background image

9

MEDIUM PRESSURE GAS SUPPLY SYSTEM 

(see BT 8058 - BT 8530/1 - BT 8531/1)

When a high delivery is required, the Gas Supply Company requires a unit with a pressure reducer and meter to
be installed, and provides a connection to the medium pressure gas supply (several bars).
This unit can either be supplied by the Gas Supply Company or the User according to Gas Supply Company
specifications.
The pressure reducer in this unit must be sized in order to be able to supply the maximum gas delivery required
by the burner, at the normal gas pressure.
Experience shows that it is best to use reducers of a good size to contain the considerable increase in pressure
when the burner stops at a high feed rate (the Standards require the gas valves to close within one second).
We recommend using a reducer that can provide almost double the maximum feed (m 3/h) required for the
burner.
Where a number of burners are used, each one must be fitted with its own pressure reducer. This will allow the
gas feed pressure to be maintained at a constant level, independently of whether one or more burners are working
at the same time, thus enabling accurate regulation of the gas feed, and therefore combustion, resulting in better
performance.
Gas piping must be adequately sized according to the quantity of gas to be supplied, therefore it is advisable to
keep the load loss within modest values (not more than 10% of the gas pressure at the burner). Remember that
the load loss is added to the existing pressure when the burner stops, hence the greater the load loss in the piping
the higher the pressure at the next ignition.
If the gas pressure reaches unacceptable levels when the burner stops (rapid closing of the gas valves), an
automatic relief valve must be installed between the reducer and the first burner valve, and also the relative
adequate pipe for discharge into the open air.
The pipe must end in a suitable place, protected from rain, and be fitted with a flame trap.
The pressure relief valve must be adjusted in order to completely discharge all excess pressure. For gas pipe
sizes, see drawing no. BT 8058.
A ball cock, gas filter, anti-vibration union, and flanged fitting must also be installed near the burner (see BT 8530/
1 and BT 8531/1).

Содержание COMIST 180 NM

Страница 1: ...Edition 2003 11 Cod 0006080810 Instruction for burners model COMIST 180 NM COMIST 250 NM COMIST 300 NM en ...

Страница 2: ......

Страница 3: ...CEI and UNI standards BALTUR guarantees the CE certification provided that the burner is coupled to the CE gas train supplied by BALTUR and the CE gas line accessories on request NOTE this declaration is not valid with regard to EC or UNI Standards for gas burners or the gas part of duel fuel burners gas light oil or gas heavy oil when such burners have been ordered in non compliance with the EC S...

Страница 4: ...e 17 Ignition and regulation with fuel oil 18 Air regulation at the combustion head 19 Adjusting the gap between the disc and nozzle UV photocell Variation for burners fitted with a fuel oil vapour pre heater 20 Ignition and regulation with methane 22 Air regulation at the combustion head 24 Reading the gas meter 24 Using the burner Maintenance 25 General diagram air regulation 26 Air control and ...

Страница 5: ...S DE ENCENDIDO GASÓLEO SERBATOIO PRE HEATER RESISTENCIAS kW 15 18 25 5 TENSIONE VOLTAGE TENSIÓN Volt 3N 400V MOTORE VENTOLA FAN MOTOR MOTORES VENTILADOR kW 3 7 5 7 5 MOTORE POMPA PUMP MOTOR MOTORES BOMBA kW 1 1 1 1 2 2 MATERIALE A CORREDO STANDARD ACCESSORIES MATERIAL EN DOTACIÓN GUARNIZIONE ISOLANTE INSULATING GASKET EMPAQUETADURA 2 2 2 FILTRO FILTER 1 1 4 1 1 4 1 1 2 TUBI FLESSIBILI FLEXIBLE PIP...

Страница 6: ...tch min 17 Gas pressure switch max 18 UV Photocell 19 Electromagnet 20 Air pressure switch 1 Bomba 2 Servomotor regulación aire 3 Cuadro eléctrico 4 Motor ventilador 5 Tornillo regulación aire en el cabezal de combustión 6 Precalentador 7 Motor bomba 8 Válvula de regulación presión 9 Vólvula funcionamiento tren piloto solo para COMIST 300 NM 10 Válvula de seguridad 11 Válvula de funcionamiento 12 ...

