- 38 -

6.6 Initial setting

Following initial setting is needed to communicate with code tag.

(1) Initial setting with factory setting

(a) In using ACPU

* Regard that the following example shows RX : M200...M327, RY : M328...M455.

M9036

FROM

H0

H680 K4M100

K4

Reading other data link condition

FROM

H0

H0E0 K4M200

K8

Reading input contact (RX)

M320

M100

SET

M328

Factory setting

(RX78) (Link)

(RY0)

SET

M448

ON finish processing initial data

(RY78)

SET

M449

ON require setting initial data

M205

(RY79)

FROMP

H0

H2E1 R0

K1

Reading error code of setting dip switch

M320(RX78)

(RX5)

(RY0)

RST

M448

OFF finish processing initial data

M321(RX79)

(RY78)

RST

M449

OFF require setting initial data

M9036

(RY79)

TO

H0

H160 K4M328

K8

Writing output (RY)

(b) In using QnACPU

Automatic refresh parameter is set with GX Developer as followings.

* Regard that the following example shows refresh range RX : M208...M335, RY : M336...M463

1. Setting with GX Developer

Start I/O No.

: 0000

Type

: Master station

All connect count

: 1

Remote input (RX)

: M208

Remote output (RY)

: M336

Remote register (RWr)

: D200

Remote register (RWw)

: D100


-

Special relay (SB)

:

Special register (SW)

: -

Retry count

: 3

utomatic connection station count

: 1

・A

Standby master station number

: 0

PLC down select

: Stop

Scan mode setting

: asynchronous

Delay information setting

: 0

Station information setting

: station information

2. Program

SM400

Reading other data link condition

FROM

H0

H680

K4M100

K4

M328

M100

Factory setting

SET

M336

(RX78) (link)

(RY0)

ON finish processing initial data

SET

M456

(RY78)

ON require setting initial data

SET

M457

M213

(RY79)

Reading error code of setting dip switch

FROMP

H0

H2E1

R0

K1

M328(RX78)

(RX5)

(RY0)

OFF finish processing initial data

RST

M456

M329(RX79)

(RY78)

OFF require setting initial data

RST

M457

(RY79)

Содержание BIS Series

Страница 1: ...fety if the processor should be damaged or the power unit malfunction Do not exceed the specifications for supply voltage conditions for use etc as indicated in this manual Handling the System Observe...

Страница 2: ...ng 22 4 2 1 Cable for CC Link 22 4 2 2 Wiring with each Unit 22 4 3 Each Part and Setting 24 5 Instructions for Programming 5 1 Connecting the System and Processing Data 26 5 2 Construction of Data Pr...

Страница 3: ...of Life Expectancy of Code Tag Information 65 7 Trouble Shooting 7 1 List of Error Code 67 7 2 Trouble Shooting 68 7 2 1 Confirmation Procedure on LED indicator 68 7 2 2 Procedure for Fault of Data L...

Страница 4: ...ores and retains information data Read write Head A Head that reads and writes information data in code tag without physical contact Supplies power for code tag Processor A Processor that executes rea...

Страница 5: ...SCPU A2USCPU S1 On and after software version E On and afer version A available only RRPA function A2USHCPU S1 On and after software version L On and afer version G available only RRPA function QnACPU...

Страница 6: ...from 20Hz to 40Hz from 20Hz to 10Hz 2 2 Efficiency Following are Efficiency of Processor BIS C 489 Applicable read write head BIS C 3 Connecting procedure for head D sub 9 pin connector Connectable q...

Страница 7: ...4 2 3 Dimension...

Страница 8: ...uence until code tag gets into 6 8 2 Writing SW 5753H communication area and then executes writing After that compares data to check Batch FI 4946H Writes specified data to specified area in code tag...

Страница 9: ...Writing Instruction AW SW Reads data in the code tag after waiting for code tag to get into communication area of read write head Batch Writing Instruction FI Writes specified 1 word data from specifi...

