background image

29 / 75

0006081327_200807

E

N
G

L

I

S

H

METHANE GAS IGNITION AND ADJUSTMENT

1)  Check that the combustion head  penetrates into the combustion 

chamber  to  theextend  required  by  the  boiler  manufacturer  . 
Check that the device that closes the air at the combustion head 
is presumable in the position suited for the required supply of 
fuel (the passage of air between the disk and combustion head 
must be significantly reduced , if in the opposite case the fuel 
supply is rather high, the passage between disk and combustion 
head  must  be  relatively  open).  See  chapter  “Adjustment  of 

combustion head”.

2)  If it has not already been down when connecting the burner to the 

gas piping, it is essentially to vent the air in the pipes, which should 
done with doors and windows open. The connector on the piping 

close to the burner must be opened and then the tap or taps that  

shut off the gas must be opened a bit. Wait until you can smell the 
gas and then close the tap. Wait a sufficient length of time, which 
will depending on the specific conditions, until the gas in the room 

disperses outside and then connect up the burner again to the gas 
piping.

3)  Check  that  there  is  water  in  the  boiler  and  that  the  system’s 

gate valves are open.

4)  Check  very  thoroughly  that  the  combustion  products  exhaust 

path is free (boiler gates and flue open).

5)  Check  that  current  to  be  connected  corresponds  with  that 

required  by  the  burner  and  that  the  electrical  connections 
(motor  and  main  line)  are  set  for  the  available  power  supply. 
Check  that  all  the  electrical  connections  carried  out  on  site 
have been correctly performed as in our wiring diagram.

6)  Apply a pressure gauge with suitable scale to the gas pressure 

outlet to check the set value (if the pressure provided for permits 
it is preferable to use a water column instrument and not use 
those with pointers for modest pressures).

7)  Put  the  air  adjustment  electric  servo  motor  cams  (see 

instructions page.....) to the positions you presume are suitable 

in proportion to the minimum and maximum modulation thermal 

flow and to the ignition heat input.

8)  Set  the  desired  value  for  the  ratio  between  the  gas  and 

air  pressures,  following  the  pneumatic  valves  adjustment 
instructions  given  in  the  manual  provided  with  the  gas  train 

installed

9)  With the burner panel switch at the “O” position and the main 

switch  on,  check,  by  manually  closing  the  contactor,  that  the 
motor turns in the correct direction, if necessary, swap around 
the  two  power  cables  for  the  three-phase  motor  to  invert  the 

direction of rotation.

10) Now switch on the control panel switch and turn the modulation 

switches  to  MIN  (minimum)  and  MAN  (manual).  The  control 
box is now powered up and the programmer sets the burner as 
described in the chapter “description of working”.

Note:  Preventilation  is  carried  out  with  air  open  and  so  the 
adjustment  servo  motor  is  switched  on  performs  its  complete 
opening run up to the set “maximum”. Only when the adjustment 
servo motor has returned to the “switch on” position will the control 
box  carry  out  its  ignition  program,  switching  on  the  transformer 

and gas valves for ignition. Check during preventilation that the 
pressure switch that controls air pressure in fact exchanges (from 
the closed position where no pressure is detected it must pass to 
the closed position with air pressure detection). If the air pressure 
switch does not detect sufficient pressure (does not carry out the 
exchange),  the  ignition  transformer  does  not  switch  on  and  the 
valves  for  the  ignition  flame  also  do  not  switch,  with  the  result 
that  the  control  box  goes  to  “lock-out”.  It  should  be  pointed  out 
that some “locking out” during this phase of first switch on can be 
regarded as normal because the ramp valves piping will still have 
some air in them and this must be eliminated before a stable flame 
can be achieved. To “release” the lock press the “release” button.