Страница 7: ...s Dimensiones A A1 A2 B B1 B2 B3 C D E F G L M N min max COMIST 180 NM 915 465 450 1225 450 775 485 1700 330 540 260 245 DN65 400 M20 300 COMIST 250 NM 1025 545 480 1255 580 675 385 1750 320 500 320 273 DN65 490 M20 340 COMIST 300 NM 1025 545 480 1260 580 680 385 1750 320 500 320 273 DN65 490 M20 350 Mod ...

Страница 8: ...orrectly installed when the pre heating tank is slightly inclined higher on the side where fuel exits to go to the nozzle This inclination serves to prevent gas from building up inside the tank Presence of gas in the preheating tank will greatly increase the time required to pressurise the fuel and it is quite likely that the burner will go into block Be careful when installing the burner on the b...

Страница 9: ...pressure stabiliser or reducer when the feed pressure exceeds 400 mm H2 O 0 04 kg cm 2 and an anti vibration union These parts must be installed as shown in our drawings see BT 8780 The following practical advice concerns the installation of essential accessories on the gas piping near the burner 1 To avoid big pressure drops on ignition there should be a piece of pipe 1 5 2 m long between the poi...

Страница 10: ...mm OF H2 O FLOW IN mc h OF METHANE p a 0 60 LENGTH OF PIPES IN METERS FLOW m3 h METHANE GAS d 0 85 IN COMMERCIAL GAS PIPES UNI 3824 68 LOAD LOSS MAX 5 mm W C N BT 1387 LUNGHEZZA VIRTUALE TRATTA in m VIRTUAL LENGHT DEALT WITH IN METRES LONGUER VIRTUELLE en m VIRTUELLE LÄNGE in m LONGITUD VIRTUAL en m PORTATA FLOW DEBIT DURCHSATZ CAUDAL m3 h BT 1387 ...

Страница 11: ...ed at a constant level independently of whether one or more burners are working at the same time thus enabling accurate regulation of the gas feed and therefore combustion resulting in better performance Gas piping must be adequately sized according to the quantity of gas to be supplied therefore it is advisable to keep the load loss within modest values not more than 10 of the gas pressure at the...

Страница 12: ...i vibration joint 11 A couple of flane D Distance between pressure stabilizer and valve about 1 5 2 m DIAGRAM OF CONNECTING A BURNER TI THE GAS PIPE NETWORK AT AVERAGE PRESSURE N BT 8531 1 1 Measuring and reducing unit 2 Interception 3 Filter 4 Reducer 5 Meter 6 Wire gauze flame trap 7 Eventual automatic overflow valve it should obviously unload outside in a suitable place 8 Emergency interception...

Страница 13: ...quired by the boiler The feed circuit must be executed according to our drawing no 0002901120 The piping must be sized to suit the length of piping and the delivery of the pump used Our instructions only concern that required to ensure good operation SPECIFIC INSTRUCTIONS FOR IGNITING A MIXED FUEL BURNER It is advisable to first ignite the burner using liquid fuel as this feed depends on the nozzl...

Страница 14: ...il recovery tanks diameter 150 height 400 should be installed as near as possible to the burner and should be about 0 5 m higher with respect to the burner s pump 1 Main cistern 2 Filter 3 Circulating pump 4 Water discharge and fuel fed system 5 Air gas discharge normally closed 6 Fuel recovery and degasifier 7 One way valve 8 By pass usually closed 9 Adjustable pressure regulator 0 2 1 bar 10 Man...

Страница 15: ...ctrodes The high voltage between the electrodes triggers the electrical discharge spark which ignites the fuel air mixture Once the ignition spark has been activated the equipment powers the magnet which by means of special lever mechanisms retracts the two shafts that cut off the flow feed and return of fuel to the nozzle Retraction of the shafts also closes the by pass inside the atomiser unit h...

Страница 16: ...ar Closing springs Pump outlet pressure gauge 20 22 bar Pre heater By pass holes 2nd flame pressure regolator 18 20 bar TRU thermostat for D version Return nozzle without needle Shaft with closing cones Atomizer unit Pre heater filter 1 Gauge to detect 1st to 2nd flame return pressure Min H 0 5 m Access to setting screws Gas and air bleeder Pumps NB The burner is fitted with an air pressure switch...

Страница 17: ... Suction 1 4 Vacuum meter connection Return Pump plate Delivery nozzle 1 4 Pressure gauge connection Heating element seal Pump pressure regulation 20 22 bar Suction Return Delivery nozzle Pump plate 1 4 Vacuum meter connection Heating element seal 1 4 Pressure gauge connection Pump pressure regulation 20 22 bar ...

