connected to the Port. Each device will have a unique Device ID that can be found in its
corresponding manual.
4.5.6
Port_x_Serial_Number –(x = 1, 2, 3, or 4) this 16-byte SINT array indicates the Serial Number
of the device connected to the Port.
4.5.7
Port_x_Parameter_Upload_Enable – (x = 1, 2, 3, or 4) this Boolean value must be set “high” or
ON to perform an upload of the current parameter set. ). (Note: The connected IO-Link device
must support this feature)
4.5.8
Port_x_Parameter_Download_Enable – (x = 1, 2, 3, or 4) this Boolean value must be set “high”
or ON to perform a download of the current parameter set. ). (Note: The connected IO-Link
device must support this feature)
4.5.9
Port_x_Parameter_Server_Enable – (x = 1, 2, 3, or 4) this Boolean value must be set “high” or
ON to allow either an upload or a download of the current parameter set. ). (Note: The