ROBLEM 

POSSIBLE CAUSE 

SOLUTION 

Water leakage 

Rubber plug at the rear plate of the machine 
is out of place. 

Water tube inside the machine is not in the 
place or broken. 
Water tube is of bad connection or broken. 
 

Put back the rubber plug. 
 
Check and reinstall or replace the water 
tube inside the machine. 
Check or replace the water tube. 

Weak cooling 

Dusty filter 
Dusty condenser. 
 
 
 
Air vent is blocked. 
The room temperature is too high. 
 
Too many windows or doors are open. 
Insufficient refrigerant or the refrigerant leaks 
out.. 
HEAT PUMP is broken. 
 

Clean the filter. 
Use a high pressure air spray to clean 
the dust. *Do not touch the condenser 
directly, it is very hot now. 
Remove the blockade. 
It’s out of the working range of the 
machine. 
Close the windows/doors. 
Please check: 
Is the current/power consumption 
decreasing? 
Is the suction pressure of the machine 
too low? 
Is the temperature of the discharging 
tube too high? 
Is the suction tube frozen in ambient 
temperature? 
7.    Replace the heat pump. 

Machine does not 
work at all. 

Bad connection of the mains and plug. 
P.C. Board fused. 
P.C. Board or transformer breaks down. 
Bad connection of the wires. 
 

Re-plug the power cord. 
Check and replace. 
Check and replace. 
Check and replace. 

Compressor doesn’t 
work, only the fan to 
circulate the air. 

Voltage/Frequency is too low. 
Overload protector of compressor breaks 
down. 
Compressor capacitor breaks down. 
Compressor breaks down. 
P.C. board breaks down. 
Room temperature is too low. 
 

Check it by a voltmeter. 
Check and replace. 
 
Check and replace. 
Check and replace. 
Check and replace. 
It is out of the working range of the 
machine. 

 
1

Содержание AC-N006R

Страница 1: ...Service Manual AC N006R AC N006RH AC T006R AC T006RH...

Страница 2: ...working range of the machine Close the windows doors Please check Is the current power consumption decreasing Is the suction pressure of the machine too low Is the temperature of the discharging tube...

Страница 3: ...bes Motor doesn t work Wires problem Loose terminal connection Motor breaks down Motor capacitor breaks down The fan blade is stuck Check and replace Check and fasten Check and replace Check and repla...

Страница 4: ...within 3g Re switch the unit after the temperature drops down Discharge temperature is too high Refrigerant is too less or has been leaked Condenser too dusty Air return of the condenser is blocked A...

Страница 5: ...ssories wires screws in the opposite steps REPLACING THE OVERLOAD PROTECTOR OF THE COMPRESSOR Take off the accessories for the overload protector Take off the defect overload protector and replace it...

Страница 6: ...l in the opposite steps REPLACING THE DOWN MOTOR CAPACITOR FOR CONDENSOR Take off the rear plate of the machine Take off the wires for the capacitor then take off the capacitor Replace with a new one...

Страница 7: ...the motor and fan blade of the evaporator Replacing the defect fan blade Re install in the opposite steps REPLACING THE PUMP MOTOR Take off the front rear plates Unfasten the wires for the pump motor...

Страница 8: ...ccording to the supplied diagram Make sure the pipes tubes are in the right position do not hit with the other parts Make sure the insulation resistance between the plug and grounding is over 2M Make...

Отзывы: