Installation
For dimensions, see Fig. 4-1 on page 7.
►
Fasten the module with 2 M6 screws and a maximum
tightening torque of 3 Nm using the mounting holes
5.2
Electrical connection
Requirements for complying with the protection
classes:
For IP67, all plugs and caps must be properly connected
and the tightening torque of 0.6 Nm must be observed
(see data sheets of connectors and caps)
5.2.1 Power supply
NOTICE
Unwanted voltage dips
Non-separated electric circuits of the power supplies for
sensor and actuator can lead to unwanted voltage dips
of the sensor supply when switching actuators.
►
Fuse the power supplies for sensors and actuators
separately.
►
Make sure that the power supply of the device is
sufficiently dimensioned to cover start-up and peak
currents and design the fuse protection concept
accordingly.
– Establish power supply of sensor/bus and
actuator via a separate power source if possible.
– The total current for the sensor and actuator
supply must not exceed 16 A each.
– For UL: Observe cable requirements and power
supply requirements (see chapter 8.7.2 on
page 14)!
5
Installation and connection
M12 plug
(L-coded, with FE)
M12 socket
(L-coded, with FE)
Fig. 5-1: Top view of M12 plugs (left) and sockets (right)
Pin
Signal
Description
1
+24 V US
Module/sensor voltage
2
GND UA
Actuator supply
3
GND US
Sensor supply
4
+24 V UA
Actuator supply
5
FE
Functional earth
Tab. 5-1: Pin assignment
BNI EIP-508-105-Z067
Network interface
Содержание BNI00H7
Страница 1: ...deutsch Betriebsanleitung english User s guide BNI EIP 508 105 Z067...
Страница 2: ...www balluff com...
Страница 3: ...BNI EIP 508 105 Z067 Betriebsanleitung deutsch...
Страница 4: ...www balluff com...
Страница 17: ...BNI EIP 508 105 Z067 User s Guide english...
Страница 18: ...www balluff com...
Страница 31: ......