Safety Precautions

Fitting, wiring, initial start-up and maintenance operations must be done by trained technicians.  

All European and local rules for electrical instruments must be respected. 

The device may only be connected to intrinsically safe measuring circuits which comply with the specifications
included in the technical data and on the serial plate. 

The device must be disconnected from all sources of power during installation and maintenance work. 

The device may only be operated under the conditions specified in the operating instructions. 

Respect all recommendations, for installation and mounting of Ex devices, from standards EN60079-14 and
EN600079 CENELEC. 

The device should not be modified or completed with anything. 

All cables to connect the sensor must be out of any place where electrostatic risk exists. 

1      DESCRIPTION

Designed for the monitoring of hydrocarbon fluids separators, the alarm device 

NivOil

may

be connected to 1, 2, or 3 sensors. 

Hydrocarbon fluid layer thickness sensor

to detect when the maximum thickness is reached. 

Overfill sensor

to detect when the fluids are on the highest level; this can occur in case of

dysfunction of a filter, when a float-valve closes to prevent an overfilling, when the level of fluid
is too high. 

Sludge layer sensor

to alarm when maintenance is necessary. 

Detection of sludge maximal level, as soon as the sludge reaches the sensor, the alarm is
switched ON.

The 3 sensors may be connected to any input of the alarm device NivOil

Any combination of the sensors can be wired. The instrument recognizes automatically the sensor
type. A LED indicates the sensor type on the diagram on the front board. When an input is not
wired, the LED is off. The alarm unit NivOil has a built-in buzzer; it is possible to disable its function
by a DIP switch configuration.The alarm unit NivOil CU/12 works with a 10 to 27 V DC power
supply has a low energy consumption. It is de-signed for the use of a solar powered battery or
any standard electric battery 

(consumption is 0.1 W – 12 V DC – with 3 sensors connected with

one complete control cycle per hour)

.The sleep mode allows optimal energy consumption. It is

adjustable by modifying the frequency of control cycle 

(from 6 minutes up to 9 days)

. A continuous

control mode could be switched on when there is no limit on consumption. All the components
are ATEX certified. The sensors are for a location in zone 0 and the alarm unit corresponds to a
zone 2. 

Important: It is necessary to follow the specific technical information corresponding to the mounting,
fitting and starting up of the devices. 

Содержание NivOil

Страница 1: ...531 M1 02 A 16 07 2010 1 NivOil 12 V DC Alarm system for oil water separators Instructions manual ...

Страница 2: ...oat valve closes to prevent an overfilling when the level of fluid is too high Sludge layer sensor to alarm when maintenance is necessary Detection of sludge maximal level as soon as the sludge reaches the sensor the alarm is switched ON The 3 sensors may be connected to any input of the alarm device NivOil Any combination of the sensors can be wired The instrument recognizes automatically the sen...

Страница 3: ...r Fit the sensor such as the sensor tip corresponds to the bottom of the greater layer thickness to detect The graduated stem 5 10 and 15 cm marks makes the adjustment easier Overfilling sensor Fit the sensor such as the ends of U probe are 2 cm under the alarming level Sludge layer sensor Fit the sensor such as the ends of U probe are 2 cm under the alarming level 3 CONFIGURATION AND ELECTRICAL C...

Страница 4: ...DIP 6 Monitoring frequency each 6 to 54 min DIP 7 Monitoring frequency each 3 to 37 h DIP 8 Monitoring frequency each 1 to 9 days DIP switch setting 0 1 2 3 4 5 6 7 8 9 DIP 6 ON Continuous monitoring 6 min 12 min 18 min 24 min 30 min 36 min 42 min 48 min 54 min DIP 7 ON Continuous monitoring 3 h 6 h 9 h 12 h 15 h 18 h 21 h 24 h 27 h DIP 8 ON Continuous monitoring 1 day 2 days 3 days 4 days 5 days ...

Страница 5: ... monitoring cyclic monitoring The energy consumption is adjustable by modifying the duration of each monitoring cycle through the settings of the DIP switch and the selector The monitoring frequency is adjustable from 6 minutes to 9 days Between 2 monitoring the alarm unit is in sleep mode monitoring function in stand by When there is not a specific sleep mode period selector on 0 and DIP 6 7 and ...

Страница 6: ...ice NivOil memorizes the type of sensor connected to each chan nel l When the TEST mode is activated an audible signal occurs if everything is correct The factory settings are without sensors l When you connect a new sensor on a free channel the alarm device NivOil will identify and memorize it as soon as you switch on the power If a sensor is removed the corresponding 3 LED will be flashing defec...

Страница 7: ...531 M1 02 A 16 07 2010 7 5 ALARM SYNOPTIC DIAGRAMS Note To avoid false alarms a 10 seconds delay is factory set up For hydrocarbon fluid layer thickness and overfilling sensors DIP3 OFF ...

Страница 8: ...d When probe ends are inside 1 cm or 2 cm inside sludges sand soils etc The alarm synoptic diagrams for the sludge probe are identical to the diagrams for hydro carbon fluid layer thickness and overfilling sensors For sludge probe DIP3 OFF Repeat alarm function The alarm repeat function is disabled or activated with the DIP switch 2 When DIP 2 is in position ON the alarm will repeat again 24 hours...

Страница 9: ...corresponding channel e Blinking not corrected Without defect No reset alarm Red LED on corresponding channel e Blinking buzzer Green LED on corresponding function e Light on Without defect Reset alarm but Red LED on corresponding channel e Light on not corrected Green LED on corresponding function e Light on Sensor status Alarm status Signals Without defect No alarm Green LED on corresponding fun...

Страница 10: ...tive test Corresponding LED are ON Negative test Corresponding green LED are blinking 9 MAINTENANCE The alarm device and its sensors do not require any maintenance operation in normal operation After an alarm occurred the sensors must be cleaned as the separator is drained To clean out a sensor use a wetted rag with a house cleaning and degreasing liquid 10 PRECAUTION Hydrocarbon fluid layer thick...

Страница 11: ...en on each channel 1 alarm signal LED red on each channel Built in audible alarm disabled by DIP switch configuration Front panel 2 push buttons for diagnostic test and alarm clearance Outputs 3 relay outputs 250 V AC 0 45 A 10 W potential free change over contacts Ex protection class I 3 1 G Ex nAC ia Ga IIB IIA T4 Gc ATEX certificate BVS 10 ATEX E 011 CE Marks According to EC directives Low Volt...

Страница 12: ... 60529 Temperature limits 20 60 C Ex protection class II 1 G Ex ia IIB T4 Intrinsic safety ATEX certificate BVS 09 ATEX E 021X Sensor type Ultrasonic detection type Wetted parts PVC Cable Elastomer resistant to oils and hydrocarbon fluids blue colour wires 2x1mm2 connections to the alarm device NivOil on screw connectors 10 m long cable max length is 300 m Protection IP68 acc EN 60529 Temperature ...

Отзывы: