Notes on programmer - Programmer sequence
Output signals on terminal board
Time key
Sec.
31,5 t1
Pre-ventilation time with air shutter open
3
t2
Safety time
-
t2'
Safety time or first safety time with burners that use pilot burners
6
t3
Short pre-ignition time (ignition transformer on terminal 16)
-
t3'
Long pre-ignition time (ignition transformer on terminal 15)
12
t4
Time between beginning of t2’ and valve consensus on terminal 19 with t2
-
t4'
Time between beginning of t2’ and valve consensus on terminal 19
12
t5
Time between end of t4 and consensus at power regulator or valve on terminal 20
18
t6
Post-ventilation time (with M2)
3
t7
Time between consent for start-up and voltage at terminal 7 (start delay for fan motor M2)
72
t8
Start-up duration (without t11 and t12)
3
t9
Second safety time for burners that use pilot burners
12
t10
Time from start-up to beginning of air pressure control without effective air shutter stroke time
-
t11
Air shutter opening stroke time
-
t12
Air shutter in low flame position (MIN) stroke time
18
t13
Admissible post-combustion time
6
t16
Initial delay of consent for air shutter OPENING
27
t20
Time to automatic closure of programmer mechanism after burner start-up
NOTE:
With voltage at 60 Hz the times are reduced by nearly 20%.
Содержание GI 500 MC
Страница 2: ......
Страница 34: ...ITALIANO 32 36 0006160064_201510 SCHEMI ELETTRICI ...
Страница 35: ...ITALIANO 33 36 0006160064_201510 ...
Страница 36: ...ITALIANO 34 36 0006160064_201510 ...
Страница 38: ...ITALIANO 36 36 0006160064_201510 ...
Страница 70: ...ENGLISH 32 36 0006160064_201510 WIRING DIAGRAMS ...
Страница 71: ...ENGLISH 33 36 0006160064_201510 ...
Страница 72: ...ENGLISH 34 36 0006160064_201510 ...
Страница 74: ...ENGLISH 36 36 0006160064_201510 ...
Страница 75: ......