Страница 18: ...valve Opened 1st flame switched on regolator Closed 1st flame switched off regulator Tie down point pressure gauge to get the backpressure which cause the output variation for the 1st and 2nd flame Pump heating resistance Enter plug to the 20 22 bar regulation pressure pump screw 1st flame pressure regulator heating resistance 18 20 bar Flame backpressure regulator almost less 2 bar than the pump ...

Страница 19: ...evice UV photocell allows the ignition phase to proceed and be completed when ignition is deactivated The unit activates the air regulation servomotor which moves the air lock to the set position see BT 8653 1 for the 2nd flame As the air regulation servomotor turns a special cam closes a microswitch that delivers power to the solenoid valve of the 2nd flame which opens gradually Therefore it is c...

Страница 20: ...ermine the exact pre heating temperature for the fuel oil Remember that the fuel must reach the nozzle at a viscosity of about 2 E To avoid interference that could cause the burner to stop the regulation thermostat must be set at a temperature of 15 20 C higher than that of the minimum thermostat Once the burner has been ignited check the reading on the pre heater thermometer to ensure that the th...

Страница 21: ...oor combustion presence of smoke formation of gas in the pre heater etc If necessary increase or decrease these settings remembering that the regulation thermostat must be set at a temperature of about 15 20 C higher than the setting on the minimum thermostat The minimum thermostat must close at the minimum temperature in order to achieve good combustion viscosity at the nozzle of about 2 E See th...

Страница 22: ...t and remain off if the flame does not appear regularly during ignition within the time allowed by the control unit Cut out leads to the fuel being shut off immediately the burner is stopped and the block LED comes on To check the efficiency of the UV photocell and the cut out device proceed as follows a Start the burner b A few minutes after ignition remove the photocell from its seat thereby sim...

Страница 23: ...itial setting can be carried out using the pressure reducer according to the value given on the pressure gauge If necessary this setting must be corrected after checking the temperature of the fuel leaving the steam heater Steam pressure on the pressure gauge bar 1 1 5 2 2 5 3 3 5 4 4 5 5 6 7 8 Approximate corresponding temperature C 120 127 133 138 143 147 151 155 158 164 169 174 Once the adjustm...

Страница 24: ...ter column instrument for low pressures do not use instruments with pointers 8 Open the air regulator as far as deemed necessary see BT 8653 1 and open the air gap between the disc and head by about one third 9 Operate the regulators on the safety valve and the first flame to enable the required gas delivery starting delivery N B See the last pages for a specific description of the procedure for r...

Страница 25: ...ult in immediate burner shut down cut out Reset the burner by pressing the special pushbutton and bring the setting on the pressure switch to a sufficient value for detecting the air pressure present during the pre ventilation phase 18 The gas pressure pressure switches minimum and maximum are used to prevent the burner from working when the gas pressure is outside the required limits According to...

Страница 26: ...ered is necessary for the boiler s needs The low calorific value for methane gas is about 8550 kcal m3 To find out the low calorific values of other types of gas contact the Gas Distributing Company Delivery per hour should be taken at the meter When checking delivery make sure that gas is not being consumed by other users If the gas delivery pressure at the meter is not above 400 mm w c take into...

Страница 27: ...ng the burner and contact the local Assistance Service to correct the fault MAINTENANCE The burner does not require any particular maintenance however it is a good rule to carry out the following operations at least at the end of the heating season 1 For burners that use gas oil remove and carefully clean the following with a solvent petrol trichloroethane petroleum filters nozzle swirl disc ignit...

Страница 28: ...ing knobs of combustion head Combustion air inlet with very locked shutter CORRECT REGULATION Combustion air inlet with air shutter sensibly open Air flow quite locked Attention Avoid complete locking GENERAL DIAGRAM AIR REGULATION Combustion head Control and fixing knobs of combustion head ...

Страница 29: ... turn in respect to the reffering scale The pointer of the red ring indicates on the respective reffering scale the rotation angle set for each cam 1 2nd Flame valve connection cam must be adjusted in a position between the 1st flame and the 2nd flame cam 2 Air regulation cam 1 flame 3 Close air shutter cam with burner in stop position 4 Air regulation cam 2nd flame 2 3 4 1 Motor cam shaft couplin...

Страница 30: ...nd 2nd flames loosen screw D unpainted screw with raised cylindrical head After the gas flow has been set remember to tighten this screw once more N B To open to the 1st flame position turn the 2nd flame regulation ring L counter clockwise by at least one full turn To set the gas flow for the 1st flame turn knob E turning it clockwise decreases gas flow turning it counter clockwise increases it Fu...

