www.balluff.com
9
english
5.1
Installation
For dimensions, see Fig. 4-1 on page 7.
►
Fasten the module with 2 M6 screws and a maximum
tightening torque of 3 Nm using the mounting holes
5.2
Electrical connection
Requirements for complying with the protection
classes:
For IP67, all plugs and caps must be properly connected
and the tightening torque of 0.6 Nm must be observed
(see data sheets of connectors and caps).
5.2.1 Power supply
NOTICE
Unwanted voltage dips
Non-separated electric circuits of the power supplies for
sensor and actuator can lead to unwanted voltage dips
of the sensor supply when switching actuators.
►
Fuse the power supplies for sensors and actuators
separately.
►
Make sure that the power supply of the device is
sufficiently dimensioned to cover start-up and peak
currents and design the fuse protection concept
accordingly.
– Establish power supply of sensor/bus and
actuator via a separate power source if possible.
– The IO-Link master BNI PG3-508-0C5-Z015
cannot be supplied from the same power
source as galvanically isolated devices such as
BNI PNT-538-_05-Z063 (see Tab. 5-1).
– The total current for the sensor and actuator
supply must not exceed 9 A each.
5
Installation and connection
7/8" socket (Power OUT)
7/8" plug (Power IN)
Fig. 5-1: Top view of 7/8" socket (left) and plug (right)
Pin
Signal
Description
1
GND
Common ground
2
3
FE
Functional earth
4
US
Module/sensor v24 V
5
UA
Actuator 24 V
Tab. 5-1: Pin assignment
BNI PG3-508-0C5-Z015
Network interface
Содержание BNI PG3-508-0C5-Z015
Страница 1: ...deutsch Betriebsanleitung english User s guide BNI PG3 508 0C5 Z015...
Страница 2: ...www balluff com...
Страница 3: ...BNI PG3 508 0C5 Z015 Betriebsanleitung deutsch...
Страница 4: ...www balluff com...
Страница 16: ......
Страница 17: ...BNI PG3 508 0C5 Z015 User s guide english...
Страница 18: ...www balluff com...