ENGLISH
33 / 42
0006160278_201804
MANUAL RESET OF PARAMETERS FROM PME71 BOARD TO LME71 CONTROL UNIT
DisplayLME71_040
Press (>1 second) - and + push buttons at the same time to start a manual parameter
saving procedure.
PrC parameter
Display: PrC
DisplayLME71_047
Press - and + push buttons to access rSt parameter.
Display: rSt
DisplayLME71_042
DisplayLME71_043
run is displayed during the download (saving process) of the programming sequence
DisplayLME71_048
End and rSt are displayed alternately.
The display shows the end of data exchange.
The warning light flashes red.
AFTER 2 MINUTES, THE UNIT CHANGES TO LOC 138
DisplayLME71_049
After the restore process, the unit is automatically in the lockout position (LOC 138)
and must be reset for operation.
DisplayLME71_045
Press (>1second) the info push button to reset the unit.
The display shows OFF
Содержание BPM 140 E 105kW
Страница 2: ......
Страница 43: ...ENGLISH 41 42 0006160278_201804 WIRING DIAGRAMS ...
Страница 45: ......