Baltibond
®
Hybrid Coating and SST304L
pH
6.5 to 9.2
Total hardness (as CaCO
3
)
50 to 750 mg/l
Total alkalinity (as CaCO
3
)
600 mg/l max.
Total dissolved solids
2050 mg/l max.
Conductivity
3300 µS/cm
Chlorides
300 mg/l max.
Sulfates*
350 mg/l max.*
Total suspended solids
25 mg/l max.
Chlorination (as free chlorine / halogen): continuous
1.5 mg/l max.
Chlorination (as free chlorine / halogen): batch dosing for cleaning &
disinfection
5-15 mg/l max. for 6 hours max.
25 mg/l max. for 2 hours max.
50 mg/l max. for 1 hour max.
Circulated water quality guidelines for Baltibond
®
Hybrid Coating
*Note
: Higher concentration of sulfates is allowed, provided the sum of chl sulfates parameters does not exceed 650 mg/l for
Baltibond/SST304L.
*Note
: In case of a HDG coil, passivation of the coil is required. During this period, both the pH and the hardness of the spray water will have
more stringent requirements. The pH must be kept between 7 and 8.2, and the hardness must be kept between 100 and 300 ppm.
Baltiplus protection
pH
6.5 to 9.0
Total hardness (as CaCO
3
)
50 to 600 mg/l
Total alkalinity (as CaCO
3
)
500 mg/l max.
Total dissolved solids
1500 mg/l max.
Conductivity
2400 µS/cm
Chlorides
250 mg/l max.
Sulfates*
250 mg/l max.*
Total suspended solids
25 mg/l max.
Chlorination (as free chlorine / halogen): continuous
1 mg/l max.
Chlorination (as free chlorine / halogen): batch dosing for cleaning &
disinfection
5-15 mg/l max. for 6 hours max.
25 mg/l max. for 2 hours max.
50 mg/l max. for 1 hour max.
Circulated water quality guidelines for Baltiplus protection
*Note:
Higher concentration of sulfates is allowed provided the sum of chl sulfates parameters does not exceed 500 mg/l for
Baltiplus protection.