Configuration via Explicit Messages (continued)
3.5
IO-Link device parameterization
There are two ways to parameterize an IO-Link device
connected to the IO-Link Port.
– Parameterization via the web server (see
page 36)
– Parameterization via
Explicit Messages
The following section describes, for example, how via
Rockwell RSLogix 5000 an IO-Link device can be
parameterized via
Explicit Messages
.
The
MSG
modules are used in the PLC program (see
Fig. 3-2).
Fig. 3-2: MSG modules
3.5.1 Read IO-Link parameters
Service code Class
Instance Attribute
0x32
0x96
1…n
1)
0x03
(Read
parameters)
1)
n: Number of ports
Tab. 3-6: Values for read IO-Link parameters
Source Length
must at least correspond to the read
parameters, but can also be bigger (in this example
100 bytes).
1.
As a
Source Element
(Write) and as a
Destination
Element
(Read), create a SINT[100] Array and select
the first row [0].
Fig. 3-3: Create SINT[100] Arrays
BNI EIP-508-105-Z067
Network interface