On first switching on, repeated “lock outs” may occur due to:

a)  The gas piping not being freed of the air sufficiently and so the 

gas quantity is not enough to provide a stable flame.

b)  The “lock-out” with flame on may be caused by flame instability 

in    ionisation  area,  due  to  incorrect  air-gas  mix. This  can  be 

remedied  by  varying  the  quantity  of  air  and/or  gas  until  the 
right  ratio  is  found.    The  same  problem  may  be  caused  by 

incorrect air/gas distribution in the combustion head. This can 

be remedied with the combustion head adjustment device by 
closing or opening further the air passage between combustion 

head and gas diffuser.

11) Set the burner at minimum thermal capacity of modulation 
(air damper control servo motor at minimum), check the size and 
appearance of the flame, making any necessary  corrections. 
To do this, follow the e instructions for the pneumatic valves. 
Then carry out a meter reading check on the quantity of gas 
supplied.  If  necessary  adjust  gas  and  combustion  air  supply 
as  described  previously  (points  7  and  8).  Subsequently  the 
combustion  is  checked  with  the  special  instruments.  For  the 

correct air-gas mix, the carbon dioxide level must be measured. 
(C02) for the methane is at least 8% or O2=6% on minimum 

burner supply up to a ideal value of 10% or 02= 3% for maximum 
supply. It is essential to check, with a suitable instrument, that 

the percentage of carbon monoxide (CO) present in the fumes 

does  not  exceed    the  limit  set  by  regulations  at  the  time  of  

installation.”

12) After adjusting the burner to minimum thermal capacity, turn the 

modulation switches to MAN (manual) and MAX (maximum). 

The servo motor that regulates the air is put at “maximum” and 

so also the gas supply reaches maximum thermal capacity. A 
check must then be carried out on the quantity of gas supplied 
(by  reading  the  meter).  With  burner  on  at  maximum  existing 
supply,  the  gas  flow  is  measured  as  the  difference  between 
the two readings at exactly one minute between one and the 
other.  Multiplying  the  value  obtained  by  sixty  you  obtain  the 
flow in sixty minutes, i.e. per hour. Multiplying the supply per 
hour (m3/h) for the gas calorific power you obtain the power 
supply in kcal/h which must correspond to or be very near to 
that required by the boiler (lowest calorific power for methane 
= 8550 kcal/h). You must prevent the burner from continuing 
to  run  if  the  flow  is  greater  than  the  maximum  permitted  for 

the  boiler,  to  avoid  possible  damage  to  the  boiler  itself,  and 

so the burner should be stopped straight after the two meter 

readings.

Содержание TBG 50LX PN

Страница 1: ...Instruction for burners model Instrucci nes para quemadores modelos Mode d emploi brule r TBG50LXPN TBG80LXPN TBG110LXPN TBG140LXPN TBG200LXPN 0006081327_200807 IT GB SP FR TBG50LXPN V TBG80LXPN V TBG...

Страница 2: ......

Страница 3: ...rialirispet tano i requisiti minimi imposti dalle Direttive Europee 90 396 CEE Direttiva Gas 92 42 CEE Direttiva Rendimenti 89 336 CEE Direttiva Compatibilit e m 73 23 CEE Direttiva Bassa Tensione 98...

Страница 4: ...ario o se si dovesse traslocare e lasciare l apparecchio assicurarsi sempre che il libretto accompagni l apparecchio in modo che possa essere consultato dal nuovo proprietario e o dall installatore Pe...

Страница 5: ...trebbero compromettere il buon funzionamento del bruciatore Per la prima messa in funzione dell apparecchio far effettuare da personale professionalmente qualificato le seguenti verifiche a il control...

Страница 6: ...ce accordingly Gas Appliances Directive 0 396 EEC made by CE0085 DVGW The Vice President and Managing Director Dr Riccardo Fava GB Before using the burner for the first time please carefully read the...

Страница 7: ...If the equipment is sold or transferred to another owner or if the owner moves and leaves the equipment make sure that the booklet always goes with the equipment so it can be consulted by the new owne...

Страница 8: ...d out by qualified technicians and in compliance with current law and regulations since incorrect installation may cause damage to person animals or things for which damage the manufacturer shall not...