Страница 10: ...ruction RYn4 RYnC Require executing identification instruction RXn5 RXnD Error detection RYn5 RYnD Unused RXn6 RXnE Unused RYn6 RYnE Unused RXn7 RXnF Require divided data RYn7 RYnF Finish divided data...

Страница 11: ...instruction cancellation while executing sequence instruction AR SR AW SW When error is occurred it won t be ON and error detection signal Xn5 XnD will be ON Require executing identification instructi...

Страница 12: ...Flag for requiring to process initial data RX n 7 8 Flag for finishing to process initial data RY n 7 8 Flag for finishing to set RX n 7 9 Flag for finishing initial data RX n 7 9 to set initial data...

Страница 13: ...0 is OFF user setting unit It is only word unit setting OFF word unit ON unused to set ON it will be word unit RYn2 Selecting number Specify number of channel to use Setting is effective when of chann...

Страница 14: ...reading data 5 RWrn 7 RWrn F RWwm Unavailable Writing area 3 3 2 1 RWwm 1 Specifying area for instruction code master station Specifying area for first address 3 3 2 2 RWwm 2 3 3 2 3 RWwm 3 Specifyin...

Страница 15: ...fying area for instruction code Head I O number of master unit Change with ASC instruction Store 4452H ASC RD D0 TOP Hn D0 K1 Store into specifying area for instruction code Head I O number of master...

Страница 16: ...sing numbers 4096 1000H Specify in the range of memory capacity of the code tag 4 Specifying area for writing data Specify data to be written into code tag ex Specify contents of D100 D104 to writing...

Страница 17: ...time valid in initial setting only Specifies standby time per 10ms when the code tag gets into communication area to inzone detection starting communication in executing sequence instruction 0 32767 0...

Страница 18: ...erval of sequence instruction to be 5 sec 5000ms Set interval TOP Hn K50 K1 Store into specifying area for interval of executing sequence instruction Head I O number of master unit Executing interval...

Страница 19: ...ruction of code tag memory 511 byte code tag address Processor BIS C 489 13 KBT02 Code tag address Hex Page byte address word address START END START END 0 0 1F 0 0F 1 20 3F 10 1F 2 40 5F 20 2F 3 60 7...

Страница 20: ...C 180 19F C0 CF D 1A0 1BF D0 DF E 1C0 1DF E0 EF F 1E0 1FF F0 FF 10 200 21F 100 10F 11 220 23F 110 11F 12 240 25F 120 12F 13 260 27F 130 13F 14 280 29F 140 14F 15 2A0 2BF 150 15F 16 2C0 2DF 160 16F 17...

Страница 21: ...F 9 240 27F 120 13F A 280 2BF 140 15F B 2C0 2FF 160 17F C 300 33F 180 19F D 340 37F 1A0 1BF omission 14 500 53F 280 29F 15 540 57F 2A0 2BF 16 580 5BF 2C0 2DF 17 5C0 5FF 2E0 2FF 18 600 63F 300 31F 19 6...

Страница 22: ...0 1BF E 380 3BF 1C0 1DF F 3C0 3FF 1E0 1FF 10 400 43F 200 21F 11 440 47F 220 23F 12 480 4BF 240 25F 13 4C0 4FF 260 27F 12 500 53F 280 29F 15 540 57F 2A0 2BF 16 580 5BF 2C0 2DF 17 5C0 5FF 2E0 2FF 18 600...

Страница 23: ...0 2 8sec 8 6sec 200 400 2 8sec 8 6sec 250 500 3 5sec 11 0sec 250 500 3 5sec 11 0sec 300 600 4 2sec 12 1sec 300 600 4 2sec 12 1sec 350 700 4 9sec 14 2sec 350 700 4 9sec 14 2sec 400 800 5 6sec 17 3sec 4...

Страница 24: ...t appropriate for installing processor BIS C 489 a Where operating temperature exceeds the range of 0 55 degrees C b Where temperature varies extremely with dew condensation c Where relative humidity...

