![Balluff BAV MA-NC-00025-01 Скачать руководство пользователя страница 6](http://html1.mh-extra.com/html/balluff/bav-ma-nc-00025-01/bav-ma-nc-00025-01_user-manual_3611700006.webp)
2
english
BAV MA-NC-00025-01
Condition Monitoring Toolkit Base Unit
Technical Data
General Features
Memory
8 GB eMMC
Ethernet connection
RJ45, 2 × 10/100 MBit/s
Micro SD card
Class 10, 128 GB tested
USB-Port
USB 2.0
EMV directive 2014/30/EU
EN 61000-6-1
EN 61000-6-3
Ambient conditions
Ambient temperature
−20…+60 °C
Storage temperature
−20…+70 °C
Protection per IEC 60529
IP20
Electrical data
Operating voltage
25.5…30 V DC
Power consumption
(without connected sensors)
at 24 V
≤ 180 mA
Maximum total current
IO-Link device supply
2.4 A (0.5 A per output)
Entire system
3 A
Ripple
< 1 %
Clock frequency
≤ 1.8 GHz (A53 core) /
400 MHz (M4 core)
Electrical connection
Power supply
2-pole Phoenix connector
IO-Link
M8, 4-pins, A-coded, female
Mechanical features
Weight
approx. 230 g
Written offer
This product contains software components that are
licensed by the copyright holders as Free Software or
Open Source Software under the GNU General Public
License, version 2, or the GNU Lesser General Public
License, version 2.1. You may receive the source code of
these software components from Balluff GmbH on a data
carrier of our choice, if you submit a request within three
years after shipping of the product (delivery made by
Balluff GmbH) to the following address:
Balluff GmbH
Open Source
Schurwaldstrasse 9
73765 Neuhausen a.d.F.
Please enter the following product data:
– Name of the product
– Serial number
– Delivery date
A fee will be charged, which is no higher than the cost of
physically performing source distribution.
Control and display elements
Pushbutton S1
Reset to factory settings:
►
Press and hold pushbutton S1 approx. 15 seconds
until the PWR, L1 and L2 LEDs light up continuously.
⇒
All settings are deleted and reset to the factory
settings.
Status-LEDs
LED Status
Function
PWR Off
No power supply
Green
Power supply available, the device is
ready.
L1
Off
Without meaning
Red
Reset to factory setting active.
L2
Off
Without meaning
Yellow
Reset to factory setting active.
Port-LEDs
LED Status
Function
1
Off
State of the Input or Output Pin is 0.
Yellow
State of the Input or Output Pin is 1.
0
Green
IO-Link connection established.
Green
flashing
No IO-Link communication.
Red
flashing
Validation failed.
Port configuration
Diagnostic
input
Input
Output
Input low
Short-circuit
Pin 1 and 3
Short-circuit
on output Pin
–
–
Short-circuit
Pin 1 and 3
Electrical connection
Power supply
M8 IO-Link connectors
1
3
2
4
M8, female, 4-pins
(top view)
Pin
Signal
Pin Signal
1
+24 V DC
1
+24 V
2
GND (0 V)
2
not conneced
3
GND
4
IO-Link-Data
Cable length
For IO-Link operation, the maximum cable length between
base unit and sensor is 20 meters.
The maximum length for the LAN cable is 30 meters.