Страница 31: ...t at its minimum position Therefore it is essential to open the maximum flow rate control device E sufficiently to ensure ignition Setting the initial rapid release trip To set the initial rapid release unscrew the protection cap F and use the back of this cap as a tool to turn pin G Turning clockwise decreases the gas flow turning counter clockwise increases it This done return cap F to its origi...

Страница 32: ...n the open position while the pump and magnetic valve remain powered When the unit receives the signal to close or if power supply is cut off the pump shuts down the magnetic valve opens decompressing the chamber above the piston The plate is closed both by the return spring and by gas pressure The flow rate for this valve is calculated to ensure full closure in less than one second This type of v...

Страница 33: ...nates when the contact is tripped and the pump cuts out If the power regulator cuts off power supply to terminal 3 the magnetic valve opens and the valve will remain open until the piston reaches the 1st stage position If regulation is shut down because the power supply has been cut off terminals 1 and 3 are no longer powered this causes the servocontrol to close the valve in less than 1 second Re...

Страница 34: ...tif FEATURES Valve normally closed With flow regulator Rapid opening and closing The VE4000B1 valves are Class A solenoid valves normally closed They may be used as ON OFF valves in the supply trains with Natural Gas Manufactured Gas or GPL on burners or combustion plants They are provided with M I and CE Approval for EN 161 ADJUSTMENT For models VE 4000B1 see fig 1 Adjustment to the flow Remove t...

Страница 35: ... tolerated post combustion period The tests will end only at the end of the pre ventilation time of the next start up The validity of working of the flame control circuit is checked each time the burner starts up The fuel valve control contacts are checked for wear during the post ventilation time A built in fuse in the appliance protects the control contacts from any overloads that may occur As r...

Страница 36: ...or fan or burner NTC NTC resistor QRA UV probe R Thermostat or pressure probe RV Fuel valve with continuous regulation S Fuse SA Air damper servomotor SB Safety limiter temperature pressure etc SM Programmer synchronous motor v In the case of servomotor auxiliary contact for consensus for fuel valve depending on air damper position V Flame signal amplifier W Thermostat or safety pressure switch z ...

Страница 37: ...power regulator or at valve on terminal 20 18 t6 Post ventilation time with M2 3 t7 Time between consensus for start up and voltage at terminal 7 start delay for fan motor M2 72 t8 Start up duration without t11 and t12 3 t9 Second safety time for burners that use pilot burners 12 t10 Time from start up to beginning of air pressure control without air damper travel time t11 Air damper opening trave...

Страница 38: ... z of the air damper servo motor During the probe test and false flame test the flame supervision test is also powered terminals 22 23 and 22 24 Safety standards In association with the use of QRA earthing of terminal 22 is compulsory The power cables must conform to existing national and local standards LFL1 is a safety device and it is therefore forbidden to open it tamper with it or modify it T...

Страница 39: ...ignal was not sent to terminal 8 by limit switch contact a Terminals 6 7 and 15 remain powered until the defect is eliminated P Lock out stop because of lack of air pressure signal Any lack of pressure from this moment onwards will cause a lock out stop Lock out stop because of flame detection circuit malfunction Start up sequence stops because the position signal for low flame was not sent to ter...

Страница 40: ... During the second verification stage this pressure must remain constant Should it drop this means that the burner on the furnace side has a blow by fault when closing Therefore the DW pressure switch operates and the tightness control equipment prevents burner start up and stops in blocked state red pilot lamp lit If second stage verification is positive the LDU 11 equipment closes the internal c...

Страница 41: ...ogramme t4 5s Putting control circuit under atmospheric pressure t6 7 5s Time between start up and energizing of main AR relay t1 22 5s 1st verification stage at atmospheric pressure t3 5s Putting control circuit gas under pressure t2 27 5s 2nd verification stage at gas pressure t5 67 5s Total time of tightness control up to burner operation consent t20 22 5s Return of programmer to rest position ...

Страница 42: ......

Страница 43: ......

Страница 44: ......

Страница 45: ......

Страница 46: ......

Страница 47: ......

Страница 48: ...37 11 Fax 051 685 75 27 28 International Tel 39 051 684 37 1 1 Fax 39 051 683 06 86 http www baltur it http www baltur com E MAIL info baltur it Technical data in this brochure are given as information only Baltur reserves the right to change specification without notice ...

Отзывы: