Tell the Controller About the Device

2

1. Every controller will need to know three things about the device being connected 
    over EtherNet/IP: 
 

n

  The IP address of the block 

 

n

  Where to look for the data (Instance ID) in the block

 

n

  How much data is at the location (Data length) 

2.  Setup the block in the engineering software with the Instance ID and the Data 

Length for the input data, the output data and the configuration data. 

Instance ID

Data Length (Bytes)

Input

100

200

Output

101

134

Configuration

102

98

Instance ID: 

 where the data is located in the device, sometimes called the 

assembly instance number.

Data length: 

 how much data to expect at this location, these are 8bit, 1byte 

short integers. For controllers that read in 2byte words or in individual bit 
counts, please see the Balluff website for the data assistance spreadsheet.

Troubleshooting Tips:

n

  For assistance with programming these values into a specific controller or 

engineering software, please contact the controller manufacturer.

n

  Some controllers have a maximum data size below the 200 bytes required, 

review the parameters of the controller before selecting.

n

  Some controllers are using a third party device (such as an Anybus gateway) 

to communicate over EtherNet/IP. These devices typically require additional 
software to configure and establish communication properly. 

Using Electronic Data Sheet (EDS) Files

The EDS file in RSLogix5000 Ver 20

 

To make life easier for some engineering platforms the eds 
files are available for download from networks.balluff.com

Содержание BNI EIP-502-105-Z015

Страница 1: ...for 4 port IO Link Master Communication Discrete I O Discrete I O Analog I O Outputs Specialty Power Power Discrete I O Analog I O Valve Manifold Control RFID or Specialty Devices Discrete I O Quick...

Страница 2: ...IO Link 1 IO Link 2 IO Link 3 IO Link 4 Pin Function Description 1 TX Transmit Data 2 RX Receive Data 3 TX Transmit Data 4 RX Receive Data M12 Network Port Pin Function Description 1 24 V Actuator Su...

Страница 3: ...are 8bit 1byte short integers For controllers that read in 2byte words or in individual bit counts please see the Balluff website for the data assistance spreadsheet Troubleshooting Tips n For assista...

Страница 4: ...established n Make sure there are no IP Address conflicts between devices n Ensure that the devices are connected on the same LAN or hardwired network n EtherNet IP DLR Device Level Ring capable devic...

Страница 5: ...k device there are some configuration bytes that must be setup Description Byte Bit 7 6 5 4 3 2 1 0 For Standard I O 0x00 For IO Link 0x01 0 IO Link 2 IO Link 1 0 0 0 0 1 IO Link 4 IO Link 3 0 0 0 0 2...

Страница 6: ...Bit 7 6 5 4 3 2 1 0 IO Link Slave Device Specific Data 8 39 56 87 104 135 152 183 IO Link Slave Device 32 bytes of Input For bitmap details see slave device manual DC Device Connected IOL IO Link Mod...

Страница 7: ...ber of Output 0 07 06 05 04 03 02 01 00 1 15 14 13 12 11 10 09 08 Restart Output after overload Pin Number of Output 2 07 06 05 04 03 02 01 00 3 15 14 13 12 11 10 09 08 Reserved Data 4 0 0 0 0 0 0 0 0...

Страница 8: ...4 Phone 905 816 1494 Toll free 1 800 927 9654 Fax 905 816 1411 E mail balluff canada balluff ca Web www balluff ca Networking Connectivity Catalog for selecting specific part numbers accessories White...

Отзывы: