AUXILIARY PUMP
In some cases (excessive distance or difference in level) it is
necessary to install a “loop-type” supply system with an auxiliary
pump, which dispenses with the connection of the burner pump
directly to the tank.
In this case the auxiliary pump can be put into operation when the
burner is started up and cut-off when the latter stops.
The electric wiring of the auxiliary pump is made by connecting
the coil (230 V) which controls the pump remote control switch to
terminals “N” (equipment terminal board) and “L1” (downstream
the motor remote control switch).
It is important to comply strictly with the previsions set forth here
below:
- The auxiliary pump should be installed as near as possible to
the fuel to be sucked.
- Its head should meet the requirements of subject system.
- We recommend a delivery rate equal to at least that of the
burner pump.
- Connection pipes should be sized to cope with the delivery
rate of the auxiliary pump.
- Always avoid to electrically connect the auxiliary pump directly
to the remote control switch of the burner motor.
HYDRAULIC DIAGRAM
LEGEND
1 - Foot valve
2 - Eventual air regulation motor
3 - 2
nd
flame nozzle
4 - 1
st
flame nozzle
5 - Safety valve normally closed
6 - 12 bar pump
7 - Valve normally closed
8 - Air gate control hydraulic jack
Note Pressure loss:
TBL 85P - 85P DACA
= 1 bar
TBL 105P - 105P DACA
= 1,5 bar
TBL 130P - 130P DACA
= 1,5 bar
TBL 160P - 160P DACA
= 2 bar
TBL 210P
= 2,5 bar
N° 0002901470
REV.: 14/11/06
Содержание TBL 105P
Страница 2: ......
Страница 24: ...47 96 0006081053_200801 E N G L I S H CAMS REGULATION SERVOMOTOR SQN 72 2B4A20...
Страница 26: ...93 96 0006081053_200801...
Страница 27: ...94 96 0006081053_200801...
Страница 28: ...95 96 0006081053_200801...
Страница 29: ...96 96 0006081053_200801...
Страница 30: ......