Страница 25: ...Processor Remote unit DA DA DA Terminal resistor Terminal resistor DB DB DB DG DG DG SLD SLD SLD FG 24V 24G FG FG Attention Terminal resistor should be connected with DA DB on both unit at the end of...

Страница 26: ...tor Color CH1 S OUT1 BK S OUT2 BK WH S IN1 GN S IN2 GN WH 24V RD 24V RD WH Shield Connector Color CH2 S OUT1 BK S OUT2 BK WH S IN1 GN S IN2 GN WH 24V RD 24V RD WH Shield Appropriate connector D sub 9...

Страница 27: ...OFF 9 ON OFF OFF ON Setting switch for transmitting rate of data link Transmission rate of data link Switch No B RATE 4 2 1 156kbps OFF OFF OFF 625kbps OFF OFF ON 2 5Mbps OFF ON OFF 5Mbps OFF ON ON 10...

Страница 28: ...CH1 ID Light on wrong condition read write head CH1 ERR when setting switch for block no is out of set range Blinking when setting switch for block no is changed in set range Light off normal conditi...

Страница 29: ...with MELSECNET Ethernet etc CC Link master local station Read write Code Head tag CH1 Sequencer Master Processor CPU unit BIS C 488 CH2 Cable for read write head Word unit Processor BIS C 489 Read wr...

Страница 30: ...d 506 251 507 252 508 253 509 254 510 255 2 words 511 2 words 1 Life expectancy of Code Tag Information 2 words BIS C 489 11 KBT02 BIS C 489 15 KBT02 0 0 1 1 2 2 3 3 4 4 5 5 6 6 Memory address 1022 40...

Страница 31: ...put signal Interlock signal Instructions ASCII Hex RXn3 RXn4 RXn5 RYn4 RYn5 RXnB RXnC RXnD RX n 7 8 RX n 7 B RYnC RYnD Reading RD 4452H CR 5243H Sequence reading AR 5241H SR 5253H Writing WD 4457H Com...

Страница 32: ...essor released data link Data link stop The data cannot be transmitted to master station because 1 data link has been stopped 2 Condition of communication with code tag Condition of communication with...

Страница 33: ...signals should be inserted Refer to 5 4 on signals for handshake 2 Reading and writing of remote register Sequence program to read or write of remote register is necessary to communicate with code ta...

Страница 34: ...d in writing Objective instruction RD CR AR SR WD CW AW SW CM ex using both of CH 1 CH 2 The first address for reading and writing to code tag 0 Number of words for reading and writing to code tag 7 A...

Страница 35: ...ting in sequence until code tag gets into 6 8 2 Writing SW 5753H communication area and executes writing when code tag got into communication After that compares data to check Batch FI 4946H Writes sp...

Страница 36: ...mote device station Remote device Sequencer CPU Master unit Processor Remote Input RX Remote Input RX Address M208 M223 E0H RX00 RX0F RX00 RX0F M224 M239 E1H RX10 RX1F RX10 RX1F M240 M255 E2H RX20 RX2...

Страница 37: ...sequence program for refreshing RX RY The following sequence program should be added In the case of the following setting is set sequence program for refresh is not required Using QJ61BT11 AJ61QBT11...

Страница 38: ...ates program to stand data link with CC Link refresh command after setting of parameter ex Number of connecting station 1 Connecting station BIS C 489 station number 1 occupies 4 stations X0 X0F PLS M...

Страница 39: ...4 1 E H Station number 30 1EH Number of occupied station Processor occupies 4 stations Station type Processor is remote device station 2 Reading data link condition of processor remote input RX Creat...

Страница 40: ...al setting program of master unit parameter setting data link setting M9036 SM400 FROM H0 H680 K4M100 K4 Reading data link condition FROM H0 H0E0 K4M200 K8 Reading RX information K4M208 M100 RST M332...

Страница 41: ...et with GX Developer as followings Regard that the following example shows refresh range RX M208 M335 RY M336 M463 1 Setting with GX Developer Start I O No 0000 Type Master station All connect count 1...

Страница 42: ...etting 0 Station information setting Station information Initial setting of remote device Initial setting Interrupt setting Initial setting Input format Hex Execute Operating Condition of executing pr...

Страница 43: ...lect number of using channel to 2 channel RY2 MOVP K5 D100 Specify retry count 5 times MOVP K200 D101 Specify inzone detecting time 2 sec CH1 MOVP K50 D102 Specify interval for executing sequence inst...

Страница 44: ...M H0 H680 K4M100 K4 Reading other data link condition M328 M100 RST M336 User setting RX78 link RY0 RST M337 Setting processing unit to word RY1 RST M338 Select number of using channel to 2 channel RY...

Страница 45: ...ecute Same as prev set RX 78 ON RY 01 OFF Using 2 channels Execute Same as prev set RX 78 ON RY 02 OFF Retry count CH1 Execute Same as prev set RX 78 ON RWw 00 5 Inzone detecting time Execute Same as...

Страница 46: ...52H CR Code 5243H 1 Operation timing The following chart shows operating timing ON External signal OFF ON M1 OFF Store data Store data Writing parameter to D1000 D1004 to D1005 D1009 ON Sequence progr...

Страница 47: ...rom remote register to processor to device of sequencer CPU when RX7 is ON Execute reading ON RY7 Executes divided time It is not executed when OFF RX7 the data is not divided OFF RY7 Stores reading d...

Страница 48: ...0 link RX7B RX3 RX4 RY4 MOVP K10 D101 10 Setting first address of reading K MOVP K10 D102 K10 Setting number of reading word Writing of setting digit TOP H0 H1E0 D100 K3 Start executing instruction SE...

Страница 49: ...uction code Sequence reading instruction AR code 5241H SR code 5253H 1 Operation timing The following chart shows operation timing ON External signal OFF ON M1 OFF Writing parameter Store data to D100...

Страница 50: ...cer CPU when RX7 is ON Execute sequence reading ON RY7 Executes divided time It is not executed when OFF RX7 the data is not divided OFF RY7 Stores reading data with FROM instruction from remote resis...

Страница 51: ...00 link RX7B RX3 RX4 RY4 MOVP K10 D101 10 Setting first address of reading K MOVP K10 D102 K10 Setting number of reading word Writing of setting digit TOP H0 H1E0 D100 K3 Start executing instruction S...

Страница 52: ...g instruction WD Code 4457H CW Code 5743H 1 Operation timing The following chart shows operating timing ON External signal OFF ON M1 OFF Writing parameter Store data from Store data from ON D2000 D200...

Страница 53: ...ot executed when OFF RX7 the data is not divided OFF RY7 Read write Code Head tag ON finish identification instruction relay RX4 and comparing accordance contact relay RX1 Execute writing OFF RY4 OFF...

Страница 54: ...OVP K10 D101 10 Setting first address of writing K MOVP K10 D102 K10 Setting number of writing word Sets D2000 D2004 as writing data BMOVP D2000 D103 K5 Writing of setting digit TOP H0 H1E0 D100 K3 Wr...

Страница 55: ...ruction code Sequence Writing Instruction AW code 5741H SW code 5753H 1 Operation timing The following chart shows operating timing ON External signal OFF ON M1 OFF Writing parameter Store data from S...

Страница 56: ...ided OFF RY7 Read write Code Head tag ON finish identification instruction relay RX4 and comparing accordance relay RX1 Execute writing OFF RY4 OFF RX1 RX3 RX4 Attention When a write command includes...

Страница 57: ...MOVP K10 D101 10 Setting first address of writing K MOVP K10 D102 K10 Setting number of writing word Sets D2000 D2004 as writing data BMOVP D2000 D103 K5 Writing of setting digit TOP H0 H1E0 D100 K3 W...