Страница 9: ...IP 44 FLAME DETECTOR SONDA DI IONIZZAZIONE NOISE dBA 72 73 75 5 79 85 WEIGHT kg 76 78 87 91 94 Natural Gas G 20 FLOW RATE MAX m n h 55 3 80 5 120 7 145 8 191 1 MIN m n h 11 13 1 18 1 20 1 47 8 PRESSU...

Страница 10: ...0 540 380 160 1280 200 450 240 219 320 280 370 M12 250 260 12 112 5 54 TBG 200LX PN 645 275 370 540 380 160 1280 200 450 250 219 320 280 370 M12 255 260 12 112 5 54 1 Combustion head 2 Gasket 3 Burner...

Страница 11: ...h 5 Safety valve 6 Pressure regulator 7 Valves seal control device obligatory for burner with maximum nominal thermal output Gas train supplied by the manufacturer The job of the installer The gas sup...

Страница 12: ...boiler s shutter Tube fixing screw Combustion chamber pressure detection stiff tube Combustion chamber pressure detection point Cut in line with diffuser Combustion chamber pressure transmission tube...

Страница 13: ...rn the cam 6 so that the float exerts sufficient pressure on the two cables then tighten the screws that fasten the cable float Finally connect the two 7 and 4 pole plugs IMPORTANT the housings for th...

Страница 14: ...set maximum If there is no flame the control box stops in its safety lock out LED 7 within 3 seconds from the opening of the main valve In the case of safety lock out the valves immediately close agai...

Страница 15: ...xtraneous light when burner startup 5 blinks l l l l l On Time out LP LP is welded in working position 6 blinks l l l l l l On Free 7 blinks l l l l l l l On Too many losses of flame during operation...

Страница 16: ...for ignition Check during preventilation that the pressure switch that controls air pressure in fact exchanges from the closed position where no pressure is detected it must pass to the closed positi...

Страница 17: ...heck the triggering that leads to immediate lock out of the burner To release the locked burner press the release button and reset the pressure switch to a value sufficient to detect the existing air...

Страница 18: ...NISATION PROBE ADJUSTMENT DIAGRAM Legend 1 Ionisation electrode 2 Ignition electrode 3 Deflector disk 4 Mixer 5 Gas outlet pipe Mod A B C TBG 50LX PN 5 3 3 TBG 80LX PN 5 8 TBG 110LX PN 5 5 TBG 140LX P...

Страница 19: ...ulates the aspiration flow from the burner fan This must of course be the case when the burner is working at maximum desired supply In practice you have to start the adjustment with the device that cl...

Страница 20: ...sure successful disassembly of the mixing unit With the same wrench turn the ball joint 6 in the direction indica ted with the arrow unhooking the lever that moves the combustion head forward figure 2...

Страница 21: ...34 75 0006081327_200807 E N G L I S H CAMS REGULATION SERVOMOTOR SQN 72 6A4A20 N 0002933651 rev 14 02 2007...

Страница 22: ...or and then check its efficiency by inserting the analog micro ammeter 4 Check visually and using the instru ment 5 Restore the connection 6 Ensure that the boiler fumes passage and chimney connection...

Страница 23: ...72 75 0006081327_200807...

Страница 24: ...73 75 0006081327_200807...

Страница 25: ...74 75 0006081327_200807...

Страница 26: ...AX P1 CONTAORE HOUR METER COMPTEUR HORAIRE CONTADOR DE HORAS PA PRESSOSTATO ARIA AIR PRESSURE SWITCH PRESSOSTAT AIR PRESOSTATO AIRE Pm PRESSOSTATO DI MINIMA GAS MIN PRESSURE SWITCH PRESSOSTAT MIN PRES...

Страница 27: ...La Casa por lo tanto se reserva cualquier posibilitad de modificati n de datos t cnicos y otras anotaciones Ce manuel rev t caract re purement indicatif La maison se reserve la possibilit de modifier...

Отзывы: