- 38 -
6.6 Initial setting
Following initial setting is needed to communicate with code tag.
(1) Initial setting with factory setting
(a) In using ACPU
* Regard that the following example shows RX : M200...M327, RY : M328...M455.
M9036
FROM
H0
H680 K4M100
K4
Reading other data link condition
FROM
H0
H0E0 K4M200
K8
Reading input contact (RX)
M320
M100
SET
M328
Factory setting
(RX78) (Link)
(RY0)
SET
M448
ON finish processing initial data
(RY78)
SET
M449
ON require setting initial data
M205
(RY79)
FROMP
H0
H2E1 R0
K1
Reading error code of setting dip switch
M320(RX78)
(RX5)
(RY0)
RST
M448
OFF finish processing initial data
M321(RX79)
(RY78)
RST
M449
OFF require setting initial data
M9036
(RY79)
TO
H0
H160 K4M328
K8
Writing output (RY)
(b) In using QnACPU
Automatic refresh parameter is set with GX Developer as followings.
* Regard that the following example shows refresh range RX : M208...M335, RY : M336...M463
1. Setting with GX Developer
Start I/O No.
: 0000
・
Type
: Master station
・
All connect count
: 1
・
Remote input (RX)
: M208
・
Remote output (RY)
: M336
・
Remote register (RWr)
: D200
・
Remote register (RWw)
: D100
・
・
-
Special relay (SB)
:
Special register (SW)
: -
・
Retry count
: 3
・
utomatic connection station count
: 1
・A
Standby master station number
: 0
・
PLC down select
: Stop
・
Scan mode setting
: asynchronous
・
Delay information setting
: 0
・
Station information setting
: station information
・
2. Program
SM400
Reading other data link condition
FROM
H0
H680
K4M100
K4
M328
M100
Factory setting
SET
M336
(RX78) (link)
(RY0)
ON finish processing initial data
SET
M456
(RY78)
ON require setting initial data
SET
M457
M213
(RY79)
Reading error code of setting dip switch
FROMP
H0
H2E1
R0
K1
M328(RX78)
(RX5)
(RY0)
OFF finish processing initial data
RST
M456
M329(RX79)
(RY78)
OFF require setting initial data
RST
M457
(RY79)
Содержание BIS Series