X S 150 400 31 Figure 14 Two Stage Gas Valve for Models UHA T X S 150 400 31 Figure 15 Modulating Gas Valve for Models UHA M X S 150 400 32 Figure 16 LED Diagnostic Codes 36 There are references in t...

Страница 8: ......

Страница 9: ...ter must be applied and operated under the general concepts of reasonable use and installed using the best building practices This equipment is not intended for use by persons including children with reduced physical sensory or mental capabilities or lack of experience and knowledge unless they have been given supervision or instruction concerning use of the equipment by a person responsible for t...

Страница 10: ...ly Description Part Number Logo Label 91031103 Cut Hazard Label 91010430 Vent Length Label 91039505 Vent to Outdoors Label 91010427 Warning Label 91010429 Rating Plate Label 91010417 Installation Label 91010431 Instruction Location Label 91010433 Lighting Instruction Label 91010425 Venting Arrangement Label 91010426 Proposition 65 Label 91070015 0 10VDC Modulating Label 91040196 ...

Страница 11: ...mber Logo Label 91031103 Cut Hazard Label 91010430 Vent Length Label 91039505 Vent to Outdoors Label 91010427 Warning Label 91010429 Rating Plate Label 91010417 Installation Label 91010431 Instruction Location Label 91010433 Lighting Instruction Label 91010425 Venting Arrangement Label 91010426 Proposition 65 Label 91070015 0 10VDC Modulating Label 91040196 ...

Страница 12: ...0034 is illustrated on the back cover Know your model number and installed configuration Model number and installed configuration are found on the heater serial plate and throughout the Installation Operation and Service Manual 2 2 Corrosive Chemicals CAUTION Product Damage Hazard Do not use equipment in area containing corrosive chemicals Refer to appropriate Material Safety Data Sheets MSDS Fail...

Страница 13: ...ndoors Must be installed in a level position with horizontal discharge May be mounted on a shelf of non combustible material May be suspended from above See Page 9 Figure or from wall brackets of sufficient strength to support the heater as listed in the Technical Data Table on Page 56 Section 16 2 and Page 58 Section 16 5 Drop rods must be a minimum of 3 8 diameter mild steel Four suspension poin...

Страница 14: ... is suitable for your application and the clearances are maintained Read and follow the safety guidelines below Keep gasoline or other combustible material including flammable objects liquids dust or vapors away from this heater or any other equipment Do not spray aerosols in the vicinity of this heater The stated clearances to combustibles represents a surface temperature of 90 F 50 C above room ...

Страница 15: ...ers may be mounted at a higher level if destratification fans are installed For Models UHA 150 400 venting directly from top of heater is not applicable For roof terminal vent elbow duct off back of heater is required Clearance to Vent 2 5 cm 31 79 cm minimum is necessary for servicing The heater must always be installed at least 6 1 8 m above the floor The vent pipe must have clearance from combu...

Страница 16: ...vision Canada Refer to Natural Gas and Propane Installation Code Standard CSA B149 1 latest revision 5 4 Electrical The heater must be electrically grounded in accordance with the following codes United States Refer to National Electrical Code NFPA 70 latest revision Wiring must conform to the most current National Electrical Code local ordinances and any special diagrams furnished Canada Refer to...

Страница 17: ...y lines must not be used to support the heater Do not locate the gas or electrical supply lines directly over the path of the flue products from the heater The heater must be installed in a location that is readily accessible for servicing The heater must be installed in accordance with clearances to combustibles as indicated on the wall tag and in this manual 6 2 Suspension WARNING Crush Hazard U...

Страница 18: ...ef equipment 7 1 2 Canadian Requirements The vent shall not terminate within 6 1 8 m of a mechanical air supply inlet to any building The vent shall not terminate within 3 9 m of a window or door that can be opened in any building any non mechanical air supply inlet to any building or of the combustion air inlet of any other piece of equipment 7 2 Vent Installation Maintain clearances to combustib...

Страница 19: ...2 5 cm clearance must be used Where local codes permit a single section of type B 1 vent material may be used at the roof or wall penetration instead of a thimble Ensure vent manufacturer s clearance from vent material is maintained Seal annular space of the type B 1 vent as well as all joints in the remaining vent 7 7 Replacing an Existing Heater in a Venting System When replacing an existing hea...

Страница 20: ... gas fired equipment or your local gas supplier If the venting must be resized use appropriate tables in US Appendix G of NFPA 54 ANSI Z223 1 latest revision National Fuel Gas Code US or Standard CSA B149 1 Natural Gas and Propane Installation Code Canada to determine minimum size All vent corrections must be in accordance with the appropriate local codes and the NFPA 54 ANSI Z223 1 latest revisio...

Страница 21: ...cal Option Horizontal Option Vent 90 Bend 12 31 cm Minimum from roof to vent termination Vent Termination Listed thimble through combustible wall Flashing By Others 12 31 cm Minimum from wall to vent termination Listed thimble through combustible roof NOTE Vent supports not shown Model Vent Diameter Part Number UHA T M X 150 400 4 10 cm 90502102 ...

Страница 22: ...m Single Wall Pipe D Area must equal sum of open area of individual vents D Single Wall Pipe The last section of vent pipe passing through the roof or wall may be Type B vent pipe All other vent materials in the building must be single wall vent pipe TOP VIEW SIDE VIEW Requirements Maximum of four heaters can be commonly vented through the roof Heaters must be of the same BTU output Heaters must b...

Страница 23: ...e 9 Concentric Vent Box 4 10 cm Single Wall Vent Pipe By Others Seal joint between single wall and Type B vent with silicone sealant Use 3 sheetmetal screws equally spaced around joint Use 3 sheetmetal screws equally spaced around collar Concentric Vent Box 6 15 cm or 8 20 cm Single Wall Inlet Air Pipe By Others One piece of 4 10 cm diameter 1 4 6 cm airspace type B vent Selkirk Model RV or equiva...

Страница 24: ...ith 3 sheet metal screws 12 31 cm Minimum from roof to combustion air terminal Flashing By Others 12 31 cm Minimum from wall to combustion air terminal Description Part Number Qty Concentric Vent Kit 150 250 UHVK1 Concentric Vent Box Top Side Assembly 90504113 1 Concentric Vent Box Bottom Assembly 90504112 1 Screw 6 x 3 8 Self Drilling 91119100 14 4 Vent Terminal with Baffle Plate 90502102R 1 6 Co...

Страница 25: ...bution fan 8 2 Building Ventilation Where ventilation is required air must be taken from an outside point where it is not likely to be contaminated or obstructed 8 3 Outside Combustion Air Supply If outside combustion air supply is required separated combustion model UHA T M X S heaters must be used Caution If the building has a slight negative pressure or corrosive contaminants such as halogenate...

Страница 26: ...plings for conducting propane and natural gas CAN CGA 8 1 latest revision 9 1 Connections Connect the heater to the gas supply ensuring that the final connections are as follows Gas supply pipe work is run in medium or heavy gauge tubing in compliance with local and national codes Meter and service must be large enough to handle all the burners being installed plus any other connected load The gas...

Страница 27: ... Heavy Gauge Pipe Gas Connector Option A Stainless Steel Flexible Gas Connector Do not twist flexible gas connector Ensure all joints are gas tight CAUTION Hold gas nipple securely with pipe wrench when attaching flexible gas connector Failure to follow these instructions can result in product damage Product Damage Hazard ...

Страница 28: ...unded in accordance with local codes In the absence of local codes in accordance with United States refer to National Electrical Code NFPA 70 latest revision Canada refer to Canadian Electrical Code CSA C22 1 Part I latest revision 10 1 Positioning Thermostats A room thermostat should be mounted on a vibration free wall or column at a height of approximately 5 1 5 m from the floor to measure the a...

Страница 29: ...SECTION 10 WIRING 21 of 59 10 2 Low Voltage Thermostat for Models UHA T M X S 150 400 NOTE Models 300 400 have two axial fans NOTE Electrical supply is located below terminal strip ...

Страница 30: ...iagram for Single Stage Gas Valves NOTE For field wiring into service junction box or if any of the original wire supplied with the heater must be replaced it must be replaced with wiring material having a temperature rating of at least 221 F 105 C and 600 volts For supply connections use No 14 AWG or larger wires ...

Страница 31: ...s Valves NOTE For field wiring into service junction box or if any of the original wire supplied with the heater must be replaced it must be replaced with wiring material having a temperature rating of at least 221 F 105 C and 600 volts For supply connections use No 14 AWG or larger wires ...

Страница 32: ...age Gas Valves 1 W2 HIGH LOW CONTROL HIGH LOW COMMON NOTE For field wiring into service junction box or if any of the original wire supplied with the heater must be replaced it must be replaced with wiring material having a temperature rating of at least 221 F 105 C and 600 volts For supply connections use No 14 AWG or larger wires ...

Страница 33: ...es HIGH STAGE NOTE For field wiring into service junction box or if any of the original wire supplied with the heater must be replaced it must be replaced with wiring material having a temperature rating of at least 221 F 105 C and 600 volts For supply connections use No 14 AWG or larger wires ...

Страница 34: ... Diagram for Modulating Gas Valves NOTE For field wiring into service junction box or if any of the original wire supplied with the heater must be replaced it must be replaced with wiring material having a temperature rating of at least 221 F 105 C and 600 volts For supply connections use No 14 AWG or larger wires ...

Страница 35: ...alves NOTE For field wiring into service junction box or if any of the original wire supplied with the heater must be replaced it must be replaced with wiring material having a temperature rating of at least 221 F 105 C and 600 volts For supply connections use No 14 AWG or larger wires ...

Страница 36: ...ALLATION OPERATION AND SERVICE MANUAL 28 of 59 10 9 Electrical Connection to the Heater Note Junction box is not provided with heater Conduit can also be attached directly to heater with wire junction made within the heater cabinet ...

Страница 37: ...n start automatically at any time Failure to follow these instructions can result in severe injury or product damage 11 1 Pre Start Up Checks All pre start up checks must be carried out before lighting the heater Ensure that the heater and all controls are suitable for the gas pressure and electrical supply to which they are to be connected 11 1 1 Louvers Where fitted the air delivery louvers need...

Страница 38: ...gure 12 There will be no ignition of the burner and lockout will occur which proves the controls are operating correctly Figure 12 Automatic Burner Control Sequence Burner Sequence for Ignition Control Flame Signal Start Gas Valve Ignition Spark Thermostat 24 V SHUT DOWN RUN START ts 10 Seconds Signals Output By Control Required Incoming Signals Flue Blower Pressure Switch P C NO NC 30 Seconds Pur...

Страница 39: ...s Valve 150 250 NG 90032505 Gas Valve 150 250 LP 90032506 Gas Valve 300 400 NG 90032520 Gas Valve 300 400 LP 90032521 Figure 14 Two Stage Gas Valve for Models UHA T X S 150 400 PSI IN C ON OFF LO HI Regulator Outlet Pressure Gas Inlet Inlet Pressure TOP VIEW END VIEW Description Part Number Gas Valve 150 250 NG 90032530 Gas Valve 150 250 LP 90032531 Gas Valve 300 400 NG 90032532 Gas Valve 300 400 ...

Страница 40: ...of 59 Figure 15 Modulating Gas Valve for Models UHA M X S 150 400 Description Part Number Gas Valve 150 250 NG 90032505 Gas Valve 150 250 LP 90032506 Gas Valve 300 400 NG 90032520 Gas Valve 300 400 LP 90032521 1 2 Exa Valve 150 250 90032550 3 4 Exa Valve 300 400 90032551 ...

Страница 41: ...ive To adjust high fire burner pressure remove regulator cover from Honeywell single stage gas valve and turn regulator adjustment screw to set required burner pressure as stated in the Technical Data Table for the correct gas and model on Page 56 Section 16 3 and Page 58 Section 16 6 3 To measure low fire burner pressure disconnect 10 VDC signal to modulating valve NOTE Low fire burner pressure i...

Страница 42: ...eater for service or during off season 11 5 External Controls External controls may include time switch interlock switch room thermostat and frost thermostat Operate each control to ensure that they function correctly Set the switches if fitted and thermostat s to the users requirements 11 6 Complete the Start Up Ensure that all covers are fitted correctly and all test points are properly sealed 1...

Страница 43: ... 2 1 To Turn On Heater 1 Ensure that the electrical and gas supplies to the heater are on Check that the on site controls are ON IMPORTANT The thermostat setting must be above the ambient temperature for the heater to operate 2 The automatic firing sequence will begin as described on Page 30 Figure 12 The heater will now operate automatically under the control of the on site controls 12 2 2 To Tur...

Страница 44: ... Normal Operation No call for heat Fast Flash Normal Operation Call for heat 2 Flashes Ignition Lockout No flame detected 3 Flashes Airflow Fault Pressure switch open or closed 4 Flashes Temperature Limit Switch Open 5 Flashes Flame Sense Error Gas valve not energized Steady On Internal Control Failure LED Diagnostic Codes ...

Страница 45: ... 29 Section 11 through Page 34 Section 11 7 to help ensure all safety systems are in working order before leaving the heater to operate Minor faults may be traced by using the troubleshooting charts on Page 41 Section 14 through Page 45 Section 14 5 IMPORTANT Check all gas pipes and pipe joints to ensure there are no cracks or gas leaks Any cracks in the pipes or pipe joints must be repaired IMPOR...

