Installation by Wire

Installation by Wire

NOTE: Must install wires listed on this page for regulator to operate.

Install BLACK Ground Wire

The BLACK Ground Wire #1 in diagram at right is included in the four-wire Ford-style plug on the wiring 

harness and is factory installed on regulator packages designated with “H” at the end of the model 

number. The other end of the Ground Wire is fitted with a ring terminal connector. In some applications, 

this wire can be connected directly to the alternator’s ground terminal post. For best accuracy ground 

as close to the battery as possible, especially when charging lithium batteries.

 

Both the alternator and 

regulator must be connected to system ground.

Install RED Power Wire

The RED Power Wire #2 in diagram at right is included in the four-wire Ford style plug and is factory 

installed on regulator packages designated with “H” at the end of the model number. The other end of 

the Power Wire is fitted with a ring terminal connector. In most applications, this wire can be connected 

directly to the alternator’s positive output post. When a diode-type battery isolator is used, the power 

and voltage sense (#9) wires must be connected to the battery side of the battery isolator. The                    

Power Wire is equipped with 15-amp ATC type fuse. The Power Wire must be fused to ensure against 

damage to the voltage regulator.

Install BROWN Ignition Wire

The BROWN Ignition Wire #3 in diagram at right provides ON/OFF voltage for the regulator. This wire is 

included in the Ford-style plug at the regulator end of the wiring harness. The other end of the wire is fitted with a butt connector. 

Typically, the ignition wire is connected to the ON side of the ignition switch. This may be at the actual switch, or to a wire in the 

existing engine wiring loom that delivers switched voltage from the ignition switch. In some cases, an oil pressure switch may 

be used to activate the regulator. In either case, the regulator’s ignition wire must see zero volts when the engine ignition is 

switched off.

Install BLUE Field Wire

The BLUE Field Wire #4 in diagram at right provides regulated current to control alternator output. The wire is included in the 

wiring harness’ Ford-style plug and is preconnected at the regulator. At the other end of the wire, you’ll find either a plug or a ring 

terminal, depending on the alternator’s field terminal connection. Attach the field wire to the alternator’s field terminal.

Install Alternator Temperature Sensor

The optional Alternator Temperature Sensors  (MC-TS-A  or MC-TS-A80) allows your MC-618 voltage regulator to monitor 

your alternator temperatures and limit output if safe operating levels are exceeded. The MC-618 uses active temperature 

regulation to maximize high-temperature output. The sensor includes a 54” (MC-TS-A)  or 80” 

(MC-TS-A80) cable, a sensing attachment lug, and positive and negative regulator plug-in 

connectors. To install the either sensor:

1. 

Connect the sensor lug to one of the four bolts that hold the alternator’s front and rear 

cases together. If a Balmar alternator is installed use the predrilled location provided on 

the rear case. Extend sensor cable to the regulator. The cable can be included within the 

regulator’s wiring harness, or can be run alongside the harness and attached with cable 

ties.

2. 

Connect the temperature sensor to the Alt. Temp. terminals on the regulator. 

 It is essential that the terminals are connected 

to the correct pin. Connect the red wire to the positive terminal #6 and the black wire to the negative terminal #5. 

 Install Positive Sense Wire

Included with the MC-618 wiring harness kit is a fused wiring pigtail which features a ring terminal at one end and a butt 

connector at the other. In the center is an ATC-type fuse and fuse holder. This wire MUST be connected at the (#9) Positive 

Battery Sense Terminal. A female quick connect plug has been pre-attached on the terminal (#9) pin. To complete installation of 

the sense circuit:

1. 

Identify the favored location for battery sensing.

 

NOTE: The voltage sense wire MUST be installed on the alternator side of any disconnect device. If a 

disconnect on the positive output cable of the alternator occurs --  such as a fuse blowing or a disconnect 

switch -- the sense wire must read the alternator output voltage and not the battery voltage. If the 

alternator is disconnected from the battery and the regulator is sensing the battery voltage, it will continue 

to output power, likely causing alternator damage. 

This is not covered under warranty.

2. 

Attach the included wiring pigtail with 10-amp fuse to a length of wire of sufficient

 

length to reach the desired sensing loca-

tion. If the length of the wire

 

between the regulator and the sensing location is 8’ or less, a 16-gauge wire is satisfactory. If 

the wire exceeds 8’, increase the wire size to 14 gauge.

3. 

Remove the female 1/4” spade terminal from the terminal (#9) pin. Crimp the spade terminal to the sense wire and 

reconnect the spade to the (#9) pin.

Magnetic

Reed Switch

17
16

15

14

13

12

11

10

9

8

7

6

5

1

2

3

4

Magnetic

Reed Switch

17
16

15

14

13

12

11

10

9

8

7

6

5

1

2

3

4

Содержание Max Charge MC-618

Страница 1: ...1 MC 618 Alternator Regulator Installation Operation Manual SUP 0283 REV C 87 C Open 26 C...

Страница 2: ...ng For Battery Type 14 LFP LiFePO4 Recommendations 15 Regulator Programming Flow Chart More details can be found on pages 9 14 16 Programming The Max Field Percentage Belt Load Manager 17 Programming...

Страница 3: ...Display 1 MC 618 real time operating data 2 Battery Type selection Basic Programming 3 Adjustment of the Maximum Field Belt Load Manager When a SG2 0300 Bluetooth Gateway is used in conjunction with t...

Страница 4: ...ance from alternator distance from inverters transmitters and other sources of RF noise convenient access and readability of the display The regulator wiring harness is 54 inches long providing a thre...

Страница 5: ...5 14 13 12 11 10 9 8 7 6 5 1 2 3 4 Ignition Connector 1 Connector 2 17 16 15 14 12 13 10 11 9 7 6 5 8 4 3 2 1 External Regulator Plug Positive Battery Sense Required for Internal Regulator Only Isolat...

Страница 6: ...nal Install Alternator Temperature Sensor The optional Alternator Temperature Sensors MC TS A or MC TS A80 allows your MC 618 voltage regulator to monitor your alternator temperatures and limit output...

Страница 7: ...ne the number of poles in the alternator in order to properly adjust your tachometer Most Balmar alternators feature 12 pole rotors and stators though in some cases the pole count may be 14 or 16 See...

Страница 8: ...egulator without a harness The two fast on connectors shown here to the left are connected to pin 10 and 11 on the regulator Of the two Deutsch style connectors on the right side only one is used in a...

Страница 9: ...tch it may be necessary to start the engine before applying test 2 If the engine must be run to accomplish test 2 be sure that the alternator is properly cabled on both positive and negative sides to...

Страница 10: ...iod specified by the battery program selected Factory set values are 13 9 volts for 0 3 hours 18 minutes and are adjustable with Av and A1c respectively See page 14 7 Calculated Absorption Charge Targ...

Страница 11: ...ation on how to use the Color Display to change MC 618 settings see the SG200 manual NOTE When a battery program is changed all settings under Advanced Settings will be replaced with the new battery p...

Страница 12: ...es Yes Yes Yes Yes Yes Standard Flooded Halogen Systems Lithium Yes Yes Yes Yes Yes Carbon Foam AGM Yes Balmar Alternator Models 6 Series Alternators 70A 150A Yes Yes Yes Yes Yes Yes XT AT Series Alte...

Страница 13: ...GULATOR TOO HOT OVER 90 C E25 BATTERY TOO COLD BELOW LIMIT E33 BATTERY SENSE DIS CONECTED E41 FIELD VOLTAGE TOO HIGH E42 STATOR VOLTAGE TOO HIGH E51 SMALL ENGINE MODE IS IN OPERATION E52 BELT LOAD MAN...

Страница 14: ...asic Programming with Reed Switch Basic Programming with Reed Switch Programming For Battery Type The MC 618 features selectable programs for the following battery technologies Standard Flooded FSb De...

Страница 15: ...n the battery or batteries can handle you may use the Max Field Belt Manager feature on the MC 618 to lower the maximum field drive output and thereby lower the maximum alternator output current See p...

Страница 16: ...a Spiral FSB Flooded Standard HAL Halogen Lighting LFP LiFeP04 FEL Max Field Belt Load F 1 95 Field F 2 90 Field Max F 3 85 Field F 4 80 Field F 5 75 Field F 6 70 Field F 7 65 Field F 8 60 Field F 9 5...

Страница 17: ...ETTING 1 FIELD REDUCTION 5 F 2 INDICATES FEL SETTING 2 FIELD REDUCTION 10 F 3 INDICATES FEL SETTING 3 FIELD REDUCTION 15 F 4 INDICATES FEL SETTING 4 FIELD REDUCTION 20 F 5 INDICATES FEL SETTING 5 FIEL...

Страница 18: ...e magnet from the reed switch 2 Wait for the mode indicator to be displayed 3 TOUCH HOLD when the mode indicator is displayed The values for that mode will begin to scroll in the opposite direction Co...

Страница 19: ...old Bulk and Absorption Controls the field output threshold required to cycle from Bulk to Absorb and Absorb to Float Factory set at 65 of field output Raising FbA shortens calculated bulk and absorpt...

Страница 20: ...supplied and installed audible or visual alert if the following issues were to occur while the regulator is in operation Low Battery Voltage 12 8V Adjustable with ALL See Page 12 High Battery Voltage...

Страница 21: ...3 Add appropriate connectors to the switched wires and connect to the positive and negative terminal connections If feature is activated prior to the regulator turning on then the regulator will star...

Страница 22: ...lso helpful diagnostic tools Voltage Regulator Testing Set your voltmeter to 12VDC and connect the negative lead to the BLACK ground wire at the regulator as shown at the diagram at right 1 With the i...

Страница 23: ...d Testing This can be accomplished by jumping a positive 12VDC current to the field terminal at the rear of the alternator This test eliminates both the regulator and the harness making it easier to i...

Страница 24: ...24 NOTES...

Страница 25: ...accident abuse neglect exposure to shock electrostatic discharge heat or humidity beyond the product s specifications improper installation inappropriate operation misapplication maintenance or modifi...

Страница 26: ...ange This guide was prepared to provide information and does not constitute a contract Balmar reserves the right without prior notice to change delete supplement or otherwise amend at any time the inf...

Отзывы: