HYSTERESIS
Setting from 1 to 99 %
The output relay only switches back when the measured value has fallen below the selected percentage.
The hysteresis cannot be set greater than or equal to the currently set threshold value.
Default setting: 1%
NC or NO SELECTION
NO (normally open): The contact is open as long as the measured value is lower than the set threshold value
NC (normally closed): The contact is closed as long as the measured value is lower than the set threshold value
Default setting: NO
Note: in the event of a power failure or device defect, all relay contacts are open
ASSIGNING OUTPUT RELAY TO INPUT E1 OR E2
The measured value of input E1 or E2 can be assigned to each individual output relay A1 to A4.
Factory setting: all relays are assigned to input 1 (E1)
OVER-RANGING DISPLAY
Measuring signal > mA max. value -> digital display = ↑
Measuring signal < mA min. value -> digital display = ↓
CLOCK-TIMER
Alternatively, relay 4 can also be used as a timer. The timer discount is switched on as soon as the ON and OFF times are set greater than 0.
--> This means that the settings for limit value relay 4 become ineffective.
ON-TIME
As long as the set ON-time is running, the contact of output relay 4 is closed
Setting range: 1 second to 24 hours
Available setting values:
0*, 1, 2, 5, 10, 30 secondes
→ no additional dot lights up
1, 2, 5, 10, 30 minutes
→ 1 additional dot light is blinking
1, 2, 3, 6, 12, 24 hours
→ 2 additional dot lights are blinking
Default setting: 0
= 10 s
= 10 min
= 12 h
OFF - time setting
As long as the set OFF time is running, the contact of output relay 4 is open
Settings as above
Default setting: 0
Note: After a power failure the device reboots, the program starts with the ON-Time
If one of the times is changed during operation, the new time takes effect immediately.
RE
10-02-2022
M-232.04-EN-AB
232-04
/5
4 limit value relays
EVEREST 214-S