Страница 46: ...g and air intake components to ensure they are in good condition gas tight and corrosion free 13 8 Maintenance Checklist Installation Code and Annual Inspections All installations and service of BANANZA equipment must be performed by a contractor qualified in the installation and service equipment sold and supplied by Bananza and conform to all requirements set forth in the BANANZA manuals and all...

Страница 47: ...e sure it is clean and free of cracks or holes Clean and replace as required Flue Blower Scroll Wheel and Motor Compressed air or a vacuum cleaner may be used to clean dust and dirt Inshot Burners and Orifices Clear of obstructions even spider webs will cause problems Carefully remove any dust and debris from the burner Direct Spark Igniter Replace if there are cracked ceramics excessive carbon re...

Страница 48: ...STALLATION OPERATION AND SERVICE MANUAL 40 of 59 Wall Tag If a wall tag is present make sure it is legible and accurate Please contact Bananza or your BANANZA independent distributor if you need a wall tag See Page 4 Section 2 1 ...

Страница 49: ...re to follow these instructions can result in death electric shock injury or property damage Burn Hazard Allow heater to cool before service Tubing may still be hot after operation Explosion Hazard Turn off gas supply to heater before service DANGER Electrical Shock Hazard Disconnect electric before service Heater must be connected to a properly grounded electrical source ...

Страница 50: ...UHA STANDARD UNIT HEATER INSTALLATION OPERATION AND SERVICE MANUAL 42 of 59 14 1 General ...

Страница 51: ...43 of 59 14 2 Troubleshooting For Automatic Ignition Burner Systems For your safety and optimum heater performance use only replacement parts sold and supplied by Bananza Conduct start up procedure as shown on Page 29 Section 11 ...

Страница 52: ... bananza com Replace ignition control Use General Troubleshooting section to trace the fault Heater Operating TROUBLESHOOT ENDS No Repair or replace as necessary Is inlet burner gas pressure correct Is live and neutral polarity correct Is flame probe circuit correct Is there a current flowing in the flame probe circuit with no flame present Yes No Does lockout occur when there is a flame present Y...

Страница 53: ...urns on No Yes Is gas pressure at inlet of the valve correct for gas type Note pressure found No Yes START 14 5 Troubleshooting for Flue Blower For your safety and optimum heater performance use only genuine replacement parts sold and supplied by Bananza Conduct start up procedure as shown on Page 29 Section 11 If problems persist contact Bananza at www bananza com Fan Operating TROUBLESHOOT ENDS ...

Страница 54: ...to remove gas valve manifold Replace in reverse order Verify that the gas flow direction of the valve is correct Use a minimum amount of gas seal on the thread joint Check that all the joints are leak free Reset gas valve See Page 33 Section 11 2 2 IT IS IMPORTANT THAT ONLY THE CORRECT GAS VALVE IS USED WHEN REPLACING THESE CONTROLS Description Part Number Single Stage Gas Valve NG Models UHA X S ...

Страница 55: ...ng the filler panel on and remove the filler panel NOTE Models UHA 300 400 have two axial fans 15 2 1 Side View of Burner Compartment with Filler Panel Removed Burner assembly must be removed to service orifices manifold or burners Following any work refit components in reverse order NOTE Models UHA 300 400 have two axial fans Burner Compartment without Filler Panel for Models UHA T M X S 150 400 ...

Страница 56: ...M X S 150 400 MODEL UHA T M X S 150 UHA T M X S 175 UHA T M X S 200 UHA T M X S 225 UHA T M X S 250 UHA T M X S 300 UHA T M X S 350 UHA T M X S 400 Orifice Quantity 7 8 9 10 11 12 14 14 Natural Gas Orifice Marking 43 43 2 25 mm 2 25 mm 2 25 mm 43 43 40 P N 91930043 91930043 91930225 91930225 91930225 91930043 91930043 91930040 Propane Orifice Marking 1 35 mm 1 35 mm 54 54 54 1 45 mm 53 53 P N 9193...

Страница 57: ... Burners UHA T M X S 200 92000000 9 Inshot Burners UHA T M X S 225 92000000 10 Inshot Burners UHA T M X S 250 92000000 11 Inshot Burners UHA T M X S 300 92000000 12 Inshot Burners UHA T M X S 350 92000000 14 Inshot Burners UHA T M X S 400 92000000 14 Limit Switch 150 400 300 400 LOWER 90412103 1 Limit Switch 300 400 UPPER 90412105 1 To replace the ignition electrode or flame probe remove the elect...

Страница 58: ...ade of aluminized steel 409 stainless steel The tube supports are made of aluminized steel 409 stainless steel 15 5 Louvers and Louver Spring Description UHA T M X S 150 175 UHA T M X S 200 250 UHA T M X S 300 400 Horizontal Louvers P N 11011847 11011847 11011846 Spring P N 91901200 91901200 91901200 Quantity 7 9 11 The louvers for standard range models UHA T M X S 150 UHA T M X S 400 are only ava...

Страница 59: ... mounting plate to vent box Remove screws securing mounting plate to fan Not shown Refit in reverse Use new gaskets Ensure sealed joints Ensure mounting plate orifice is clear and not obstructed MODEL UHA T M X S 150 300 Flue Blower P N 90710403 IT IS IMPORTANT THAT ONLY THE CORRECT FLUE BLOWER SPECIFIED FOR EACH MODEL TYPE IS USED WHEN REPLACING THESE ITEMS Carry out a start up after working on o...

Страница 60: ...Vent Box Air Plate Remove screws securing outlet flange to the flue adapter Refit in reverse order Remove screws securing flue blower mounting plate to vent box Remove screws securing mounting plate to blower Refit in reverse Use new gaskets Ensure sealed joints Ensure mounting plate orifice is clear and not obstructed MODEL UHA T M X S 350 400 Flue Blower P N 90710402 IT IS IMPORTANT THAT ONLY TH...

Страница 61: ...HA T M X S 300 UHA T M X S 350 UHA T M X S 400 15 9 Ignition Control The control mounts to the electrical plate Pull out ignition cable and wiring from board noting their positions Release the four mounting standoffs Refit in reverse Ensure correct location of ignition cable and all other wiring 15 10 Axial Fan Guard Motor Assembly The axial fan unit for the heater is supplied completely assembled...

Страница 62: ...0416 2 15 10 2 To Replace the Fan Assembly To replace the fan assembly reverse the procedure shown above Check that the fan blades are free to rotate before turning on the power to the fan Strictly comply with the color code of the fan wires to ensure correct operation See Page 22 Section 10 3 Page 24 Section 10 5 or Page 26 Section 10 7 wiring diagram Use only genuine replacement parts sold and s...

Страница 63: ... 25 5 64 8 25 5 64 8 D in cm 17 6 44 7 17 6 44 7 17 6 44 7 17 6 44 7 17 6 44 7 E in cm 19 4 49 3 19 4 49 3 19 4 49 3 19 4 49 3 19 4 49 3 F in cm 30 0 76 2 30 0 76 2 32 0 81 3 32 0 81 3 32 0 81 3 G in cm 6 0 15 2 6 0 15 2 6 6 16 8 6 6 16 8 6 6 16 8 H in cm 8 7 22 1 8 7 22 1 8 6 22 8 6 22 8 6 22 J in cm 17 2 43 7 17 2 43 7 17 7 45 17 7 45 17 7 45 K in cm 3 1 7 9 3 1 7 9 8 1 20 6 8 1 20 6 8 1 20 6 L ...

Страница 64: ...gth of flue stated or heater may not operate properly 16 3 Technical Data Table Model UHA T M X S 150 UHA T M X S 175 UHA T M X S 200 UHA T M X S 225 UHA T M X S 250 Total Input High Fire Btu h x 1000 150 175 200 225 250 Total Input Low Fire Btu h x 1000 105 122 5 140 157 5 175 Total Output High Fire Btu h x 1000 123 143 5 164 184 5 205 Total Output Low Fire Btu h x 1000 86 100 115 129 143 5 Effic...

Страница 65: ...SECTION 16 SPECIFICATIONS 57 of 59 16 4 Dimension Data for Models UHA T M X S 300 400 ...

Страница 66: ...20 V A 11 6 11 6 11 6 Air Volume CFM 4663 4663 4663 Flue and Air Intake Flue Intake Size in cm 4 10 4 10 4 10 Air Intake Size in cm 5 13 5 13 5 13 Maximum Straight Flue Air Intake ft m 40 1 40 1 40 1 Weight Net lbs kg 355 161 0 375 170 1 375 170 1 Do not exceed the maximum length of flue stated or heater may not operate properly 16 6 Technical Data Table Model UHA T M X S 300 UHA T M X S 350 UHA T...

Страница 67: ...tenance history The data plate and or serial number are removed defaced modified or altered in any way The ownership of the BANANZA UHA Series is moved or transferred This warranty is nontransferable Bananza is not permitted to inspect the damaged controller and or component parts READ YOUR INSTALLATION OPERATION AND SERVICE MANUAL If you have questions about your controller contact your installin...

Страница 68: ......

Страница 69: ......

Страница 70: ......

Страница 71: ......

Страница 72: ......

Отзывы: