SETTINGS
MAIN DISPLAY: Viewing and setting Setpoint, Offset and Tempo
Access to parameter entry:
Setpoint, Offset and Tempo
Access to other parameters
(Frequency, Thresholds, Language,
Device version, etc.)
Status of the relays (open or closed)
One click displays the name and function of the relay
(Alarm Tempo/ Cycles or Totalizer)
See chapter THRESHOLDS
The main display shows:
- The setpoint
- The volume*
- Downcount of TEMPO**
- The status of each relay S1, S2 & S3
- The Totalization
- The number of cycles
* Volume counted during a dsing cycle (Reset at each start).
** Countdown stops once the setpoint is reached (otherwise it alarms the operator).
From the main display, the following parameters can be entered:
SETPOINT
Press the "Value" key to enter the setpoint (Volume to reach)
OFFSET
Press the ''OFSET'' key to enter the real volume passed at the time the circuit was closed.
Example: Setpoint at 1 litre.
The closing time of the solenoid valve generated 1.010 litre instead of the requested 1 litre.
To compensate for this discrepancy between set point and volume reached at the end of the cycle, the 10 ml discrepancy can be entered in
the BAMOWIZ in order to order the circuit to close at 990 ml.
There will then really be 1 litre delivered.
RE
30-03-2022
M-217.05-EN-AD
217-05
/8
Counter, Totalizer, Dosing
controller
BAMOWIZ DOZ