![background image](http://html1.mh-extra.com/html/baltur/tbg-450lx-mc/tbg-450lx-mc_instruction-manual-for-installation-use-and-maintenance_3793385066.webp)
•
Install a suitable disconnecting switch for each power supply line of
the burner, following the indications in the diagram on the side and
in the table 1.
Sezionatore
fig1
PROTECTION WITH DISCONNECTING SWITCH, CIRCUIT BREAKER AND DIFFERENTIAL SWITCH
TABLE 1
Connection 3~400V and 1+N ~230V 50 Hz
TBG 450 ME
TBG 510 ME
TBG 650 ME
TBG 750 ME
1~230V 50
Hz
3~400V 50
Hz
1~230V 50
Hz
3~400V 50
Hz
1~230V 50
Hz
3~400V 50
Hz
1~230V 50
Hz
3~400V 50
Hz
Motor connection
-
Y
-
Y
-
Y/Δ
-
Y/Δ
Motor nom curr
A
-
16,5
-
19,9
-
26,8
-
33
Motor thermal protection calibration
(F1)
A
-
18
-
22
-
17
-
21
Connection line minimum section (S1,
S2) 4)
sq.mm
1,5
4
1,5
6
1,5
10
1,5
10
Pole number
1+N
3
1+N
3
1+N
3
1+N
3
Intervention characteristics
C
C
C
C
C
C
C
C
Nominal current (In) 5)
A
6
20
6
25
6
32
6
40
Ultimate rated short-circuit breaking
capacity (Icu) 6)
kA
10
10
10
10
10
10
10
10
Nominal residual current (IΔ)
mA
30
300
30
300
30
300
30
300
Type of residual current
AC
AC
AC
AC
AC
AC
AC
AC
Intervention time 7)
sec
< 0,2
< 0,07
< 0,07
< 0,07
< 0,2
< 0,07
< 0,2
< 1
4)
Sections S1 and S2 are calculated for PVC insulated copper conductors, class 5 or higher, at an ambient temperature of 40° C, considering single cables
placed side by side and not wound. Provide for any downgrades in case of different conditions.
The sections of connection cables must be chosen based on the distance from the connection point so that the voltage drop at the burner panel terminals
does not exceed 4% with respect to the nominal value.
5)
The protection devices against overcurrents have been calculated at an ambient temperature of 30° C. Provide for any downgrades in case of different
conditions.
6)
The maximum short-circuit current at the connection point must not exceed the value indicated in the table.
7)
The intervention time refers to the residual current equal to the nominal value IΔ. L'RCD is of instantaneous type (not selective).
Provide for 2 protection devices (one for each line) having the following features:
- DISCONNECTING SWITCH
8
- PROTECTION AGAINST OVERCURRENTS
- DIFFERENTIAL PROTECTION AGAINST INDIRECT CONTACTS (RCD)
The reference values for these devices are shown in the table.
8)
The disconnecting switch must be padlockable in the OFF position.
The burner can be installed only in TN or TT systems. It cannot be installed in IT systems.
The functionality of RCD must be periodically checked following the procedure and the intervals indicated by the manufacturer of the device.
ENGLISH
18 / 46
0006160271_202007
Содержание TBG 450LX MC
Страница 2: ......
Страница 38: ...SCHEMI ELETTRICI ITALIANO 36 46 0006160271_202007...
Страница 39: ...ITALIANO 37 46 0006160271_202007...
Страница 40: ...ITALIANO 38 46 0006160271_202007...
Страница 41: ...ITALIANO 39 46 0006160271_202007...
Страница 42: ...ITALIANO 40 46 0006160271_202007...
Страница 43: ...ITALIANO 41 46 0006160271_202007...
Страница 44: ...ITALIANO 42 46 0006160271_202007...
Страница 45: ...ITALIANO 43 46 0006160271_202007...
Страница 46: ...ITALIANO 44 46 0006160271_202007...
Страница 47: ...ITALIANO 45 46 0006160271_202007...
Страница 84: ...WIRING DIAGRAMS ENGLISH 36 46 0006160271_202007...
Страница 85: ...ENGLISH 37 46 0006160271_202007...
Страница 86: ...ENGLISH 38 46 0006160271_202007...
Страница 87: ...ENGLISH 39 46 0006160271_202007...
Страница 88: ...ENGLISH 40 46 0006160271_202007...
Страница 89: ...ENGLISH 41 46 0006160271_202007...
Страница 90: ...ENGLISH 42 46 0006160271_202007...
Страница 91: ...ENGLISH 43 46 0006160271_202007...
Страница 92: ...ENGLISH 44 46 0006160271_202007...
Страница 93: ...ENGLISH 45 46 0006160271_202007...
Страница 95: ......