![baltur TBG 85P Скачать руководство пользователя страница 46](http://html.mh-extra.com/html/baltur/tbg-85p/tbg-85p_instruction-manual-for-installation-use-and-maintenance_470437046.webp)
ENGLISH
14 / 30
0006081041_201809
•
To reclose the electrical panel lid, fix the screws (1) with a torque
of about 5 Nm to ensure the correct seal.
To gain access to the control panel (8), slide the transparent door
(7) for a short distance following the direction on the arrow indicated
in the figure exerting slight pressure with a tool (e.g. a screwdriver)
following the arrows' direction and slide it for a short distance to
separate it from the cover.
• To secure the transparent door on the panel properly, position the
hooks at their hooking points (9), slide the door in the direction
indicated by the arrow until you hear a click that ensures its seal.
CAUTION / WARNINGS
Only professionally qualified personnel may open the burner
electrical switchboard.
•
In case of phase-phase 230V electrical grids, if these latter are
unbalanced, the voltage between flame detection electrode and
ground can not be enough to ensure burner correct operation.
The problem is solved by using a type AR1 insulating transformer
cod.0005020028 connected as shown in the following diagram.
Ph
Ph 230
ION IN
ION PROBE
AR 1
ION
L (1)
IN (2)
tensione_elettrodi
1
1
0002934780a
8
7
0002934780d1
9
9
9
9