3
/
4
FULMAR H 120
© 2018, All rights reserved BaltLED, UAB. Specifications are subject to change without notice.
SURFACE MOUNTING
9
11
10 BROWN
–
L, BLUE
–
N, YELLOW/GREEN - PE
www.baltled.com
26
th
October, 2018
FULMAR INDUSTRIAL LUMINAIRES
INSTALLATION GUIDE
STANDARD
DALI
(L)
–
line (brown)
(N)
–
neutral (blue)
(PE)
–
protective earth
(green/yellow)
(L)
–
line (brown)
(N)
–
neutral (blue)
(PE)
–
protective earth (green/yellow)
EMERGENCY (L)
–
line (black)
EMERGENCY (N)
–
neutral (grey)
(L)
–
line
(N) - neutral
(PE)
–
protective earth
(green/yellow)
DALI line (black)
DALI line (grey)
(L)
–
line (brown)
(N)
–
neutral (blue)
(PE)
–
protective earth (green/yellow)
EMERGENCY (L)
–
line (black)
EMERGENCY (N)
–
neutral (grey)
DALI line (white)
DALI line (red)
CONNECTION SCHEME
EMERGENCY
EME DALI
QUANTITY OF LUMINAIRES PER CIRCUIT BREAKER
SKU
LUMINAIRE QTY PER 16A
TYPE C CIRCUIT BREAKER
LUMINAIRE QTY PER 25A
TYPE C CIRCUIT BREAKER
BWLH-02584060
150
275
BWLH-05084060
80
147
BWLH-10084060
42
77
BWLH-15084060
29
53
BWLH-20084060
24
44
BWLH-20184060
20
37
BWLH-025840100
150
275
BWLH-050840100
80
147
BWLH-100840100
42
77
BWLH-150840100
29
53
BWLH-200840100
24
44
BWLH-201840100
20
37
BWLH-025840120
130
238
BWLH-050840120
80
147
BWLH-100840120
40
73
BWLH-150840120
27
50