Lower Water Collection Channel
The lower water collection channels collect water coming off the adiabatic pre-cooler pads and redirects it into the sump. At
least quarterly and upon seasonal startup, inspect the lower water collection channels for debris. Removal of the adiabatic pre-
cooler pads is required to inspect the lower water collection channels, refer to section
Adiabatic Pre-Cooler Pad Removal
Page 24
for location of the lower water collection channels.
Figure 10. Lower water collection channel
Sump Strainer
A removable stainless-steel sump strainer is supplied for each air inlet face as shown in
. Do not operate the unit with
the sump strainers removed. The sump strainers can be accessed via the sump access doors. To remove the sump strainer,
remove all wingnuts securing the assembly and lift the assembly out of the unit using the grab handle. Ensure all wingnuts are
reinstalled when reinstalling the sump strainer. At least quarterly and upon seasonal startup, remove and clean the sump
strainers and replace, as necessary. Clean the sump strainer by removing all surface debris and ensuring the perforations are
clear.
Figure 11. Sump strainer & sump drain valve access cover