Страница 58: ...N and read write head OFF ON Error detection M213 RX5 OFF 2 Explanation of operating The following explains the timimg operation Sequencer CPU Processor ON external relay M1 set instruction code first...

Страница 59: ...link condition FROM H0 H680 K4M100 K4 M1 M100 M331 M211 M212 M340 Setting instruction code MOVP H4946 D100 Link RX7B RX3 RX4 RY4 MOVP K10 D101 10 Setting first address of writing K MOVP K10 D102 K10...

Страница 60: ...l signal OFF ON M1 OFF Writing parameter Store data from Store data from ON D2000 D2004 D2005 D2009 Sequence program OFF TOP TOP Request of executing ON ID instruction M340 RY4 OFF Finish of ON ID ins...

Страница 61: ...ring data with TO instruction when RX7 is ON ON RY7 Executes divided time It is not executed when OFF RX7 the data is not divided OFF RY7 Read write Code Head tag ON finish identification instruction...

Страница 62: ...ng word Sets D2000 D2004 as comparing data BMOVP D2000 D103 K5 Writing of setting digit TOP H0 H1E0 D100 K3 Write comparing data TOP H0 H1E3 D103 K5 Start executing instruction SET M340 RY4 Initializa...

Страница 63: ...13 RX5 OFF 2 Explanation of operating The following explains the timimg operation Sequencer CPU Processor ON external relay M1 set instruction code with TO instruction then ON RY4 ON RX3 Read write Co...

Страница 64: ...400 Reading other data link condition FROM H0 H680 K4M100 K4 M1 M100 M340 M211 M212 M340 Setting instruction code MOVP H4C43 D100 Link RX7B RX3 RX4 RY4 Specify the first address to clear K10 MOVP K10...

Страница 65: ...nnel CH1 External External Signal interlock signal Start SET M2 SM400 Reading other data link condition FROM H0 H680 K4M100 K4 M2 M100 M331 M212 M213 M340 M1 sequence instruction RST M340 Stop link RX...

Страница 66: ...on Program to cancel error that occurred in using instructions written in this chapter Using channel CH1 External External Signal interlock signal Start SET M2 SM400 Reading other data link condition...

Страница 67: ...ate of manufacture Hex Address per word 3FE 3FF Address per byte 7FD 7FC 7FF 7FE Life expectancy information 20 06 00 is the data of system management and impossible to write in Code tag FRAM memory e...

Страница 68: ...2 RX4 OFF ON ID BUSY M211 RX3 OFF Communication code tag ON and read write head OFF ON Error detection M213 RX5 OFF 2 Explanation of operating Following are about operating of timing chart Sequencer C...

Страница 69: ...k signal Start SET M1 SM400 Reading other data link condition FROM H0 H680 K4M100 K4 M1 M100 M331 M211 M212 M340 Setting instruction code MOVP H524C D100 link RX7B RX3 RX4 RY4 Writing of setting digit...

Страница 70: ...Set address Setting address exceeds Check address page address in WP error setting range page address instruction of sequence program does not 11H digit in WP instruction exceed setting range of addre...

Страница 71: ...e above procedure 1 LED PW turns off 2 Watch dog timer error occurred Reset hardware with reset switch 3 The LED does not turn on Possible hardware problem when power is supplied again Consult manufac...

Страница 72: ...make wiring in pipe ground pipe surely LED ID ERR turns on 7 Cause Procedure 1 Contents of error code Confirm contents of error code Check the sequence of the program refer to procedure 7 1 2 Block se...

Страница 73: ...SW009B duplicated station number is ON or not Check master side Y Check SW0098 SW009B Check SW0080 SW0083 that indicates ON that indicates ON Check slave side N Station number Power is supplied or no...

Страница 74: ...ber N switch is set correctly Station number is defective accordance or not 3 Set station no correctly Y Supply power again ON reset switch N MST LED turns off or not Master unit already Y exist Reset...

Отзывы: